Miniature
circuit breakers
Low Voltage Products & Systems 15.1
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
S200
UL 489 Series
Description
The S200 Series miniature circuit breaker
offers a compact solution for protection
requirements. The S200U AND S200UP
devices are UL 489 tested current limiting and
DIN rail mounted.
The S200U and S200UP is available with
application-specific trip characteristics to
provide maximum circuit protection.
The breakers offer thermal-magnetic
trip protection according to K and Z
characteristics.
For the worldwide market, the breakers carry
UL, CSA, IEC, CE and many other agency
approvals and certifications.
Features
UL current limiting
Fast breaking time (2.3 – 2.5 ms)
Bus connection system
Wide range of accessories
Available with variable depth handle
mechanism
CE certified and marked
DIN rail mounting
Finger safe terminals
Multi-function terminals
Suitable for reverse feed
UL 489 Listed - branch circuit protective
device. UL File #E212323
Miniature Circuit Breakers
Miniature Circuit Breakers
S200U S200UP S201DC
Amperage 0.2 – 63 0.2 – 25 1 – 25
Voltage 240 VAC 480Y/277VAC 60 VDC
Poles
1, 2, 3, 4 1, 2, 3, 4 1
Trip
characteristics K, Z K, Z K, Z
Interrupting
ratings
Up to 25 kA : IEC 60947-2
10 kA : UL 489
10 kA : CSA 22.2 No. 5
Up to 25 kA : IEC 60947-2
10 kA : UL 489
10 kA : CSA 22.2 No. 5
14 kA : UL489
Auxiliary
contacts Yes Yes Yes
Bell alarm Yes Yes Yes
Shunt trip Yes Yes Yes
Bus bar Yes Yes Yes
S200 UL 489 Series
Miniature
circuit breakers
15.2 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
No. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
K
1
0.2 S201U-K0.2
$ 38
3
0.2 S203U-K0.2
$ 137
0.3 S201U-K0.3 0.3 S203U-K0.3
0.5 S201U-K0.5 0.5 S203U-K0.5
0.75 S201U-K0.75 0.75 S203U-K0.75
1 S201U-K1 1 S203U-K1
1.6 S201U-K1.6 1.6 S203U-K1.6
2 S201U-K2 2 S203U-K2
3 S201U-K3 3 S203U-K3
4 S201U-K4 4 S203U-K4
5 S201U-K5 5 S203U-K5
6 S201U-K6 6 S203U-K6
8 S201U-K8 8 S203U-K8
10 S201U-K10 10 S203U-K10
15 S201U-K15 15 S203U-K15
16 S201U-K16 16 S203U-K16
20 S201U-K20 20 S203U-K20
25 S201U-K25 25 S203U-K25
30 S201U-K30 41 30 S203U-K30 137
32 S201U-K32 43 32 S203U-K32 141
40 S201U-K40 45 40 S203U-K40 146
50 S201U-K50 50 50 S203U-K50 155
60 S201U-K60 54 60 S203U-K60 166
63 S201U-K63 59 63 S203U-K63 171
2
0.2 S202U-K0.2
91
4
0.2 S204U-K0.2
194
0.3 S202U-K0.3 0.3 S204U-K0.3
0.5 S202U-K0.5 0.5 S204U-K0.5
0.75 S202U-K0.75 0.75 S204U-K0.75
1 S202U-K1 1 S204U-K1
1.6 S202U-K1.6 1.6 S204U-K1.6
2 S202U-K2 2 S204U-K2
3 S202U-K3 3 S204U-K3
4 S202U-K4 4 S204U-K4
5 S202U-K5 5 S204U-K5
6 S202U-K6 6 S204U-K6
8 S202U-K8 8 S204U-K8
10 S202U-K10 10 S204U-K10
15 S202U-K15 15 S204U-K15
16 S202U-K16 16 S204U-K16
20 S202U-K20 20 S204U-K20
25 S202U-K25 25 S204U-K25
30 S202U-K30 91 30 S204U-K30 194
32 S202U-K32 93 32 S204U-K32 194
40 S202U-K40 100 40 S204U-K40 202
50 S202U-K50 105 50 S204U-K50 205
60 S202U-K60 114 60 S204U-K60 211
63 S202U-K63 123 63 S204U-K63 217
S201U-K
S202U-K
S203U-K
S204U-K
Tripping characteristic K
UL 489
240 VAC
10 kA
Inductive loads
• K Curve
• Designed for allowing higher in-rush
currents during system start up
• Example: motors, transformers
Accessories & technical data
Accessories – See page 15.7
Technical data – See page 15.76 - 15.82
S200U-K, 240 VAC
Branch circuit protection
UL 489, CSA 22.2 No. 5
Note: This breaker for AC use only
Discount schedule CB-17 [BM]
Miniature
circuit breakers
Low Voltage Products & Systems 15.3
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
Z
1
0.5 S201U-Z0.5
$ 54
3
0.5 S203U-Z0.5
$ 182
1 S201U-Z1 1 S203U-Z1
1.6 S201U-Z1.6 1.6 S203U-Z1.6
2 S201U-Z2 2 S203U-Z2
3 S201U-Z3 3 S203U-Z3
4 S201U-Z4 4 S203U-Z4
5 S201U-Z5 5 S203U-Z5
6 S201U-Z6 6 S203U-Z6
8 S201U-Z8 8 S203U-Z8
10 S201U-Z10 10 S203U-Z10
15 S201U-Z15 15 S203U-Z15
16 S201U-Z16 16 S203U-Z16
20 S201U-Z20 20 S203U-Z20
25 S201U-Z25 25 S203U-Z25
30 S201U-Z30 30 S203U-Z30
32 S201U-Z32 57 32 S203U-Z32 185
40 S201U-Z40 61 40 S203U-Z40 189
50 S201U-Z50 68 50 S203U-Z50 196
60 S201U-Z60 75 60 S203U-Z60 205
63 S201U-Z63 80 63 S203U-Z63 212
2
0.5 S202U-Z0.5
121
4
0.5 S204U-Z0.5
274
1 S202U-Z1 1S204U-Z1
1.6 S202U-Z1.6 1.6 S204U-Z1.6
2 S202U-Z2 2S204U-Z2
3 S202U-Z3 3S204U-Z3
4 S202U-Z4 4S204U-Z4
5 S202U-Z5 5S204U-Z5
6 S202U-Z6 6S204U-Z6
8 S202U-Z8 8S204U-Z8
10 S202U-Z10 10 S204U-Z10
15 S202U-Z15 15 S204U-Z15
16 S202U-Z16 16 S204U-Z16
20 S202U-Z20 20 S204U-Z20
25 S202U-Z25 25 S204U-Z25
30 S202U-Z30 30 S204U-Z30
32 S202U-Z32 123 32 S204U-Z32 276
40 S202U-Z40 128 40 S204U-Z40 283
50 S202U-Z50 137 50 S204U-Z50 292
60 S202U-Z60 146 60 S204U-Z60 304
63 S202U-Z63 155 63 S204U-Z63 305
No. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
S204U-Z
S203U-Z
S202U-Z
S201U-Z
S200U-Z, 240 VAC
Branch circuit protection
UL 489, CSA 22.2 No. 5
Tripping characteristic Z
UL 489
240 VAC
10 kA
Resistive loads
• Z Curve
• Designed to provide maximum protection
with a very low short
circuit trip setting
• Example: semiconductors, control circuits
Accessories & technical data
Accessories – See page 15.7
Technical data – See page 15.76 - 15.82
Note: This breaker for AC use only
Discount schedule CB-17 [BM]
Miniature
circuit breakers
15.4 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
K
1
0.2 S201UP-K0.2
3
0.2 S203UP-K0.2
0.3 S201UP-K0.3 0.3 S203UP-K0.3
0.5 S201UP-K0.5 0.5 S203UP-K0.5
0.75 S201UP-K0.75 0.75 S203UP-K0.75
1 S201UP-K1 1 S203UP-K1
1.6 S201UP-K1.6 1.6 S203UP-K1.6
2 S201UP-K2 2 S203UP-K2
3 S201UP-K3 3 S203UP-K3
4 S201UP-K4 $ 61 4 S203UP-K4 $ 219
5 S201UP-K5 5 S203UP-K5
6 S201UP-K6 6 S203UP-K6
8 S201UP-K8 8 S203UP-K8
10 S201UP-K10 10 S203UP-K10
15 S201UP-K15 15 S203UP-K15
16 S201UP-K16 16 S203UP-K16
20 S201UP-K20 20 S203UP-K20
25 S201UP-K25 25 S203UP-K25
2
0.2 S202UP-K0.2
4
0.2 S204UP-K0.2
0.3 S202UP-K0.3 0.3 S204UP-K0.3
0.5 S202UP-K0.5 0.5 S204UP-K0.5
0.75 S202UP-K0.75 0.75 S204UP-K0.75
1 S202UP-K1 1 S204UP-K1
1.6 S202UP-K1.6 1.6 S204UP-K1.6
2 S202UP-K2 2 S204UP-K2
3 S202UP-K3 3 S204UP-K3
4 S202UP-K4 162 4 S204UP-K4 301
5 S202UP-K5 5 S204UP-K5
6 S202UP-K6 6 S204UP-K6
8 S202UP-K8 8 S204UP-K8
10 S202UP-K10 10 S204UP-K10
15 S202UP-K15 15 S204UP-K15
16 S202UP-K16 16 S204UP-K16
20 S202UP-K20 20 S204UP-K20
25 S202UP-K25 25 S204UP-K25
No. of
poles
Rated
current Catalog number List prices No. of
poles
Rated
current Catalog number List price
S204UP-K
S203UP-K
S202UP-K
S201UP-K
S200UP-K, 480Y/277 VAC
Branch circuit protection
UL 489, CSA 22.2 No. 5
Tripping characteristic K
UL 489
480Y/277 VAC
10 kA
Inductive loads
• K Curve
• Designed for allowing higher in-rush
currents during system start up
• Example: motors, transformers
Accessories & technical data
Accessories – See page 15.7
Technical data – See page 15.76 - 15.82
Note: This breaker for AC use only
Discount schedule CB-17 [BM]
Miniature
circuit breakers
Low Voltage Products & Systems 15.5
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
Z
1
0.5 S201UP-Z0.5
3
0.5 S203UP-Z0.5
1 S201UP-Z1 1 S203UP-Z1
1.6 S201UP-Z1.6 1.6 S203UP-Z1.6
2 S201UP-Z2 2 S203UP-Z2
3 S201UP-Z3 3 S203UP-Z3
4 S201UP-Z4 4 S203UP-Z4
5 S201UP-Z5 $ 80 5 S203UP-Z5 $ 285
6 S201UP-Z6 6 S203UP-Z6
8 S201UP-Z8 8 S203UP-Z8
10 S201UP-Z10 10 S203UP-Z10
15 S201UP-Z15 15 S203UP-Z15
16 S201UP-Z16 16 S203UP-Z16
20 S201UP-Z20 20 S203UP-Z20
25 S201UP-Z25 25 S203UP-Z25
2
0.5 S202UP-Z0.5
4
0.5 S204UP-Z0.5
1 S202UP-Z1 1 S204UP-Z1
