New Product News
Solid-state Timers
H3DK
DIN Track-mounted, 22.5-mm-width
Standard Timer Series
A wide AC/DC power supply range (24 to 240 VAC/DC).*1
All sub-series include models with 12-VDC power supply.*1
G-type Models (H3DK-G) now include model with 240 to 440-
VAC power supply.
•UL*
2, CSA*3, and CCC certification and EN 61812-1 compliance.
CE Marking.
EMC (EN 61812-1) compliance for application in heavy industri-
al, residential, commercial, or light industrial environments.
Finger-safe terminal block and captive screws according to EN 50274.
*1. Except for the H3DK-H.
*2. Except for the H3DK-GE.
*3. Scheduled to obtain certification in April 2012.
LR
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Model Number Structure
The Entire H3DK Series
Model Number Legend (Not all models that can be represented with the model number legend can necessarily be produced.)
H3DK Series
H3DK-M/-S Multi-range,
Multi-mode Timers
Eight-mode Timer
H3DK-M1/M2
Operating Modes
A: ON Delay
B: Flicker OFF Start
B2: Flicker ON Start
C: Signal ON/OFF Delay
D: Signal OFF Delay
E: Interval
G: Signal ON/OFF Delay
J: One-shot Output
Four-mode Timer
H3DK-S1/S2
Operating Modes
A: ON Delay
B2: Flicker ON Start
E: Interval
J: One-shot Output
H3DK-F
Twin Timers
H3DK-H Power
OFF-delay Timers
H3DK-G
Star-delta Timers
Operating Modes
Power OFF-delay
Timer
Operating Modes
Star-delta Timer
Operating Modes
Flicker-OFF Start/
Flicker-ON Start
Page 2 Page 11 Page 15 Page 21
1234
H3DK-@@@@
1. Type 2. Control Output
* M- and S-type models only.
3. Supply Voltage
*1 H-type models only.
*2 G-type models only.
4. Time Ranges (H-type
Models Only)
Symbol Meaning
M Eight-mode Timer
S Four-mode Timer
F Twin Timer
G Star-delta Timer
H Power OFF-delay Timer
Symbol Meaning
1 SPDT
2DPDT
Symbol Meaning
Blank 24 to 240 VAC/DC
A12 VDC
B 24 to 48 VAC/DC
C *1 100 to 120 VAC
D *1 200 to 240 VAC
E *1 240 to 440 VAC *2
Symbol Meaning
S 0.1 to 1.2 s or 1 to 12 s
L 1 to 12 s or 10 to 120 s
2
New Product News
Multi-range, Multi-mode Timer
H3DK-M/H3DK-S
Multiple time ranges and operating modes let you cover a wide
range of applications.
The time-limit DPDT output contacts can be changed to time-limit
SPDT and instantaneous SPDT output contacts using a switch.
Sequence checks are easily performed by setting an instanta-
neous output to 0.
Start signal control for the H3DK-M.
LR
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Ordering Information
List of Models
Accessories (Order Separately)
Model Structure
Supply voltage Control output Eight-mode Timer Four-mode Timer
24 to 240 VAC/DC
Contact output, DPDT (time-limit DPDT, or time-limit
SPDT + instantaneous SPDT)
Changed using a switch.
Model H3DK-M2 H3DK-S2
Contact output, SPDT (time-limit SPDT) Model H3DK-M1 H3DK-S1
12 VDC
Contact output, DPDT (time-limit DPDT, or time-limit
SPDT + instantaneous SPDT)
Changed using a switch.
