Fuse Supports & Disconnecting Switches
RATINGS, DIMENSIONS AND WEIGHTS
Insulator Rating Dim. Term
Max. Class/ Fuse Fig. Approximate Dimensions (inches) -inal Appr.
GE Fuse Nominal NEMA Clip No. Type Ship
Cat. No. Rating System BIL Tech. Cntrs. see A D EFGHJKLMNPRSTbl. Wt(lb)
(kV) (kV) (kV) Ref. (in.) Tbl."F" "C"
Table A - INDOOR FUSE SUPPORTS & DISCONNECTING SWITCHES
Table A1 - Size B Type EK-1B Fuse Supports (Nondisconnecting, 1 9/16-inch ferrule diameter)
9F61ABB101 2.75/5.5 4.8 60 A-20 8.12 1,5,7 17 4 6.0 4.0 3.3 0.2 4.5 615.4 17 1 36
9F61ABG101 8.25 13.8 95 A-20 8.12 1,5,7 17 4 8.5 6.5 3.3 0.2 4.5 620.3 17 1 48
9F61ADG101 15.5 13.8 95 A-20 11.5 1,5,7 20 4 8.8 6.5 3.3 0.3 4.5 620.3 22 1 50
9F61ADJ101 15.5 14.4 110 A-20 11.5 1,5,7 20 4 10.3 8.0 3.3 0.3 4.5 620.3 22 1 60
Table A2 - Size C Type EK-1C Fuse Supports (Nondisconnecting, 2-inch ferrule diameter)
9F61AAB201 2.75 4.8 60 A-20 71,5,7 14 3.5 6.5 4.0 2.8 0.2 4.5 615.4 17 1 23
9F61ACB201 5.5 4.8 60 A-20 91,5,7 16 3.5 6.5 4.0 2.8 0.2 4.5 615.4 17 1 25
9F61AEG201 15.5 13.8 95 A-20 12 1,5,7 19 3.5 9.3 6.5 2.8 0.3 4.5 620.3 22 1 37
9F61AGG201 15.5 13.8 95 A-20 15 1,5,7 22 3.5 9.3 6.5 2.8 0.3 4.5 623.3 25 1 39
9F61AGJ201 15.5 14.4 110 A-20 15 1,5,7 22 3.5 10.8 8.0 2.8 0.3 4.5 623.3 25 1 42
9F61AHM201 25.8 23.0 150 A-20 21 1,6,7 33 6.0 13.8 11.0 3.5 0.3 5.5 730.5 32 3 63
Table A3 - Size C Type EK-3C Fuse Disconnecting Switches (2-inch ferrule diameter)
9F61AAB205 2.75 4.8 60 A-20 73,5,7 16.8 3.5 6.5 4.0 10.0 16.8 6.3 5.5 2.8 0.2 4.5 615.4 17 1 36
9F61ACB205 5.5 4.8 60 A-20 93,5,7 16.8 3.5 6.5 4.0 10.0 18.5 6.3 5.5 2.8 0.2 4.5 615.4 17 1 38
9F61AEG205 15.5 13.8 95 A-20 12 3,5,7 21.8 3.5 9.3 6.5 12.5 24.0 6.3 5.5 2.8 0.3 4.5 620.3 22 1 48
9F61AGG205 15.5 13.8 95 A-20 15 3,5,7 24.8 3.5 9.3 6.5 12.5 26.8 6.3 5.5 2.8 0.3 4.5 623.3 25 1 50
9F61AGJ205 15.5 14.4 110 A-20 15 3,5,7 24.8 3.5 10.8 8.0 14.0 28.3 6.3 5.5 2.8 0.3 4.5 623.3 25 1 55
9F61AHM205 25.8 23.0 150 A-20 21 3,6,7 34.8 6.0 13.8 11.0 17.0 36.5 7.8 5.3 3.5 0.3 5.5 730.5 32 3 76
Table A4 - Size D Type EK-1D Fuse Supports (Nondisconnecting, 3-inch ferrule diameter)
9F61AAB301 2.75 4.8 60 A-20 71,5,7 14 3.5 9.0 4.0 2.8 0.2 4.5 615.4 17 1 35
9F61AEB301 2.75/5.5 4.8 60 A-20 12 1,5,7 19 3.5 9.0 4.0 2.8 0.3 4.5 620.3 22 1 35
9F61AEG301 8.25 13.8 95 A-20 12 1,5,7 19 3.5 11.5 6.5 2.8 0.3 4.5 620.3 22 1 53
9F61AGG301 15.5 13.8 95 A-20 15 1,5,7 22 3.5 11.5 6.5 2.8 0.3 4.5 623.3 25 1 55
9F61AGJ301 15.5 14.4 110 A-20 15 1,5,7 22 3.5 13.0 8.0 2.8 0.3 4.5 623.3 25 1 65
9F61AHM301 25.8 23.0 150 A-20 21 1,6,7 33 6.0 16.0 11.0 3.5 0.3 5.5 730.5 32 3 85
Table A5 - Size D Type EK-3D Fuse Disconnecting Switches (3-inch ferrule diameter)
9F61AAB305 2.75 4.8 60 A-20 73,5,7 16.8 3.5 9.0 4.0 11.0 17.0 6.3 5.5 2.8 0.2 4.5 615.4 17 1 45