1.6 S202UP-Z1.6 1.6 S204UP-Z1.6
2 S202UP-Z2 2 S204UP-Z2
3 S202UP-Z3 3 S204UP-Z3
4 S202UP-Z4 4 S204UP-Z4
5 S202UP-Z5 212 5 S204UP-Z5 388
6 S202UP-Z6 6 S204UP-Z6
8 S202UP-Z8 8 S204UP-Z8
10 S202UP-Z10 10 S204UP-Z10
15 S202UP-Z15 15 S204UP-Z15
16 S202UP-Z16 16 S204UP-Z16
20 S202UP-Z20 20 S204UP-Z20
25 S202UP-Z25 25 S204UP-Z25
No. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
S204UP-Z
S203UP-Z
S202UP-Z
S201UP-Z
S200UP-Z, 277/480Y/277 VAC
Branch circuit protection
UL 489, CSA 22.2 No. 5
Tripping characteristic Z
UL 489
480Y/277 VAC
10 kA
Resistive loads
• Z Curve
• Designed to provide maximum protection
with a very low short
circuit trip setting
• Example: semiconductors, control circuits
Accessories & technical data
Accessories – See page 15.7
Technical data – See page 15.76 - 15.82
Note: This breaker for AC use only
Discount schedule CB-17 [BM]
Miniature
circuit breakers
15.6 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
1
1 S201DC-K1
1.6 S201DC-K1.6
2 S201DC-K2
3 S201DC-K3
4 S201DC-K4
6 S201DC-K6 $ 36
8 S201DC-K8
10 S201DC-K10
13 S201DC-K13
16 S201DC-K16
20 S201DC-K20
25 S201DC-K25
1
1 S201DC-Z1
1.6 S201DC-Z1.6
2 S201DC-Z2
3 S201DC-Z3
4 S201DC-Z4 38
6 S201DC-Z6
8 S201DC-Z8
10 S201DC-Z10
16 S201DC-Z16
20 S201DC-Z20
25 S201DC-Z25
No. of
poles
Rated
current Catalog number List price
S201DC-K
S201DC, 60 VDC
Branch circuit protection
UL 489, CSA 22.2 No. 5
K, Z
S201DC
60 VDC
Tripping characteristic K
UL 489
60 VDC
14 kA
Inductive loads
• K Curve
• Designed for allowing higher in-rush
currents during system start up
• Example: motors, transformers
Accessories & technical data
Accessories – See page 15.7
Technical data – See page 15.76 - 15.82
Tripping characteristic Z
UL 489
60 VDC
14 kA
Resistive loads
• Z Curve
• Designed to provide maximum protection
with a very low short circuit trip setting
Accessories & technical data
Accessories – See page 15.7
Technical data – See page 15.76 - 15.82
Note: This breaker for DC use only.
S201DC-Z
Discount schedule CB-17 [BM]
Miniature
circuit breakers
Low Voltage Products & Systems 15.7
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
S2C-H6RU
S2C-S6RU
Auxiliary contacts
The auxiliary contacts will signal whether the breaker is in the ON or OFF position.
Description Catalog number List price
For eld mounting: right side S2C-H6RU $ 21
Bell alarm
The bell alarm includes a set of contacts that will only signal when the breaker has tripped.
Typically the contacts would be connected to an alarm or bell to signal the operator that an overcurrent
trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without opening
the breaker.
Description Catalog number List price
For eld mounting: right side S2C-S6RU $ 31
Rotary operating mechanism
Allows “through the door” operation.
Description Catalog number List price
Handle mechanism
S2C-DH $ 71
Shunt trip
For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens
the breaker after control voltage is applied.
Description Catalog number List price
For eld mounting: right side
12…60 VAC/DC S2C-A1U $ 89
For eld mounting: right side
110…415 VAC S2C-A2U 89
110…250 VDC
S2C-A1U
S2C-DH
Possible mounting arrangements of MCB accessories
Accessories
S200U & S200UP
UL 489, CSA 22.2 No. 5
+ST+S/H+S/H (H)+S/H (H)
+ST+H+H+H)
Legend
Auxiliary contact H
Bell alarm/Auxiliary contact S/H
Bell alarm/Auxiliary contact
used as auxiliary contact
S/H (H)
Shunt trip ST
Discount schedule CB-17 [BM]
Miniature
circuit breakers
15.8 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
Approximate dimensions in mm
S200U
Shunt trip
in OFF
position
Connection drawings
Bell alarm S2C-S6RU
Auxiliary contact in ON position
Auxiliary contact in OFF position
Auxiliary contact S2C-H6RU Shunt trip S2C-A...U
In ON and OFF position after hand operation
S2C-A1U
S2C-A2U
In OFF position after tripping
Accessories
S200U, S200UP & S201DC
UL 489, CSA 22.2 No. 5
S2C-H6RU, S2C-S6RU S2C-A..U
S200UP
S201DC
Miniature
circuit breakers
Low Voltage Products & Systems 15.9
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
S200U-UP S2C-A....U
Mounting
Addition of a S2C-H6RU auxiliary contact
Addition of a S2C-S6RU bell alarm contact
Addition of a S2C-A..U shunt trip
Accessories
S200U & S200UP
UL 489, CSA 22.2 No. 5
Miniature
circuit breakers
15.10 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
SZ-BSK
Dimension drawings in mm
BUSBARS MAY BE USED ON BOTH
SIDES OF MCBS
For
use on:
Amp
rating
Number
of poles Phases Busbar length
(mm)
Catalog
number
List
price
S200U
S200UP
S201DC
80
6
12
18
1
1
1
103.2
208.8
314.4
PS 1/6/16BP
PS 1/12/16BP
PS 1/18/16BP
$ 19
30
40
S200U
S200UP
S201DC
80
6
12
18
2
2
2
103.2
208.8
314.4
PS 2/6/16BP
PS 2/12/16BP
PS 2/18/16BP
22
35
50
S200U
S200UP
S201DC
80
6
12
18
3
3
3
103.2
208.8
314.4
PS 3/6/16BP
PS 3/12/16BP
PS 3/18/16BP
25
40
60
UL approved busbars UL file # E250145
UL 489 busbar cannot be cut.
Accessories
S200U & S200UP
UL 489, CSA 22.2 No. 5
Busbar tooth covers
Description Catalog number List price
Covers ve unused poles of Busbar SZ-BSK $ 4
1 Phase
2 Phase
3 Phase
BUSBARS MAY BE CENTER FED IN
ORDER TO INCREASE AMPACITY TO
130 AMPS
Discount schedule CB-17 [BM]
Miniature
circuit breakers
Low Voltage Products & Systems 15.11
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
Technical data S200U S200UP S201DC
Specifications: UL 489, CSA C 22.2 No. 5, IEC 60 947-2 UL 489, VDE 0660
UL File-Number: E 212323, UL, Current limiting series ratings E212323, UL
No. of poles: 1, 2, 3 & 4 1
Tripping characteristics: K, Z K, Z
Rated current: 0.2 (K) 0.5 (Z) ... 63 A 0.2 (K) 0.5 (Z) ... 25 A 1 - 25 A
Rated voltage: Single pole: 240VAC
Multi pole: 240VAC
Single pole: 277VAC
Multi pole: 480Y/277VAC
Short circuit capacity: 10 kA 14 kA
Frequency: 50/60 Hz 50/60 Hz
Degree of protection: IP 20 IP 20
Mounting position: Vertical and horizontal Vertical and horizontal
Fixing: 35 mm DIN rail 35 mm DIN rail
Clamps only for Cu: 18-4 AWG (0.75 … 25 mm2) 18-4 AWG (0.75 … 25 mm2)
Service life, mech. and at rated load: 20,000 operations 10,000 operations
Tightening torque: 25 in. lbs (2.8 Nm) 25 in. lbs (2.8 Nm)
Ambient temperature: – 25 °C … + 55 °C/– 13 °F … + 131 °F – 25 °C … + 55 °C/– 13 °F … + 131 °F
Shock resistance: 30 g at least 2 impacts shock, duration 13 ms
30 g at least 2 impacts shock, duration 13 ms
Auxiliary contact S2C-H6RU and S2C-S6RU
Rated current: 10
Rated voltage AC / DC: 24
Contact: 1 pole double throw
Connection capacity mm218 – 14 AWG (0.75…2.5 mm2)
Tightening torque: 11 in.Ibs (1.2 Nm)
Shock resistance acc. to DIN IEC 68-2-6: 5 g, 20 frequency cycles 5...150...5 Hz at 24 VAC/DC, 5 mA auto-reclosing < 10 ms
Mechanical service life: 10,000 operations
Shunt trip Type S2C-A1U S2C-A2U
Rated voltage AC
DC
V
V
12 ... 60
12 ... 60
110 ... 415
110 ... 250
Max. release duration ms < 10 < 10
Min. release voltage AC
DC
V
V
7
10
55
80
Consumption on release AC
DC
VA
VA
40 ... 200
40 ... 200
55 ... 210
55 ... 110
Coil resistance Ω3.7 225
Terminals AWG/mm218…6 / 0.75 – 16 18…6 / 0.75 – 16
Tightening torque in.Ibs/Nm 18 / 2 18 / 2
Technical data
S200U, S200UP & S201DC
UL 489, CSA 22.2 No. 5
Miniature
circuit breakers
15.12 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
Internal resistance and power loss
Internal resistance per pole in mz, power loss per pole in W.