Model H3DK-M2A H3DK-S2A
Contact output, SPDT (time-limit SPDT) Model H3DK-M1A H3DK-S1A
Item Specification Model
Mounting Track
50 cm (l) x 7.3 mm (t) PFP-50N
1 m (l) x 7.3 mm (t) PFP-100N
1 m (l) x 16 mm (t) PFP-100N2
End Plate --- PFP-M
Spacer --- PFP-S
Model Operating modes Terminal block Input type Output type Mounting method Safety standards Accessories
H3DK-M2
A: ON Delay
B: Flicker OFF start
B2: Flicker ON start
C: Signal ON/OFF Delay
D: Signal OFF Delay
E: Interval
G: Signal ON/OFF Delay
J: One-shot Output
9 terminals
Voltage input
Relay, DPDT
DIN Track mounting
cURus (UL 508
CSA C22.2 No. 14)
EN 61812-1
IEC 60664-1 4 kV/2
EN 50274
User label
H3DK-M1 Relay, SPDT
H3DK-S2 A: ON Delay
B2: Flicker ON start
E: Interval
J: One-shot Output
---
Relay, DPDT
H3DK-S1 6 terminals Relay, SPDT
H3DK-M/H3DK-S
3
Specifications
Time Ranges
Ratings
Time range setting 0.1 s 1 s 10 s 1 min 10 min 1 h 10 h 100 h
Set time range 0.1 to 1.2 s 1 to 12 s 10 to 120 s 1 to 12 min 10 to 120 min 1 to 12 h 10 to 120 h 100 to 1,200 h
Scale numbers 12
Power supply voltage *1 24 to 240 VAC/DC, 50/60 Hz *2
12 VDC *2
Allowable voltage fluctuation
range
24 to 240 VAC/DC: 85% to 110% of rated voltage
12 VDC: 90% to 110% of rated voltage
Power reset Minimum power-OFF time: 0.1 s
Reset voltage 10% of rated voltage
Voltage input
24 to 240 VAC/DC
High level: 20.4 to 264 VAC/DC, Low level: 0 to 2.4 VAC/DC
12 VDC
High level: 10.8 to 13.2 VDC, Low level: 0 to 1.2 VDC
*3
Power con-
sumption
H3DK-M2/-S2 At 240 VAC: 6.6 VA max. *4
H3DK-M1/-S1 At 240 VAC: 4.5 VA max. *4
H3DK-M2A/-S2A At 12 VDC: 0.9 W max.
H3DK-M1A/-S1A At 12 VDC: 0.6 W max.
Control output
Contact output: 5 A at 250 VAC with resistive load (cosφ = 1),
5 A at 30 VDC with resistive load *5,
0.15 A max. at 125 VDC with resistive load,
0.1A at 125 VDC with L/R of 7 ms.
The minimum applicable load is 10 mA at 5 VDC (P reference value).
Contact materials : Ag-alloy + Gold plating
Ambient operating temperature 20 to 55°C (with no icing)
Storage temperature 40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%
*1. When using a 24-VDC power supply voltage, there
will be an inrush current of approximately 0.25 A.
Allow for this inrush current when turning ON and
OFF the power supply to the Timer with device with
a solid-state output, such as a sensor.
*2. DC ripple: 20% max.
*3. The power consumption is for mode A after the
Timer times out.
For the H3DK-M@, the maximum power consump-
tion is given, including the current consumed by the
input circuit.
*4. Refer to DC Power Consumptions (Reference In-
formation) on page 27 for DC power consumptions.
*5. The control output ratings are for one H3DK oper-
ating alone. If you operate two or more Timers side
by side, refer to Installation Pitch and Output
Switching Capacity (Reference Values) on the next
page.
H3DK-M/H3DK-S
4
Characteristics
I/O
*If the INST/TIME switch on the front of the Timer is set to INST on the H3DK-M2/-S2, relay R2 will
operate as instantaneous contacts and will turn ON/OFF in synchronization with the power supply.
Item Model H3DK-M1/-M2 H3DK-S1/-S2
Input Start Functions to start timing. There is no start input.
Output
Control
output
The output is turned ON/OFF according to the operating mode when the value
that is set on the dial is reached. *
0 1 2 3 4 5 6
80
70
60
50
40
30
20
10
d = 5 mm
d=0 mm
d = 10 mm
d = 50 mm
Ambient temperature (°C)
Maximum ambient operating
temperature in specifications
Load current (A)
DIN Track Timer installation pitch: d
Tested Timer: H3DK-M/-S
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
Test
timer
1
Test
timer
2
Test
timer
3
Test
timer
4
Test
timer
5
Testing Method
+100 ms
50 ms
H3DK-M/H3DK-S
5
Connections
Block Diagrams
H3DK-M1/-M2
H3DK-S1/-S2
Output circuit
RAMROM
Indicator circuitInput circuit
Power supply circuit
AC (DC) input
Start input
Power
indicator
Output
indicator
Time setting
detection circuit
Time specification
switches
Operating mode
switch
One-chip microcomputer
Clock
Output circuit
Indicator circuit
Power supply circuit
AC (DC) input
Power
indicator
Output
indicator
Time setting
detection circuit
Time specification
switches
Operating
mode switch
RAMROM
One-chip microcomputer
Clock
H3DK-M/H3DK-S
6
Terminal Arrangement
Input Connections
The start input of the H3DK-M1/-M2 is a voltage input.