9F61AEB305 2.75/5.5 4.8 60 A-20 12 3,5,7 21.8 3.5 9.0 4.0 11.0 22.0 6.3 5.5 2.8 0.3 4.5 620.3 22 1 45
9F61AEG305 8.25 13.8 95 A-20 12 3,5,7 21.8 3.5 11.5 6.5 13.5 24.5 6.3 5.5 2.8 0.3 4.5 620.3 22 1 63
9F61AGG305 15.5 13.8 95 A-20 15 3,5,7 24.8 3.5 11.5 6.5 13.5 27.3 6.3 5.5 2.8 0.3 4.5 623.3 25 1 65
9F61AGJ305 15.5 14.4 110 A-20 15 3,5,7 24.8 3.5 13.0 8.0 15.0 28.8 6.3 5.5 2.8 0.3 4.5 623.3 25 1 75
9F61AHM305 25.8 23.0 150 A-20 21 3,6,7 34.8 6.0 16.0 11.0 18.0 37.3 7.8 5.3 3.5 0.3 5.5 730.5 32 3 100
Table A6 - Size DD Type EK-1DD Fuse Supports (Nondisconnecting, 3-inch ferrule diameter)
9F61AAB401 2.75 4.8 60 A-20 72,5,7 14 3.5 12.3 4.0 2.8 0.2 4.5 615.4 17 1 45
9F61AEB401 2.75/5.5 4.8 60 A-20 12 2,5,7 19 3.5 12.3 4.0 2.8 0.3 4.5 620.3 22 1,2 45
9F61AEG401 8.25 13.8 95 A-20 12 2,5,7 19 3.5 14.8 6.5 2.8 0.3 4.5 620.3 22 1 63
9F61AGG401 15.5 13.8 95 A-20 15 2,5,7 22 3.5 14.8 6.5 2.8 0.3 4.5 623.3 25 1 65
9F61AGJ401 15.5 14.4 110 A-20 15 2,5,7 22 3.5 16.3 8.0 2.8 0.3 4.5 623.3 25 1 75
9F61AHM401 25.8 23.0 150 A-20 21 2,6,7 33 6.0 19.3 11.0 3.5 0.3 5.5 730.5 32 3 95
Table A7 - Size DD Type EK-3DD Fuse Disconnecting Switches (3-inch ferrule diameter)
9F61AAB405 2.75 4.8 60 A-20 74,5,7 16.8 3.5 12.3 4.0 14.3 18.5 6.3 5.5 2.8 0.2 4.5 615.4 17 1 50
9F61AEB405 2.75/5.5 4.8 60 A-20 12 4,5,7 21.8 3.5 12.3 4.0 14.5 23.0 6.3 5.5 2.8 0.3 4.5 620.3 22 1,2 50
9F61AEG405 8.25 13.8 95 A-20 12 4,5,7 21.8 3.5 14.8 6.5 17.0 25.5 6.3 5.5 2.8 0.3 4.5 630.2 22 1 68
9F61AGG405 15.5 13.8 95 A-20 15 4,5,7 24.8 3.5 14.8 6.5 17.0 28.5 6.3 5.5 2.8 0.3 4.5 623.3 25 1 70
9F61AGJ405 15.5 14.4 110 A-20 15 4,5,7 24.8 3.5 16.3 8.0 18.5 30.0 6.3 5.5 2.8 0.3 4.5 623.3 25 1 80
9F61AHM405 25.8 23.0 150 A-20 21 4,6,7 34.8 6.0 19.3 11.0 21.5 38.3 7.8 5.3 3.5 0.3 5.5 730.5 32 3 105
Table A8 - Size EE Type EK-1EE Fuse Supports (Nondisconnecting, 4-inch ferrule diameter)
9F61AFB501 5.08 4.5 60 A-20 14, 12 2,5,7 22.9 4.4 13.0 4.0 3.6 0.3 4.5 622.3 24.1 4 60
9F61AFG501 15.0 13.8 95 A-20 14, 12 2,5,7 22.9 4.4 15.5 6.5 3.6 0.3 4.5 622.3 24.1 1 75
9F61AFJ501 15.0 14.4 110 A-20 14, 12 2,5,7 22.9 4.4 17.0 8.0 3.6 0.3 4.5 622.3 24.1 1 85
Table A9 - Size DDDD Type EK-1DDDD Fuse Supports (Nondisconnecting, for Bolted-end Fuses)
9F61AHG001
9F61AHJ001 For Bolted-end fuses. Request outline drawings from factory.
9F61AKB001
(1) IMPORTANT: When selecting a mounting for a current-limiting fuse, it is necessary that the clip centers and size agree with the fuse selected.
(2) Terminal type based on continuous-current ratings of fuse. Order and price separately (see Table C).
(3) Prices of Fuse Supports and Disconnecting Switches include live parts for both ends.
Catalog GEP 9013B - GE Medium Voltage Power Fuses
Page 10