Type Rated
current
Device series
K
Device series
Z
AmzWmzW
S200U
S200UP
0.2 42500 1.7
0.3 20000 1.8
0.5 6340 1.6 10100 2.5
0.75 2500 1.4
1 1400 1.4 2270 2.3
1.6 625 1.6 1100 2.8
2 460 1.8 619 2.5
3 211 1.9 211 1.9
4 163 2.6 163 2.6
6 67 2.4 104 3.7
8 45 2.9 55 3.5
10 19 1.9 21 2.1
13
16 8.2 2.1 10.9 2.8
20 7.3 2.9 7.3 2.9
25 5.6 3.5 5.6 3.5
32 4.1 4.2 4.1 4.2
40 4.0 6.4 4.0 6.4
50 1.2 3.0 1.8 4.4
63 1.3 5.2 1.3 5.2
Technical data
S200U & S200UP
UL 489, CSA 22.2 No. 5
Miniature
circuit breakers
Low Voltage Products & Systems 15.13
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
K and Z Ambient temperature T (°C/°F)
In (A) – 40/– 40 – 30/– 22 – 20/– 4 – 10/14 0/32 10/50 20/68 30/86 40/104 50/122 60/140 70/158
0.5 0.66 0.64 0.61 0.59 0.56 0.53 0.50 0.47 0.43 0.40 0.35 0.31
1.0 1.32 1.27 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61
1.6 2.12 2.04 1.96 1.88 1.79 1.70 1.60 1.50 1.39 1.26 1.13 0.98
2.0 2.65 2.55 2.45 2.35 2.24 2.12 2.00 1.87 1.73 1.58 1.41 1.22
3.0 4.0 3.8 3.7 3.5 3.4 3.2 3.0 2.8 2.6 2.4 2.1 1.8
4.0 5.3 5.1 4.9 4.7 4.5 4.2 4.0 3.7 3.5 3.2 2.8 2.4
6.0 7.9 7.6 7.3 7.0 6.7 6.4 6.0 5.6 5.2 4.7 4.2 3.7
8.0 10.8 10.2 9.8 9.4 8.9 8.5 8.0 7.5 6.9 6.3 5.7 4.9
10.0 13.2 12.7 12.2 11.7 11.2 10.6 10.0 9.4 8.7 7.9 7.1 6.1
13.0 17.2 16.6 15.9 15.2 14.5 13.8 13.0 12.2 11.3 10.3 9.2 8.0
16.0 21.2 20.4 19.6 18.8 17.9 17.0 16.0 15.0 13.9 12.6 11.3 9.8
20.0 26.5 25.5 24.5 23.5 22.4 21.2 20.0 18.7 17.3 15.8 14.1 12.2
25.0 33.1 31.9 30.6 29.3 28.0 26.5 25.0 23.4 21.7 19.8 17.7 15.3
32.0 42.3 40.8 39.2 37.5 35.8 33.9 32.0 29.9 27.7 25.3 22.6 19.6
40.0 52.9 51.0 49.0 46.9 44.7 42.4 40.0 37.4 34.6 31.6 28.3 24.5
50.0 66.1 63.7 61.2 58.6 55.9 53.0 50.0 46.8 43.3 39.5 35.4 30.6
63.0 83.3 80.3 77.2 73.9 70.4 66.8 63.0 58.9 54.6 49.8 44.5 38.6
Temperature derating
Max. operating current values depending on the ambient temperature for a circuit-breaker of characteristics type K and Z
Tripping characteristic Z (68 °F)
Breaker calibration temperature 68°F
See chart below for temperature DeRating
Tripping characteristic K (68 °F)
Breaker calibration temperature 68°F
See chart below for temperature DeRating
Technical data
S200U & S200UP
UL 489, CSA 22.2 No. 5
Miniature
circuit breakers
15.14 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
Notes
Miniature
circuit breakers
Low Voltage Products & Systems 15.15
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
S200
Supplementary protective devices
UL 1077 Series
Description
The S200 UL 1077 Series miniature
supplementary protector offers a compact
solution for protection requirements. The S200
devices are DIN rail mounted.
The S200 is available with application-specific
trip characteristics to provide maximum circuit
protection.
The supplementary protectors offer thermal-
magnetic trip protection according to B, C, D,
K and Z characteristics.
For the worldwide market, the breakers carry
UL, CSA, IEC, CE and many other agency
approvals and certifications.
Features
Energy limiting
Fast breaking time (2.3 – 2.5 ms)
Bus connection system
Wide range of accessories
Available with variable depth handle
mechanism
CE certified and marked
DIN rail mounting
Finger safe terminals
Multi-function terminals
Suitable for reverse feed
UL1077 Recognized supplemental
protective device. UL file # E76126
S200 Series
S200 S200P S280UC S290
Amperage 0.5 – 63 A 0.2 – 63 A 0.2 – 63 A 80 - 125 A
Voltage 480Y/277 VAC 480Y/277 VAC 250/500 VDC 480Y/277 VAC
Poles
1, 2, 3, 4 1, 2, 3, 4 1, 2, 3, 4 1, 2, 3, 4
Trip
characteristics B, C, D, K K, Z K, Z C
Interrupting
ratings
6 kA : IEC 60898
6 kA : UL 1077
6 kA : CSA 22.2 No. 235
Up to 25kA : IEC 60947-2
10kA : UL 1077
Up to 6kA : IEC 60947-2
10kA : UL 1077
6 kA : CSA 22.2 No. 235
Up to 10 kA: IEC 60947-2
5 kA: UL 1077
6 kA : CSA 22.2 No. 235
Auxiliary
contacts Yes Yes Yes Yes
Bell alarm Yes Yes Yes Yes
Shunt trip Yes Yes Yes Yes
Undervoltage
release Yes Yes Ye s No
Bus bar Yes Yes Yes No
Supplementary protective devices
Miniature
circuit breakers
15.16 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
B
1
6 S201-B6
$ 20
3
6 S203-B6
$ 77
10 S201-B10 10 S203-B10
13 S201-B13 13 S203-B13
16 S201-B16 16 S203-B16
20 S201-B20 20 S203-B20
25 S201-B25 25 S203-B25
32 S201-B32 25 32 S203-B32 82
40 S201-B40 27 40 S203-B40 86
50 S201-B50 34 50 S203-B50 93
63 S201-B63 45 63 S203-B63 100
1
+
NA
6 S201-B6NA
38 3
+
NA
6 S203-B6NA
96
10 S201-B10NA 10 S203-B10NA
13 S201-B13NA 13 S203-B13NA
16 S201-B16NA 16 S203-B16NA
20 S201-B20NA 20 S203-B20NA
25 S201-B25NA 25 S203-B25NA
32 S201-B32NA 45 32 S203-B32NA 100
40 S201-B40NA 52 40 S203-B40NA 107
50 S201-B50NA 57 50 S203-B50NA 114
63 S201-B63NA 64 63 S203-B63NA 121
2
6 S202-B6
52
4
6 S204-B6
105
10 S202-B10 10 S204-B10
13 S202-B13 13 S204-B13
16 S202-B16 16 S204-B16
20 S202-B20 20 S204-B20
25 S202-B25 25 S204-B25
32 S202-B32 57 32 S204-B32 82
40 S202-B40 61 40 S204-B40 86
50 S202-B50 66 50 S204-B50 83
63 S202-B63 70 63 S204-B63 100
No. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
S201-B
S203-BNA
S201-BNA
S203-B
S204-B
S200-B, 480Y/277 VAC
Supplemental protectors
UL 1077, CSA 22.2, No. 235
Tripping characteristic B
UL 1077
480Y/277VAC
6 kA
Resistive loads
• B Curve
• Designed for use in cable protection
applications
• Example: control circuits, lighting
Accessories & technical data
Accessories – See page 15.26
Technical data – See page 15.76 - 15.82
Note: Switching neutral is noted by “NA” in the catalog number.
S202-B
Discount schedule CB-17 [BM]
Miniature
circuit breakers
Low Voltage Products & Systems 15.17
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
C
1
0.5 S201-C0.5
$ 22
3
0.5 S203-C0.5
$ 80
1 S201-C1 1 S203-C1
1.6 S201-C1.6 1.6 S203-C1.6
2 S201-C2 2 S203-C2
3 S201-C3 3 S203-C3
4 S201-C4 4 S203-C4
6 S201-C6 6 S203-C6
8 S201-C8 8 S203-C8
10 S201-C10 10 S203-C10
13 S201-C13 13 S203-C13
16 S201-C16 16 S203-C16
20 S201-C20 20 S203-C20
25 S201-C25 25 S203-C25
32 S201-C32 25 32 S203-C32 84
40 S201-C40 27 40 S203-C40 89
50 S201-C50 29 50 S203-C50 100
63 S201-C63 34 63 S203-C63 109
1
+
NA
0.5 S201-C0.5NA
43 3
+
NA
0.5 S203-C0.5NA
100
1 S201-C1NA 1 S203-C1NA
1.6 S201-C1.6NA 1.6 S203-C1.6NA
2 S201-C2NA 2 S203-C2NA
3 S201-C3NA 3 S203-C3NA
4 S201-C4NA 4 S203-C4NA
6 S201-C6NA 6 S203-C6NA
8 S201-C8NA 8 S203-C8NA
10 S201-C10NA 10 S203-C10NA
13 S201-C13NA 13 S203-C13NA
16 S201-C16NA 16 S203-C16NA
20 S201-C20NA 20 S203-C20NA
25 S201-C25NA 25 S203-C25NA
32 S201-C32NA 32 S203-C32NA
40 S201-C40NA 48 40 S203-C40NA 112
50 S201-C50NA 54 50 S203-C50NA 121
63 S201-C63NA 59 63 S203-C63NA 134
2
0.5 S202-C0.5
52
4
0.5 S204-C0.5
116
1 S202-C1 1 S204-C1
1.6 S202-C1.6 1.6 S204-C1.6
2 S202-C2 2 S204-C2
3 S202-C3 3 S204-C3
4 S202-C4 4 S204-C4
6 S202-C6 6 S204-C6
8 S202-C8 8 S204-C8
10 S202-C10 10 S204-C10
13 S202-C13 13 S204-C13
16 S202-C16 16 S204-C16
20 S202-C20 20 S204-C20
25 S202-C25 25 S204-C25
32 S202-C32 57 32 S204-C32 121
40 S202-C40 61 40 S204-C40 125
50 S202-C50 66 50 S204-C50 144
63 S202-C63 73 63 S204-C63 160
No. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
S202-C
S204-C
S203-C
S201-C
S201-CNA
S203-CNA
S200-C, 480Y/277 VAC
Supplemental protectors
UL 1077, CSA 22.2, No. 235
Tripping characteristic C
UL 1077
480Y/277 VAC
6 kA
Resistive loads
• C Curve
• Designed for use with medium magnetic
start up currents
• Example: lighting, control panels
Accessories & technical data
Accessories – See page 15.26
Technical data – See page 15.76 - 15.82
Note: Switching neutral is noted by “NA” in the catalog
number.