A1 15
B1
A2
1816
A1 15
25/21
B1
26/2228/24
A2
1816
A1 15
25/21
26/2228/24
A2
1816
A1 15
A2
1816
15
R1
1618
15
R1
1618
25/21
R2
*
26/2228/24
15
R1
1618
15
R1
1618
25/21
R2
*
26/2228/24
H3DK-M1 H3DK-M2 H3DK-S1 H3DK-S2
Start
See note 3.
(DIN notation) (DIN notation) (DIN notation) (DIN notation)
Start
See note 3. See note 3. See note 3.
A2
A1 15
1816
B1
A2
A1 15
1816
B1
(21)
25
28
(24)
26
(22)
A2
A1 15
1816 A2
A1 15
1816
(21)
25
28
(24)
26
(22)
Note 1: The time-limit contact symbol for previous models of Timers was . The time-limit contact symbol for the H3DK is . A different symbol is
used because the H3DK supports multiple operating modes.
Note 2: *The relay R2 can be set to either instantaneous or time-limit contacts using the switch on the front of the Timer.
Note 3: The power supply terminals do not have polarity.
Sensor Timer
A1 (+)
A2 ()
B1
Start
24
VDC
24 VDC
(sensor
power supply)
(+)
()
Sensor
Timer
A1 ()
A2 (+)
B1
Start
24
VDC
()
(+)
Timer
A1
A2
B1
Start
Operates when PNP transistor turns ON. Operates when NPN transistor turns ON. Operates when relay turns ON.
24 VDC
(sensor
power supply)
H3DK-M/H3DK-S
7
Nomenclature
*If the switch is left between settings, proper operation may not be possible.
Make sure that the switch is set properly.
Note: The default settings are for 0.1 s in mode A.
Terminal Block
(See notes 1 and 2.)
Bottom ViewFront View
Time range switch
Operating mode switch
Output indicator (orange)
(Lit while Timer gives output.)
Operation/power indicator (green)
(Lit while the power is ON.)
INIT/TIME switch for relay R2
(Default setting is for time-limit
output.)*
Main dial (for
setting the time)
User label
attachment location
Note 1. Use solid wire (2.5 mm2 max.) or fer-
rules with insulative sleeves to connect
to the terminals.
To maintain the withstand voltage after
connecting the terminals, insert no
more than 8 mm of exposed conductor
into the terminal.
Recommended Ferrules
Phoenix Contact
•AI@@@ Series
•AI-TWIN@@@ Series
Note 2. Screw Tightening Torque
Recommended torque: 0.49 N·m
Maximum torque: 0.98 N·m
8 mm max. 8 mm max.
Using Solid Wire
(2.5 mm
2
Max.)
Using Ferrule with
Insulative Sleeve
H3DK-M2
H3DK-S2
User label attachment
location
Main dial
(for setting the time)
Front View
Time range switch
Output indicator (orange)
(Lit while Timer gives output.)
Operation/power indicator (green)
(Lit while the power is ON.)
Operating mode switch
*If the switch is left between settings, proper operation may not be possible.
Make sure that the switch is set properly.
Note: The default settings are for 0.1 s in mode A.
User label attachment
location
Main dial
(for setting the time)
Front View
Time range switch*
Output indicator (orange)
(Lit while Timer gives output.)
Operation/power indicator (green)
(Lit while the power is ON.)
Operating mode switch*
*If the switch is left between settings, proper operation may not be possible.
Make sure that the switch is set properly.
Note: The default settings are for 0.1 s in mode A.
H3DK-M1 H3DK-S1
H3DK-M/H3DK-S
8
Dimensions (Unit: mm)
Timers
Track Mounting Products (Sold Separately)
Refer to page 28 for details.
Operating Procedures
Basic Operation
Setting Switches
Each switch has a snap mechanism that secures the switch at given positions. Set the switch to one of these positions.