Discount schedule CB-17 [BM]
Miniature
circuit breakers
15.18 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
D
1
0.5 S201-D0.5
3
0.5 S203-D0.5
1 S201-D1 1 S203-D1
1.6 S201-D1.6 1.6 S203-D1.6
2 S201-D2 2 S203-D2
3 S201-D3 3 S203-D3
4 S201-D4 4 S203-D4
6 S201-D6 6 S203-D6
8 S201-D8 8 S203-D8
10 S201-D10 $ 27 10 S203-D10 $ 98
13 S201-D13 13 S203-D13
16 S201-D16 16 S203-D16
20 S201-D20 20 S203-D20
25 S201-D25 25 S203-D25
32 S201-D32 29 32 S203-D32 98
40 S201-D40 34 40 S203-D40 105
50 S201-D50 38 50 S203-D50 114
63 S201-D63 50 63 S203-D63 130
1
+
NA
0.5 S201-D0.5NA
3
+
NA
0.5 S203-D0.5NA
1 S201-D1NA 1 S203-D1NA
1.6 S201-D1.6NA 1.6 S203-D1.6NA
2 S201-D2NA 2 S203-D2NA
3 S201-D3NA 3 S203-D3NA
4 S201-D4NA 4 S203-D4NA
6 S201-D6NA 6 S203-D6NA
8 S201-D8NA 8 S203-D8NA
10 S201-D10NA 57 10 S203-D10NA 139
13 S201-D13NA 13 S203-D13NA
16 S201-D16NA 16 S203-D16NA
20 S201-D20NA 20 S203-D20NA
25 S201-D25NA 25 S203-D25NA
32 S201-D32NA 61 32 S203-D32NA 139
40 S201-D40NA 66 40 S203-D40NA 139
50 S201-D50NA 70 50 S203-D50NA 145
63 S201-D63NA 77 63 S203-D63NA 155
2
0.5 S202-D0.5
4
0.5 S204-D0.5
1 S202-D1 1 S204-D1
1.6 S202-D1.6 1.6 S204-D1.6
2 S202-D2 2 S204-D2
3 S202-D3 3 S204-D3
4 S202-D4 4 S204-D4
6 S202-D6 6 S204-D6
8 S202-D8 8 S204-D8
10 S202-D10 64 10 S204-D10 158
13 S202-D13 13 S204-D13
16 S202-D16 16 S204-D16
20 S202-D20 20 S204-D20
25 S202-D25 25 S204-D25
32 S202-D32 70 32 S204-D32 155
40 S202-D40 105 40 S204-D40 168
50 S202-D50 114 50 S204-D50 178
63 S202-D63 130 63 S204-D63 188
No. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
S202-D
S204-D
S203-D
S201-D
S201-DNA
S203-DNA
S200-D, 480Y/277 VAC
Supplemental protectors
UL 1077, CSA 22.2, No. 235
Tripping characteristic D
UL 1077
480Y/277 VAC
6 kA
Inductive loads
• D Curve
• Designed for allowing higher in-rush
currents during system start up
• Example: motors, transformers
Accessories & technical data
Accessories – See page 15.26
Technical data – See page 15.76 - 15.82
Note: Switching neutral is noted by “NA” in the
catalog number.
Discount schedule CB-17 [BM]
Miniature
circuit breakers
Low Voltage Products & Systems 15.19
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
KNo. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
S201-K
S202-K
S203-K
S204-K
1
0.5 S201-K0.5
$ 27
3
0.5 S203-K0.5
$ 96
1 S201-K1 1 S203-K1
1.6 S201-K1.6 1.6 S203-K1.6
2 S201-K2 2 S203-K2
3 S201-K3 3 S203-K3
4 S201-K4 4 S203-K4
5 S201-K5 5 S203-K5
6 S201-K6 6 S203-K6
8 S201-K8 8 S203-K8
10 S201-K10 10 S203-K10
13 S201-K13 13 S203-K13
15 S201-K15 15 S203-K15
16 S201-K16 16 S203-K16
20 S201-K20 20 S203-K20
25 S201-K25 25 S203-K25
30 S201-K30 30 S203-K30
32 S201-K32 32 32 S203-K32 107
40 S201-K40 36 40 S203-K40 109
50 S201-K50 41 50 S203-K50 125
60 S201-K60 45 60 S203-K60 137
63 S201-K63 50 63 S203-K63 144
1
+
NA
0.5 S201-K0.5NA
59 3
+
NA
0.5 S203-K0.5NA
139
1 S201-K1NA 1 S203-K1NA
1.6 S201-K1.6NA 1.6 S203-K1.6NA
2 S201-K2NA 2 S203-K2NA
3 S201-K3NA 3 S203-K3NA
4 S201-K4NA 4 S203-K4NA
6 S201-K6NA 6 S203-K6NA
8 S201-K8NA 8 S203-K8NA
10 S201-K10NA 10 S203-K10NA
13 S201-K13NA 13 S203-K13NA
16 S201-K16NA 16 S203-K16NA
20 S201-K20NA 20 S203-K20NA
25 S201-K25NA 25 S203-K25NA
32 S201-K32NA 62 32 S203-K32NA 144
40 S201-K40NA 68 40 S203-K40NA 150
50 S201-K50NA 77 50 S203-K50NA 169
63 S201-K63NA 88 63 S203-K63NA 178
2
0.5 S202-K0.5
61
4
0.5 S204-K0.5
132
1 S202-K1 1 S204-K1
1.6 S202-K1.6 1.6 S204-K1.6
2 S202-K2 2 S204-K2
3 S202-K3 3 S204-K3
4 S202-K4 4 S204-K4
5 S202-K5 5 S204-K5
6 S202-K6 6 S204-K6
8 S202-K8 8 S204-K8
10 S202-K10 10 S204-K10
13 S202-K13 13 S204-K13
15 S202-K15 15 S204-K15
16 S202-K16 16 S204-K16
20 S202-K20 20 S204-K20
25 S202-K25 25 S204-K25
30 S202-K30 30 S204-K30
32 S202-K32 70 32 S204-K32 137
40 S202-K40 73 40 S204-K40 146
50 S202-K50 80 50 S204-K50 155
60 S202-K60 98 60 S204-K60 165
63 S202-K63 102 63 S204-K63 171
S201-KNA
S203-KNA
S200-K, 480Y/277 VAC
Supplemental protectors
UL 1077, CSA 22.2, No. 235
Tripping characteristic K
UL 1077
480Y/277 VAC
6 kA
Inductive loads
• K Curve
• Designed for allowing higher in-rush
currents during system start up
• Example: motors, transformers
Accessories & technical data
Accessories – See page 15.26
Technical data – See page 15.76 - 15.82
Note: Switching neutral is noted by “NA” in the
catalog number.