Do not set it midway between two positions. Malfunction could result from an improper setting.
89.4
100
88.2
22.522.5 69.1
79
H3DK-M2
H3DK-S2
H3DK-M1
65.6 52
4
22.5
H3DK-S1
Operating
mode switch
INIT/TIME
switch
Time range
switch
H3DK-M/H3DK-S
9
Timing Charts
There is no start input with the H3DK-S. Timer operation starts when the power is turned ON.
There is no instantaneous output with the H3DK-@1.
Note 1.The reset time is 0.1 s min. Make sure the signal input time is 0.05 s or longer.
Note 2.“t” is the set time. “ta” is a time that is less that the set time.
A: ON Delay
B: Flicker OFF Start
B2: Flicker ON start
C: Signal ON/ OFF Delay
tt−a t
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24)
Power indicator
Power
*
Start input
Output
Timing
**
* For power ON-delay operation, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is ignored while the Timer is in
operation.
Basic Operation
tt ttt
t−a t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24)
Power indicator
Power
*
Start input
Output
Timing
**
* To start with the power supply, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is ignored while the Timer is in
operation.
TimingTiming
Timing
Basic Operation
tt ttt
t−a t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24)
Power indicator
Power
*
Start input
Output
Timing
**
* To start with the power supply, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is ignored while the Timer is in
operation.
TimingTiming
Timing
Basic Operation
tttt
t−a t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24)
Power indicator
Power
*
Start input
Output
Timing
* The start input is valid while the Timer is in
operation.
Timing
Timing
Timing
Basic Operation
H3DK-M/H3DK-S
10
Note 1.The reset time is 0.1 s min. Make sure the signal input time is 0.05 s or longer.
Note 2.“t” is the set time. “ta” is a time that is less that the set time.
D: Signal OFF delay
E: Interval
G: Signal ON/ OFF Delay
J: One-shot Output (ON delay)
tt
t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24)
Power indicator
t−a t−a
Power
*
Start input
Output
* The start input is valid while the Timer is in
operation.
Timing
Basic Operation
tt t
t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24)
Power indicator
t−a
Power
*
Start input
Output
Timing
**
* For power ON-delay operation, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is valid while the Timer is in
operation.
Basic Operation
tttt
t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24)
Power indicator
t−a
Power
Start input
Output
*
* The start input is valid while the Timer is in
operation.
Timing
Timing
Timing
Timing
Basic Operation
tt t
1 s±0.6 s
(fixed)
1 s±0.6 s
(fixed)
1 s±0.6 s
(fixed)
t−a
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24)
Power indicator
t−a
Power
*
Start input
Output
Timing
**
* To start with the power supply, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is valid while the Timer is in
operation.
1 s±0.6 s
(fixed)
Basic Operation
11
New Product News
Twin Timer
H3DK-F
Switch between flicker-OFF or flicker-ON start mode.
Independent ON time and OFF time settings.
Eight time ranges from 0.1 s to 1,200 h.
LR
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Ordering Information
List of Models
Accessories (Order Separately)
Model Structure
Specifications
Time Ranges
Ratings
Operating modes Supply voltage Control output H3DK-F
Flicker OFF start/flicker ON start 24 to 240 VAC/DC Contact output: SPDT Model H3DK-F
12 VDC Contact output: SPDT Model H3DK-FA
Item Specification Model
Mounting Track
50 cm (l) x 7.3 mm (t) PFP-50N
1 m (l) x 7.3 mm (t) PFP-100N
1 m (l) x 16 mm (t) PFP-100N2
End Plate --- PFP-M
Spacer --- PFP-S
Model Operating modes Terminal block Output type Mounting method Safety standards Accessories
H3DK-F Flicker OFF start/flicker ON
start 6 terminals Relay, SPDT DIN Track mounting
cURus
(UL508
CSA C22.2 No. 14)
EN 61812-1
IEC 60664-1 4 kV/2
EN 50274
User label
Time range setting 0.1 s 1 s 10 s 1 min 10 min 1 h 10 h 100 h
Set time range 0.1 to 1.2 s 1 to 12 s 10 to 120 s 1 to 12 min 10 to 120 min 1 to 12 h 10 to 120 h 100 to 1,200 h
Scale numbers 12
Power supply voltage *1 24 to 240 VAC/DC, 50/60 Hz *2
12 VDC *2
Allowable voltage fluctuation range 24 to 240 VAC/DC: 85% to 110% of rated voltage
12 VDC: 90% to 110% of rated voltage
Power reset Minimum power-OFF time: 0.1 s
Reset voltage 10% of rated voltage
Power consumption H3DK-F At 240 VAC: 4.5VA max. *3
H3DK-FA At 12 VDC: 0.6 W max.