Discount schedule CB-17 [BM]
Miniature
circuit breakers
15.20 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
K
1
0.2 S201P-K0.2
3
0.2 S203P-K0.2
0.3 S201P-K0.3 0.3 S203P-K0.3
0.5 S201P-K0.5 0.5 S203P-K0.5
0.75 S201P-K0.75 0.75 S203P-K0.75
1 S201P-K1 1 S203P-K1
1.6 S201P-K1.6 1,6 S203P-K1,6
2 S201P-K2 2 S203P-K2
3 S201P-K3 3 S203P-K3
4 S201P-K4 4 S203P-K4
6 S201P-K6 $ 54 6 S203P-K6 $ 146
8 S201P-K8 8 S203P-K8
10 S201P-K10 10 S203P-K10
13 S201P-K13 13 S203P-K13
16 S201P-K16 16 S203P-K16
20 S201P-K20 20 S203P-K20
25 S201P-K25 25 S203P-K25
32 S201P-K32 32 S203P-K32
40 S201P-K40 45 40 S203P-K40 157
50 S201P-K50 54 50 S203P-K50 180
63 S201P-K63 64 63 S203P-K63 205
2
0.2 S202P-K0.2
0.3 S202P-K0.3
0.5 S202P-K0.5
0.75 S202P-K0.75
1 S202P-K1
1.6 S202P-K1,6
2 S202P-K2
3 S202P-K3
4 S202P-K4
6 S202P-K6 96
8 S202P-K8
10 S202P-K10
13 S202P-K13
16 S202P-K16
20 S202P-K20
25 S202P-K25
32 S202P-K32 100
40 S202P-K40 107
50 S202P-K50 114
63 S202P-K63 130
No. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
S203P-K
S200P-K, 480Y/277 VAC
Supplemental protectors
UL 1077, CSA 22.2, No. 235
Tripping characteristic K
UL 1077
480Y/277 VAC
10 kA
Inductive loads
• K Curve
• Designed for allowing higher in-rush
currents during system start up
• Example: motors, transformers
Accessories & technical data
Accessories – See page 15.26
Technical data – See page 15.76 - 15.82
S201P-K
S202P-K
Discount schedule CB-17 [BM]
Miniature
circuit breakers
Low Voltage Products & Systems 15.21
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
ZNo. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
1
0.5 S201P-Z0.5
3
0.5 S203P-Z0.5
1 S201P-Z1 1 S203P-Z1
1.6 S201P-Z1.6 1.6 S203P-Z1.6
2 S201P-Z2 2 S203P-Z2
3 S201P-Z3 3 S203P-Z3
4 S201P-Z4 4 S203P-Z4
6 S201P-Z6 6 S203P-Z6
8 S201P-Z8 $ 54 8 S203P-Z8 $ 187
10 S201P-Z10 10 S203P-Z10
16 S201P-Z16 16 S203P-Z16
20 S201P-Z20 20 S203P-Z20
25 S201P-Z25 25 S203P-Z25
32 S201P-Z32 57 32 S203P-Z32 192
40 S201P-Z40 61 40 S203P-Z40 196
50 S201P-Z50 70 50 S203P-Z50 214
63 S201P-Z63 80 63 S203P-Z63 228
2
0.5 S202P-Z0.5
1 S202P-Z1
1.6 S202P-Z1.6
2 S202P-Z2
3 S202P-Z3
4 S202P-Z4
6 S202P-Z6
8 S202P-Z8 102
10 S202P-Z10
16 S202P-Z16
20 S202P-Z20
25 S202P-Z25
32 S202P-Z32 109
40 S202P-Z40 114
50 S202P-Z50 125
63 S202P-Z63 137
S201P-Z
S203P-Z
S200P-Z, 480Y/277 VAC
Supplemental protectors
UL 1077, CSA 22.2, No. 235
S202P-Z
Tripping characteristic Z
UL 1077
480Y/277 VAC
10 kA
Resistive loads
• Z Curve
• Designed to provide maximum
protection with a very low short
circuit trip setting
• Example: semiconductors
Accessories & technical data
Accessories – See page 15.26
Technical data – See page 15.76 - 15.82
Discount schedule CB-17 [BM]
Miniature
circuit breakers
15.22 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
K
No. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
S281-KW
S282-KW
S283-KW
1
0.2 S281-K0.2W
$ 50
3
0.2 S283-K0.2W
$ 215
0.3 S281-K0.3W 0.3 S283-K0.3W
0.5 S281-K0.5W 0.5 S283-K0.5W
0.75 S281-K0.75W 0.75 S283-K0.75W
1 S281-K1W 1 S283-K1W
1.6 S281-K1.6W 1,6 S283-K1,6W
2 S281-K2W 2 S283-K2W
3 S281-K3W 3 S283-K3W
4 S281-K4W 4 S283-K4W
6 S281-K6W 6 S283-K6W
8 S281-K8W 8 S283-K8W
10 S281-K10W 10 S283-K10W
13 S281-K13W 13 S283-K13W
16 S281-K16W 16 S283-K16W
20 S281-K20W 20 S283-K20W
25 S281-K25W 25 S283-K25W
32 S281-K32W 50 32 S283-K32W 215
40 S281-K40W 60 40 S283-K40W 240
50 S281-K50W 70 50 S283-K50W 270
63 S281-K63W 80 63 S283-K63W 300
2
0.2 S282-K0.2W
145
0.3 S282-K0.3W
0.5 S282-K0.5W
0.75 S282-K0.75W
1 S282-K1W
1.6 S282-K1,6W
2 S282-K2W
3 S282-K3W
4 S282-K4W
6 S282-K6W
8 S282-K8W
10 S282-K10W
13 S282-K13W
16 S282-K16W
20 S282-K20W
25 S282-K25W
32 S282-K32W 150
40 S282-K40W 160
50 S282-K50W 170
63 S282-K63W 190
Ring tongue
compatible
S280W-K 480Y/277 VAC
Supplemental protectors, ring tongue
UL 1077, CSA 22.2, No. 235
Tripping characteristic K
UL 1077
480Y/277 VAC
10 kA
Inductive loads
• K Curve
• Designed for allowing higher in-rush
currents during system start up
• Example: motors, transformers
Accessories & technical data
Accessories – See page 15.26
Technical data – See page 15.76 - 15.82
Discount schedule CB-17 [BM]
Miniature
circuit breakers
Low Voltage Products & Systems 15.23
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
KNo. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
S281UC-K
S282UC-K
S283UC-K
1
0,2 S281UC-K0.2
$ 115
3
0.2 S283UC-K0.2
$ 420
0,3 S281UC-K0.3 0.3 S283UC-K0.3
0,5 S281UC-K0.5 0.5 S283UC-K0.5
0,75 S281UC-K0.75 0.75 S283UC-K0.75
1 S281UC-K1 1 S283UC-K1
1,6 S281UC-K1.6 1.6 S283UC-K1.6
2 S281UC-K2 2 S283UC-K2
3 S281UC-K3 3 S283UC-K3
4 S281UC-K4 4 S283UC-K4
6 S281UC-K6 6 S283UC-K6
8 S281UC-K8 8 S283UC-K8
10 S281UC-K10 10 S283UC-K10
16 S281UC-K16 16 S283UC-K16
20 S281UC-K20 20 S283UC-K20
25 S281UC-K25 25 S283UC-K25
32 S281UC-K32 115 32 S283UC-K32 450
40 S281UC-K40 150 40 S283UC-K40 500
50 S281UC-K50 150 50 S283UC-K50 520
63 S281UC-K63 170 63 S283UC-K63 600
2
0,2 S282UC-K0.2
270
0,3 S282UC-K0.3
0,5 S282UC-K0.5
0,75 S282UC-K0.75
1 S282UC-K1
1,6 S282UC-K1.6
2 S282UC-K2
3 S282UC-K3
4 S282UC-K4
6 S282UC-K6
8 S282UC-K8
10 S282UC-K10
16 S282UC-K16
20 S282UC-K20
25 S282UC-K25
32 S282UC-K32 290
40 S282UC-K40 300
50 S282UC-K50 350
63 S282UC-K63 390
S201DC S282UC
500 VDC
Two Pole
LOAD
3+
4-
S280UC-K, 500 VDC
Supplemental protectors
UL 1077, CSA 22.2, No. 235
Tripping characteristic K
UL 1077
250/500 VDC
10 kA
Inductive loads
• K Curve
• Designed for allowing higher in-rush
currents during system start up
• Example: motors, transformer
Accessories & technical data
Accessories – See page 15.26
Technical data – See page 15.76 - 15.82
Direct current applications
The S280UC differs from standard miniature
circuit breakers in that the UC versions in-
clude a permanent magnet which aids in the
extinguishing of the arc during medium and
high level faults. It is necessary to observe
the correct polarity and current direction
when connecting the UC breakers. Two ex-
amples of correct connection are shown.
Termination points are marked on all UC
type MCBs, points one (1) and four (4) are
negative and points two (2) and three (3) are
positive.
Discount schedule CB-17 [BM]
Miniature
circuit breakers
15.24 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
ZNo. of
poles
Rated
current Catalog number List price No. of
poles
Rated
current Catalog number List price
1
0.5 S281UC-Z0.5
$ 190
3
0.5 S283UC-Z0.5
$ 660
1 S281UC-Z1 1 S283UC-Z1
1.6 S281UC-Z1.6 1.6 S283UC-Z1.6
2 S281UC-Z2 2 S283UC-Z2
3 S281UC-Z3 3 S283UC-Z3
4 S281UC-Z4 4 S283UC-Z4
6 S281UC-Z6 6 S283UC-Z6
8 S281UC-Z8 8 S283UC-Z8
10 S281UC-Z10 10 S283UC-Z10
16 S281UC-Z16 16 S283UC-Z16
20 S281UC-Z20 20 S283UC-Z20
25 S281UC-Z25 25 S283UC-Z25
32 S281UC-Z32 190 32 S283UC-Z32 680
40 S281UC-Z40 210 40 S283UC-Z40 740
50 S281UC-Z50 240 50 S283UC-Z50 850
63 S281UC-Z63 270 63 S283UC-Z63 950
2
0.5 S282UC-Z0.5
440
1 S282UC-Z1
1.6 S282UC-Z1.6
2 S282UC-Z2
3 S282UC-Z3
4 S282UC-Z4
6 S282UC-Z6
8 S282UC-Z8
10 S282UC-Z10
16 S282UC-Z16
20 S282UC-Z20
25 S282UC-Z25
32 S282UC-Z32 460
40 S282UC-Z40 480
50 S282UC-Z50 560
63 S282UC-Z63 620
S281UC-Z
S282UC-Z
S283UC-Z
S280UC-Z, 500 VDC
Supplemental protectors
UL 1077, CSA 22.2, No. 235
S201DC S282UC
500 VDC
Two Pole
LOAD
3+
4-
Tripping characteristic Z
UL 1077
250/500 VDC
10 kA
Resistive loads
• Z Curve
• Designed to provide maximum
protection with a very low short
circuit trip setting
• Example: semiconductors
Accessories & technical data
Accessories – See page 15.26
Technical data – See page 15.76 - 15.82
Direct current applications
The S280UC differs from standard miniature
circuit breakers in that the UC versions in-
clude a permanent magnet which aids in the
extinguishing of the arc during medium and
high level faults. It is necessary to observe
the correct polarity and current direction
when connecting the UC breakers. Two ex-
amples of correct connection are shown.
Termination points are marked on all UC
type MCBs, points one (1) and four (4) are
negative and points two (2) and three (3) are
positive.
Discount schedule CB-17 [BM]
Miniature
circuit breakers
Low Voltage Products & Systems 15.25
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
S291-C
C
S290
480Y/277 VAC
UL 1077, CSA 22.2, No. 235
1 80 S291-C80 $ 140
100 S291-C100 168
125 S291-C125 196
2 80 S292-C80 280
100 S292-C100 336
125 S292-C125 392
3 80 S293-C80 420
100 S293-C100 504
125 S293-C125 588
4 80 S294-C80 560
100 S294-C100 672
125 S294-C125 784
No. of
poles
Rated
current Catalog number List price
Tripping characteristic C
UL 1077
480Y/277 VAC
5 kA, single pole
14ka, multi pole
Resistive loads
• C Curve
• Designed for use with medium magnetic
start up currents
• Example: lighting, control panels
Accessories & technical data
Accessories – See page 15.27
Technical data – See page 15.76 - 15.82
S292-C
S293-C
S294-C
Discount schedule CB-17 [BM]
Miniature
circuit breakers
15.26 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
Auxiliary contacts
The auxiliary contacts will signal whether the breaker is in the ON or OFF position.