Control output
Contact output: 5 A at 250 VAC with resistive load (cosφ = 1),
5 A at 30 VDC with resistive load *4,
0.15 A max. at 125 VDC with resistive load,
0.1 A at 125 VDC with L/R of 7 ms.
The minimum applicable load is 10 mA at 5 VDC (P reference value).
Contact materials : Ag-alloy + Gold plating
H3DK-F
12
*1. When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.25 A. Allow for this inrush current when turning ON and OFF the
power supply to the Timer with device with a solid-state output, such as a sensor.
*2. DC ripple: 20% max.
*3. Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
*4. The control output ratings are for one H3DK operating alone. If you operate two or more Timers side by side, refer to Installation Pitch and Output Switching Capacity
(Reference Values) on the next page.
Characteristics
Ambient operating temperature 20 to 55°C (with no icing)
Storage temperature 40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%
0 1 2 3 4 5 6
80
70
60
50
40
30
20
10
d = 5 mm
d
= 0 mm
d = 10 mm
d = 50 mm
Ambient temperature (°C)
Maximum ambient operating
temperature in specifications
Load current (A)
DIN Track Timer installation pitch: d
Tested Timer: H3DK-F
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
Test
timer
1
Test
timer
2
Test
timer
3
Test
timer
4
Test
timer
5
Testing Method
H3DK-F
13
Connections
Nomenclature
Block Diagrams
H3DK-F
AC (DC)
input
ON
indicator
OFF
indicator
One-chip microcomputer
Output circuit
Indicator
circuit
RAMROM Clock
ON/OFF start switch
Power supply
circuit
Time
specification
switches
ON/OFF time setting
detection circuit
Terminal Arrangement
H3DK-F
Note: The power supply terminals do not have po-
larity.
A1 15
A2
1816
15
R1
1618
A2
A1 15
1816
(DIN notation)
Terminal Block
(See notes 1 and 2.)
ON time range switch
Bottom ViewFront View
ON time setting dial
(Sets the ON time.)
OFF time setting dial
(Sets the OFF time.)
ON output
indicator (orange)
OFF output
indicator (green)
OFF time range switch
ON/OFF start switch
(Default setting is for
an OFF start.)
User label
attachment location
H3DK-F
Note 1. Use solid wire (2.5 mm2 max.) or fer-
rules with insulative sleeves to connect
to the terminals.
To maintain the withstand voltage after
connecting the terminals, insert no
more than 8 mm of exposed conductor
into the terminal.
Recommended Ferrules
Phoenix Contact
•AI@@@ Series
•AI-TWIN@@@ Series
Note 2. Screw Tightening Torque
Recommended torque: 0.49 N·m
Maximum torque: 0.98 N·m
8 mm max. 8 mm max.
Using Solid Wire
(2.5 mm
2
Max.)
Using Ferrule with
Insulative Sleeve
H3DK-F
14
Dimensions (Unit: mm)
Timers
Track Mounting Products (Sold Separately)
Refer to page 28 for details.
Operating Procedures
Basic Operation
Timing Charts
Note 1. The reset time is 0.1 s min.
Note 2. When power is supplied in flicker ON start mode, the OFF indicator lights momentarily. This, however, has no effect on the performance of the Timer.
89.4
100
88.2
22.5 69.1
79 65.6 52
4
H3DK-F
OFF time range
switch
ON time range
switch
ON/OFF start
switch
ON time setting dial
OFF time setting dial
Flicker OFF start Flicker ON start
tONtOFF tOFFtOFFtOFF
tON
tON: ON set time
tOFF: OFF set time
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Power (A1 and A2)
ON indicator (15 and 18)
OFF indicator (15 and 16)
0.1 s min.