Description Catalog number List price
For eld mounting: right side S2C-H6R $ 21
Bell alarm
The bell alarm includes a set of contacts that will only signal when the breaker has tripped.
Typically the contacts would be connected to an alarm or bell to signal the operator that an overcurrent
trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without opening
the breaker.
Description Catalog number List price
For eld mounting: right side S2C-S/H6R 1 $ 48
Shunt trip
For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens
the breaker after control voltage is applied.
Description Catalog number List price
For eld mounting: right side
A1-12-60 VAC (12 – 60 VDC)
A2-110-415 VAC (110 – 250 VDC)
S2C-A1
S2C-A2
$ 75
70
Undervoltage release
When control voltage drops below approximately 50 % of rated voltage, the UVR opens the breaker.
The breaker can not be operated unless proper control voltage is rst applied to the UVR coil.
Description Catalog number List price
For eld mounting: right side
12 VDC
24 VAC/VDC
48 VAC/VDC
110 VAC/VDC
220 VAC/VDC
380 VAC
S2C-UA 12
S2C-UA 24
S2C-UA 48
S2C-UA 110
S2C-UA 230
S2C-UA 400
$ 216
216
216
216
216
216
S2C-H6R
S2C-A
S2C-UA
Accessories
S200 & S200P
UL 1077, CSA 22.2, No. 235
1 Combination bell alarm/auxiliary contact.
Possible mounting arrangements of MCB accessories
+ST+S/H+S/H (H)+S/H (H)
+ST+H+H+H)
Legend
Auxiliary contact H
Bell alarm/Auxiliary contact S/H
Bell alarm/Auxiliary contact
used as auxiliary contact
S/H (H)
Shunt trip ST
Undervoltage release UR
Discount schedule CB-17 [BM]
Miniature
circuit breakers
Low Voltage Products & Systems 15.27
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
Accessories
S290
UL 1077, CSA 22.2, No. 235
S290-H11
Auxiliary contacts
The auxiliary contacts will signal whether the breaker is in the ON or OFF position.
Description Catalog number List price
Auxiliary contact S290-H11 $ 72
Bell alarm
The bell alarm includes a set of contacts that will only signal when the breaker has tripped.
Typically the contacts would be connected to an alarm or bell to signal the operator that an overcurrent
trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without opening
the breaker.
Description Catalog number List price
Signal contact S290-S $ 112
Shunt trip
For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens
the breaker after control voltage is applied.
Description Catalog number List price
For eld mounting, left side
110V – 415VAC S290-A1 $ 43
For eld mounting, left side
24 – 48VDC S290-A2 67
Discount schedule CB-17 [BM]
Miniature
circuit breakers
15.28 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
Approximate dimensions
S200, S200P, S280UC, S280W, S290
UL 1077, CSA 22.2, No. 235
S200, S200P
LS
Addition of S2C-A...U
S2C-H6R, S2C-A... S2C
S280UC & S280W
S290
Miniature
circuit breakers
Low Voltage Products & Systems 15.29
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
For
use on:
Amp
rating
Number
of poles Phases Busbar length
(mm)
End cap catalog
number
Catalog
number
List
price
S200
S200 P
63
80
60
60
1
1
986
986
PS1/60
PS1/60/16
$ 51
51
For
use on:
Amp
rating
Number
of poles Phases Busbar length
(mm)
End cap catalog
number
Catalog
number
List
price
S200
S200 P
63
80
58
58
2
2
1035
1035
PS-END
PS-END
PS2/58SP
PS2/58/16SP
$ 100
119
For
use on:
Amp
rating
Number
of poles Phases Busbar length
(mm)
End cap catalog
number
Catalog
number
List
price
S200
S200 P
63
80
60
60
3
3
1065
1065
PSB-ENDSP
PSB-ENDSP
PS3/60SP
PS3/60/16SP
$ 135
180
For
use on:
Amp
rating
Number
of poles Phases Busbar length
(mm)
End cap catalog
number
Catalog
number
List
price
S200
S200 P
80
80
60
60
4
4
1056
1056
PS-END1
PS-END1
PS4/60/16SP
PS4/60/16SP
$ 210
210
1 Phase
2 Phase
3 Phase
4 Phase
NOTE
ALL BUSBARS MAY BE CENTER FED IN ORDER
TO INCREASE AMPACITY UP TO 130 A.
NOTE
BUSBARS MAY BE USED ON LINE OR
LOAD SIDE OF MCBS
Accessories
S200 & S200P
UL 1077, CSA 22.2, No. 235
1 Phase
2 Phase
3 Phase
3 Phase + N
Discount schedule CB-17 [BM]
Miniature
circuit breakers
15.30 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
For
use on:
Amp
rating
Number
of poles Phases Busbar length
(mm)
End cap catalog
number
Catalog
number
List
price
S200 &
S200 P
63
80
38
38
1
1
1044
1044
PS1/38H
PS1/38/16H
$ 45
51
For
use on:
Amp
rating
Number
of poles Phases Busbar length
(mm)
End cap catalog
number
Catalog
number
List
price
S200 &
S200 P 80 58 4 1048 PS-END1SP PS4/58/16NSP $ 255
1 Phase with 1 auxiliary
For
use on:
Amp
rating
Number
of poles Phases Busbar length
(mm)
End cap catalog
number
Catalog
number
List
price
S200 &
S200 P 80 48 2 1065 PS-ENDSP PS2/48/16SP $ 168
For
use on:
Amp
rating
Number
of poles Phases Busbar length
(mm)
End cap catalog
number
Catalog
number
List
price
S200 &
S200 P 80 39 3 980 PS-ENDSP PS3/39/16SP $ 127
3 Phase with 1 auxiliary
2 Phase with 1 auxiliary
3 Phase + N, for use with 2 pole-MCBs on 3 phase/4W system
Accessories
S200 & S200P
UL 1077, CSA 22.2, No. 235
NOTE
ALL BUSBARS MAY BE CENTER FED IN ORDER
TO INCREASE AMPACITY UP TO 130 A.
NOTE
BUSBARS MAY BE USED ON LINE OR
LOAD SIDE OF MCBS
1 Phase + Aux
2 Phase + Aux
3 Phase + Aux
3 Phase + N
Discount schedule CB-17 [BM]
SZ-BSK
Busbar tooth covers
Description Catalog
number
List
price
Covers ve unused poles of busbar SZ-BSK $ 4
Miniature
circuit breakers
Low Voltage Products & Systems 15.31
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
Notes
Miniature
circuit breakers
15.32 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
Technical data
S200, S200P & S290
UL 1077, CSA 22.2, No. 235
Technical data S200 S200P S290
Specifications: UL 1077, CSA C 22.2, VDE 0660, 60898, 60947-2 UL 1077, IEC 898
UL File-Number: E 76126 UL CL
No. of poles: 1, 2, 3 & 4 1, 2, 3 & 4
Tripping characteristics: B,C,D, K & Z K & Z C
Rated current: 0.5-63 A 0.2-63 A 80-125 A
Rated voltage: Multi pole: 480Y/277 VAC 277Y/480 VAC
Short circuit capacity: S200 6kA; S200P 10 kA Single pole 5 kA; Multi-pole 14 kA
Frequency: 50/60 Hz 50/60 Hz
Degree of protection: IP 20 IP 20
Mounting position: Vertical, horizontal Vertical, horizontal
Fixing: 35mm DIN rail 35mm DIN rail
Clamps only for Cu: 18-4 AWG 14-1/0 AWG
Service life, mech. and at rated load: 20,000 operations 10,000 operations
Tightening torque: 25 in. lbs (2.8 Nm) 35 in. lbs
Ambient temperature: – 25°C … – 13°F / 70°C … 158°F -25°C... -13°F / 45°C... 113
Shock resistance: 30 g at least 3 impacts, shock duration
of 11 ms
5g min. of 2 impacts, shock duration
of 11 ms
Auxiliary contact S2C-H6R and Signal contact S2C-S6R for S200 and S200P
Rated current: 10
Rated voltage AC / DC: 24
Contact: 1 pole, single throw
Connection capacity mm218 – 14 AWG (0.75…2.5)
Tightening torque: 11 in. Ibs (1.2 Nm)
Shock resistance acc. to DIN IEC 68-2-6: 5 g, 20 frequency cycles 5...150...5 Hz at 24 VAC/DC, 5 mA auto-reclosing < 10 ms
Mechanical service life: 10,000 operations
Shunt trip S2C-A1 S2C-A2
Rated voltage AC
DC
12 ... 60 V
12 ... 60 V
110 ... 415 V
110 ... 250 V
Max. release duration < 10 ms < 10 ms
Min. release voltage AC
DC
7 V
10 V
55 V
80 V
Consumption on release AD
DC
40 ... 200 VA
40 ... 200 VA
55 ... 210 VA
55 ... 110 VA
Coil resistance 3.7 225
Terminals 18…6/0.75 – 16 AWG/mm218…6/0.75 – 16 AWG/mm2
Tightening torque 18/2 in.Ibs/Nm 18/2 in.Ibs/Nm
Undervoltage release
S2C-UA
12 DC
S2C-UA
24 AC
S2C-UA
24 DC
S2C-UA
48 AC
S2C-UA
48 DC
S2C-UA
110 AC
S2C-UA
110 DC
S2C-UA
230 AC
S2C-UA
230 DC
S2C-UA
400 AC
Standards IEC/EN 60947-1
Rated voltage AC
DC
12 V
24 V
24 V
48 V
48 V
110 V
110 V
230 V
230 V
400 V
Frequency 50 ... 60 Hz
Release trip 0.35 UnOVO 0.7 Un V
Terminals 2 x 16/2 x 1.5 AWG/mm2
Consumption 0.2 VA 3.6 VA 2 VA 3.6 VA 2.1 VA 3.5 VA 2.2 VA 3.7 VA 2.3 VA 2.4 VA
Resistance to corrosion constant atmosphere: 23/83 – 40/93 – 55/20; variable atmosphere: 25/95 – 40/93 °C/RH
Protection degree IPXXB / IP2X
Tightening torque 3.5/0.4 in.Ibs/Nm
Miniature
circuit breakers
Low Voltage Products & Systems 15.33
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
Internal resistance and power loss
Internal resistance per pole in mz, power loss per pole in W
Type Rated
current
Device series
B, C, D1
Device series
K
Device series
Z
AmzWmzWmzW
S200 &
S200P
0.5 5500 1.4 6340 1.6 10100 2.5
1 1440 1.4 1550 1.6 2270 2.3
1.6 630 1.6 695 1.8 1100 2.8
2 460 1.8 460 1.9 619 2.5
3 150 1.3 165 1.5 202 1.8
4 110 1.8 120 2.0 149 2.4
6 55 2.0 52 1.9 104 3.7
8 15 1.0 38 2.5 53.9 3.45
10 13.3 1.3 12.6 1.26 17.5 1.7
13 13.3 2.3 12.6 1.26 - -
16 7.0 1.8 7.7 2.0 10.9 2.8
20 6.25 2.5 6.7 2.7 6.0 2.4
25 5.0 3.2 4.6 2.9 4.1 2.6
32 3.6 3.7 3.5 3.6 2.8 2.9
40 3.0 4.8 2.8 4.5 2.5 4.1
50 1.3 3.25 1.25 2.9 1.8 4.4
63 1.2 4.8 0.7 5.2 1.3 5.2
1 Current intensities 0.5 - 4 apply exclusively to C-type trip characteristics
Technical data
S200 & S200P
UL 1077, CSA 22.2, No. 235
Temperature derating
Max operating current depending on the ambient temperature of a circuit breaker characteristics type B, C and D
B,C & D Ambient Temperatures T (Cº/Fº)
Amps
-40/-40 -30/-22 -20/-4 -10/14 0/32 10/50 20/68 30/86 40/104 50/122 60/140 70/158
0.67 0.65 0.62 0.60 0.58 0.55 0.53 0.50 0.47 0.44 0.41 0.37
1.33 1.29 1.25 1.20 1.15 1.11 1.05 1.00 0.94 0.88 0.82 0.75
2.13 2.07 2.00 1.92 1.85 1.77 1.69 1.60 1.51 1.41 1.31 1.19
2.67 2.58 2.49 2.40 2.31 2.21 2.11 2.00 1.89 1.76 1.63 1.49
4.0 3.9 3.7 3.6 3.5 3.3 3.2 3.0 2.8 2.6 2.4 2.2
5.3 5.2 5.0 4.8 4.6 4.4 4.2 4.0 3.8 3.5 3.3 3.0
8.0 7.7 7.5 7.2 6.9 6.6 6.3 6.0 5.7 5.3 4.9 4.5
10.7 10.3 10.0 9.6 9.2 8.8 8.4 8.0 7.5 7.1 6.5 6.0
13.3 12.9 12.5 12.0 11.5 11.1 10.5 10.0 9.4 8.8 8.2 7.5
17.3 16.8 16.2 15.6 15.0 14.4 13.7 13.0 12.3 11.5 10.6 9.7
21.3 20.7 20.0 19.2 18.5 17.7 16.9 16.0 15.1 14.1 13.1 11.9
26.7 25.8 24.9 24.0 23.1 22.1 21.1 20.0 18.9 17.6 16.3 14.9
33.3 32.3 31.2 30.0 28.9 27.6 26.4 25.0 23.6 22.0 20.4 18.6
42.7 41.3 39.9 38.5 37.0 35.4 33.7 32.0 30.2 28.2 26.1 23.9
53.3 51.6 49.9 48.1 46.2 44.2 42.2 40.0 37.7 35.3 32.7 29.8
66.7 64.5 62.4 60.1 57.7 55.3 52.7 50.0 47.1 44.1 40.8 37.3
84.0 81.3 78.6 75.7 72.7 69.6 66.4 63.0 59.4 55.6 51.4 47.0
112.6 107.2 102.1 97.2 92.6 88.2 84.0 80.0 76.0 72.2 68.6 65.2
140.7 134.0 127.6 121.6 115.8 110.3 105.0 100.0 95.0 90.3 85.7 81.5
175.9 167.5 159.5 151.9 114.7 137.8 131.3 125.0 118.8 112.8 107.2 101.8
Miniature
circuit breakers
15.34 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
Technical data
S200, S200P & S290
UL 1077, CSA 22.2, No. 235
Tripping characteristic B Tripping characteristic C Tripping characteristic D
Tripping characteristic K Tripping characteristic Z
Miniature
circuit breakers
Low Voltage Products & Systems 15.35
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
Miniature circuit breaker
Application guide
Introduction
The circuit breaker plays an important role in providing over-current
protection and a disconnect means in electrical networks. Recent
advancements in circuit breaker technology has increased breaker
performance and protection.
Overload
A slow and small overcurrent situation that causes the ampacity and
temperature of the circuit to gradually increase over time. This type of
event is characterized by a slight increase in the load (ampacity) on the
circuit and is interrupted by the thermal trip unit of the breaker.
Thermal Example
10A
Breaker
Light
15A
The light draws more than 10 amps for
an extended period of time creating a
thermal overload.
Short circuit
A rapid and intense overcurrent situation that causes the ampacity of
the circuit to increase. This type of event is characterized by a dramatic
increase in the load (ampacity) on the circuit and is interrupted by the
magnetic trip unit of the breaker.
Breaker definition
A breaker is a device designed to isolate a circuit during an overcurrent
event without the use of a fusible element. A breaker is a resettable
protective device that protects against two types of overcurrent
situations; Overload and Short Circuit.
ABB current limiting breaker
Tripping lever
Operating
mechanism
Operator
Electro-magnetic protection Upper
terminal
Thermal
protection-
bimetal
Arc
chamber
Fixed
contact
Moving
contact
DIN rail holder
Lower terminal
Space for
identification
marker
Miniature
circuit breakers
15.36 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
Circuit breaker construction
Thermal / Magnetic trip units definition
ABB Current Limiting Breakers use an electromechanical (Thermal /
Magnetic) trip unit to open the breaker contacts during a overcurrent
event. The thermal trip unit is temperature sensitive and the magnetic
trip unit is current sensitive. Both units act independently and
mechanically with the breaker’s trip mechanism to open the breaker’s
contacts.
Overload protection
The thermal trip unit protects against a continuous overload. The
thermal unit is comprised of a bimetal element located behind the
circuit breaker trip bar and is part of the breaker’s current carrying path.
When there is an overload, the increased current ow heats the bimetal
causing it to bend. As the bimetal bends it pulls the trip bar which
opens the breaker’s contacts.
The time required for the bimetal to bend and trip the breaker varies
inversely with the current. Because of this, the tripping time becomes
quicker as current increases in magnitude.
Overload protection is applicable to any installation, conductor, or
component which can be subjected to low-magnitude but long-
time over-currents. Low-magnitude, long-time over-currents can be
dangerous because they reduce the life of the electrical installation,
conductor, and components and if left unchecked could result in re.
Magnetic trip units (short circuit protection)
The Magnetic trip unit protects against a short circuit. The magnetic
trip unit is comprised of an electromagnet and an armature.
Components of a magnetic trip unit
When there is a short circuit, a high magnitude of current passes
through the coils creating a magnetic eld that attracts the movable
armature towards the xed armature. The hammer trip is pushed
against the movable contact and the contacts are opened. The
opening of the breakers contacts during a short circuit is complete in .5
milli-seconds.
Current Flow During Operation
All highlighted components are energized during operation
Magnetic Trip Unit Thermal Trip Unit
Trip Bar
Operating Mechanism Thermal Trip Unit
Armature and Plunger
Movable Contact Magnet Trip Unit
Miniature
circuit breakers
Low Voltage Products & Systems 15.37
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
Circuit breaker construction
Arc runners / Arc chutes
The arc runner and arc chute limit and dissipate the arc energy during
the interruption of an overload or short circuit event.
During an overload or short circuit event, the contacts of the breaker
separate and an electrical arc is formed between the contacts through
air. The arc is moved into the arch chute by “running” the arc down the
interior of the breaker along the arc runner. When the arc reaches the
arc chute it is broken into small segmented arcs. The segmented arcs
split the overall energy level into segments less than 25V. Each 25V
segment does not have a high enough energy level to maintain an arc
and all energy is naturally dissipated.
Breaker curves
Thermal Trip Unit (region one)
The rst sloping region of the breaker curve is a graphical
representation of the tripping characteristics of the thermal trip unit.
This portion of the curve is sloped due to the nature of the thermal trip
unit. The trip unit bends to trip the breaker’s trip bar in conjunction with
a rise in amperage (temperature) over time. As the current on the circuit
increases, the temperature rises, the faster the thermal element will trip.
Example using the curve below: If you had a 10A breaker and the circuit
was producing 30 amps of current, the breaker would trip between
2 seconds and 1 minute. In this example you would nd the circuit
current on the bottom of the graph (Multiples of rated current). The rst
line is 10 amps (10 amp breaker x a multiple of one), the second line is
20 amps (10 amp breaker x multiple of 2), and the third line is 30 amps
(10amp breaker x multiple of 3). Next you would trace the vertical 30A
line up until it intersects the red portion of the breaker thermal curve.
If you follow the horizontal lines, on both sides of the red curve, to the
left you will see that the breaker can trip as fast as 2 seconds and no
slower than 1 minute.
Magnetic Trip Unit (region two)
This region of the breaker curve is the instantaneous trip unit. ABB’s
miniature circuit breaker’s instantaneous trip unit interrupts a short
circuit in 2.3 to 2.5 milliseconds. Because of this the curve has no
slope and is graphically represented as a vertical straight line.
Example using the curve above: If you had a 10 amp breaker the
magnetic trip element would interrupt a short circuit between 10 and 30
amps (10 amp breaker x multiple of 2 and 3) in 2.3 to 2.5 milliseconds.
Breaker Contacts (region three)
This region of the curve is the time required for the contacts of the
breaker to begin to separate. The contacts will open in less than .5
milliseconds and is graphically represented by the bottom vertical
portion of the curve.