Output (15 and 18)
tOFF tOFF
tONtONtONtON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
tON: ON set time
tOFF: OFF set time
Power (A1 and A2)
ON indicator (15 and 18)
OFF indicator (15 and 16)
0.1 s min.
Output (15 and 18)
15
New Product News
Set two time ranges between 1 and 120 s with one Timer.
Models with 240 to 440-VAC power supply added to series.
LR
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Ordering Information
List of Models
Accessories (Order Separately)
Model Structure
*1. Except for the H3DK-GE.
Specifications
Time Ranges
Ratings
Operating modes Supply voltage Control output H3DK-G
Star-delta Timer
24 to 240 VAC/DC Contact outputs
Delta circuit: SPDT, Star circuit: SPDT
Model H3DK-G
12 VDC Model H3DK-GA
240 to 440 VAC Model H3DK-GE
Item Specification Model
Mounting Track
50 cm (l) x 7.3 mm (t) PFP-50N
1 m (l) x 7.3 mm (t) PFP-100N
1 m (l) x 16 mm (t) PFP-100N2
End Plate --- PFP-M
Spacer --- PFP-S
Model Terminal block Operating/resetting method Output type Mounting method Safety standards Accessories
H3DK-G 9 terminals Time-limit operation/self-
resetting
Time-limit (relay)
Star circuit: SPDT
Delta circuit: SPDT
DIN Track mounting
cURus*1
(UL 508
CSA C22.2 No. 14)
EN 61812-1
IEC 60664-1 4 kV/2
EN 50274
User label
Time range setting t1x1 t1x10
Star set time (t1) range 1 to 12 s 10 to 120 s
Star-Delta transfer time (t2) Select from 0.05, 0.1, 0.25, or 0.5 s.
H3DK-G, -GA H3DK-GE
Power supply voltage *1 24 to 240 VAC/DC, 50/60 Hz *2
12 VDC *2 240 to 440 VAC (50/60 Hz) *5
Allowable voltage fluctuation range 24 to 240 VAC/DC: 85% to 110% of rated voltage
12 VDC: 90% to 110% of rated voltage 80 % to 110% of rated voltage
Power reset Minimum power-OFF time: 0.5 s
Reset voltage 10% of rated voltage
Power consumption H3DK-G At 240 VAC: 6.6 VA max. *3
At 440 VAC: 34 VA max.
H3DK-GA At 12 VDC: 0.9 W max.
Star-delta Timer
H3DK-G
H3DK-G
16
*1. When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.25 A. Allow for this inrush current when turning ON and OFF the
power supply to the Timer with device with a solid-state output, such as a sensor.
*2. DC ripple: 20% max.
*3. Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
*4. The control output ratings are for one H3DK operating alone. If you operate two or more Timers side by side, refer to Installation Pitch and Output Switching Capacity
(Reference Values) on the next page.
*5. For the H3DK-GE, approx. 6 A of inrush current will flow when the power supply is turned ON. When selecting the device connected to the Timer, allow leeway in
the current ratings.
Characteristics
Control output
Contact output (Time-limit output: relay, Star output:
SPDT, Delta output: SPDT):
5 A at 250 VAC with resistive load (cos
φ
= 1),
5 A at 30 VDC
with
resistive load *3, *4
0.15 A max at 125 VDC with resistive load,
0.1 A at 125 VDC with L/R of 7 ms.
The minimum applicable load is 10 mA at 5 VDC (P
reference value).
Contact materials : Ag-alloy + Gold plating
Contact output: Ith 2 A
1.5 A at 120 VAC with AC-15,
1 A at 240 VAC with AC-15,
0.3 A at 440 VAC with AC-15,
Contact materials : Ag-alloy + Gold plating
Ambient operating temperature 20 to 55°C (with no icing)
Storage temperature 40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%
H3DK-G, -GA H3DK-GE
0 1 2 3 4 5 6
80
70
60
50
40
30
20
10
d = 5 mm
d = 0 mm
d = 10 mm
d = 50 mm
Ambient temperature (°C)
Maximum ambient operating
temperature in specifications
Load current (A)
DIN Track Timer installation pitch: d
Tested Timer: H3DK-G
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
Test
timer
1
Test
timer
2
Test
timer
3
Test
timer
4
Test
timer
5
Testing Method