Arc Runner Arc Chute
Magnetic Trip Unit
(Region Two)
Thermal Trip Unit
(Region One)
Moving Contacts
(Region Three)
Miniature
circuit breakers
15.38 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
Circuit breaker current limitation
Current limiting definitions
All ABB Miniature Circuit Breakers are UL tested and certied as current
limiting protective devices. Current limiting circuit breakers provide
a higher level of circuit protection than a typical zero point external
breakers.
UL AC 60Hz cycle
UL denes an AC cycle as the potential energy of the wave form
traveling from Zero-to-Positive amplitude, Positive-to-Zero amplitude,
Zero-to-Negative amplitude, Negative-to-Zero amplitude 60 times in
one second. One cycle is completed every 16.6 milliseconds.
UL breaker current limiting
UL denes breaker current limitation as a breaker that interrupts
and isolates a fault in less than 1/2 of an AC cycle. 1/2 a cycle is
completed in 8.3 milliseconds.
NEC240.2 current limiting
A device that, when interrupting current in its current-limiting range,
reduces the current owing in the faulted circuit to a magnitude
substantially less than that obtainable in the same circuit if the device
were replaced with a solid conductor having comparable impedance.
IEC 60947-2 current limiting circuit breaker
A circuit breaker with sufciently short trip time to prevent the short-
circuit current from reaching the peak value which would otherwise be
reached.
ABB current limiting breakers
ABB current limiting breakers can interrupt and isolate a fault in 1/8 of
an AC cycle. The breaker fault interruption is completed in 2.3 to 2.5
milliseconds.
Zero point extinguishing breakers
A typical zero point extinguishing breaker interrupts a fault and does
not isolate the energy. The breaker allows an arc to be present between
the open contacts until the AC wave form crosses zero. When the
wave form crosses zero, the potential energy is zero and the arc
(fault) naturally extinguishes. The arc could be present for up to 8.3
milliseconds.
Current limiting breakers and electrical networks
Current Limitation
When a short-circuit condition occurs, the “ideal” current limiting circuit
breaker opens before the current waveform can reach its full potential
magnitude which occurs at ¼ cycle (4.17ms). ABB’s current limiting
breakers can interrupt a fault in about ½ cycle or 2.3ms to 2.5ms.
ABB’s current limiting breakers interrupt a short circuit in less than 1/8
cycle and limit the amount of current that can reach a circuit. Limiting
the available current on the circuit provides additional protection
against network, breaker, or bus damage and prevents the tripping of
upstream breakers (selective coordination).
IsqT
The true destructive nature of a short circuit is measured by the time
it is available combined with the peak value of the short circuit. The
IsqT (Amps Squared over Time) value represents the amount of energy
available on a network during a short circuit and is represented by the
shaded area on the graph below.
During a short circuit both magnetic forces and thermal energy
combine to damage devices on the electrical network. The level of
thermal energy and magnetic forces are directly proportional to the
square of the current. The magnetic forces vary as a square of the
peak current available and the thermal energy varies as a square of
the RMS (root mean square) current available. ABB’s current limiting
breakers will limit the let-through energy to a fraction (1/100th) of the
value which is available from the network. By comparison, a Zero
Crossing breaker would let-through approximately 100 times as much
destructive energy as the current limiting circuit breaker
[ (100,000A / 10,000A) squared – 100X].
ABB’s current limiting breakers limit the short circuit current to a
relatively small magnitude in a extremely short time, which dramatically
limits a short circuit’s destructive energy.
Miniature
circuit breakers
Low Voltage Products & Systems 15.39
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
Circuit breaker current limitation
Current limiting and zero crossing breakers
During the initial stages of a short circuit a breaker’s contacts open
to interrupt the circuit. After the contacts open an arc forms in the air
between the contacts on both the current limiting and zero crossing
breaker contacts. What distinguishes a current limiting breaker from a
zero crossing breaker is what each breaker does after an arc is formed
between the open contacts.
A current limiting breaker “runs” the arc down the breaker arc runner
into an arc chute that extinguishes the arc.
A zero crossing breaker does not attempt to extinguish the arc. The
breaker is designed to withstand the energy of the arc long enough
for the waveform to cross zero. When the wave form crosses zero the
potential energy is zero and the arc naturally extinguishes itself.
ABB’s current limiting breakers interrupt the arc energy in 2.3ms to
2.5ms (1/8 cycle) and a zero crossing breaker allows the arc to be
present for up to 8.3ms (1/2 cycle). A zero crossing breaker will let
through 100 times as much energy as an ABB current limiting breaker.
Current limiting example
The lab test report below details a 20A S200 series current limiting
breaker interrupting a 28kA fault in 1.7 milliseconds. The total “I
Square T” value is 32.0kA.
Zero crossing example
The test report below details a 20A Zero Point Extinguishing breaker
interrupting a 9kA fault in 9 milliseconds. The total "I Square T" value
is 104.0kA.
500
-500
V
U-L2
100 /div
-400
-300
-200
-100
100
200
300
400
06.9990.99991.99972.99963.99944.99935.9991
kSample499.93 Sample/div
10
-10
kA
I-L2
2 k/div
-8
-6
-4
-2
2
4
6
8
Time A Time B
Legend
Voltage
Amps
500
-500
V
U-BCP L2
100 /div
-400
-300
-200
-100
100
200
300
400
06.9990.99991.99972.99963.99944.99935.9991
kSample499.93 Sample/div
10
-10
kA
I-L2
2 k/div
-8
-6
-4
-2
2
4
6
8
Time A Time B
Legend
Voltage
Amps
Miniature
circuit breakers
15.40 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
Selective coordination and series ratings
IEC 60497-1 selective coordination definition
Coordination between the operating characteristics of two or more
over-current protection devices, so that when an over-current within
established limits occurs, the device designated to operate within those
limits trips whereas the other do not trip.
Example of breaker coordination
When an over-current event occurs at the branch breaker level (CB1),
and the event is within the operating characteristics of the breaker,
then the branch breaker should interrupt the circuit (open) and the
main breaker should remain closed and energized. The chart below
gives a graphical representation of a down stream branch breaker (B
curve) and a main breaker (A curve) with coordination. The separation
between the curves allows the branch breaker to react to the fault and
the main breaker remain closed and energized.
Example of no breaker coordination
Selective breaker coordination is not achieved when there is an
overload event at the branch breaker level (MCB1) and both the branch
breaker and main breaker interrupt the circuit (open). When there is
no breaker coordination several circuits lose power that should remain
operational during and after the overload event. The chart below gives a
graphical representation of a down stream branch breaker (B curve) and
a main breaker (A curve) without coordination. There is no separation
between the curves. The branch breaker will react to a fault and the
main breaker will open and de-energize all circuits down stream.
Problems in coordination occur when the branch breaker allows
the "I Square T" value of the short circuit to rise to a level that is in
the operating range of the up-stream main breaker. Proper breaker
coordination is easier to achieve with the use of current limiting
breakers at the branch level.
Selective coordination and current limiting breakers
Recent improvements in ABB circuit breaker technology has pushed
the performance of breakers to the same level as fuses. The reaction
time and tripping characteristics of current limiting breakers are now on
par with fuses. This allows ABB to provide a high level of coordination
between branch breakers and the main. A current limiting branch
breaker will limit the “I Square T” value well below the level of the
operating range of the up-stream main breaker.
ABB’s current limiting branch breakers can coordinate between the
main breaker up to 35kA.
Selective coordination and zero crossing breakers
Zero crossing breakers do not limit the “I Square T” value. They wait for
the wave form to cross zero and allow a high level of let-through energy
to pass through the system. The “I Square T” value of a zero crossing
breaker is high enough that the main breaker will likely trip during a
short circuit. With zero crossing breakers it is extremely difcult to
coordinate between branch and main breakers.
A typical zero crossing breaker’s coordination level is below 10kA.
There are a few manufactures that have achieved coordination
between a branch zero crossing breaker and the main by slowing the
performance (protection) of the main breaker.
Main
breaker
CB1 CB2 CB3 CB4
Short circuit
Miniature
circuit breakers
Low Voltage Products & Systems 15.41
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0202
15
Selective coordination and series ratings
Series ratings –vs- selective coordination
Selective coordination
Selective coordination is achieved when there is a short circuit on a
branch circuit breaker, the branch breaker opens and isolates the fault,
and the main breaker remains closed. The rating is usually a value
above the “stand alone” interrupting rating of the branch breaker and
the “stand alone” rating of the main breaker.
Example:
65kA rated main breaker
10kA rated branch breaker
Coordination between the two breakers up to 35kA
There can be a short circuit on the branch breaker up to 35kA where
the branch will open (CB1) and the main breaker will remain closed.
Although the branch has a 10kA “stand alone” rating both the breakers
work together to limit the available short circuit to allow the branch
(CB1) to isolate the fault.
Series ratings
Series ratings are different from coordination ratings. Unlike
coordination ratings where the branch opens and the main remains
closed, a series rated combination is one where both the branch and
main breakers open and work together to isolate the fault.
The series rating combination of two breakers is equal to the “stand
alone” interrupting value of the main breaker. This is a result of the
main breaker let-through value being lower than the “stand alone”
interrupting value of the branch breaker. During a short circuit the main
breaker will limit the energy to a level that is below the “stand alone”
value of the branch breaker.
Example:
65kA rated main breaker
10kA rated branch breaker
Series combination rating between the two breakers up to 65kA
There can be a short circuit on the branch breaker up to 65kA where
the branch will open and the main breaker will open. Although the
branch breaker (CB1) has a 10kA “stand alone” rating the main breaker
has a let-through value below 10kA. If there is a fault up to 65kA on
the network the main breaker will limit the energy to a value less than
the rating of the branch breaker (CB1). Both breakers will trip (no
coordination) but the network can safely withstand a fault of 65kA.
Main
breaker
65 kA
CB1
10 kA
CB2
10 kA
CB3
10 kA
CB4
10 kA
35 kA or 65 kA short circuit
Miniature
circuit breakers
15.42 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb-control.com
15
Tripping lever
Operating
mechanism
Operator
Electro-magnetic protection
Upper terminal
Thermal
protection-bimetal
Arc chamber
Fixed contact
Moving contact
DIN rail clipLower terminal
Space for
identification marker
Miniature circuit breaker cutaway