cui.com
CUI Inc │ SERIES: VMS-160 │ DESCRIPTION: AC-DC POWER SUPPLY date 07/01/2016 │ page 2 of 5
INPUT
parameter conditions/description min typ max units
voltage 90
125
264
373
Vac
Vdc
frequency 47 63 Hz
current at 100 Vac, cold start
at 200 Vac, cold start
2.5
1.25
A
A
inrush current at 230 Vac, full load, cold start
power factor correction
measured at full load and 115 Vac/60 Hz and
230 Vac/50 Hz input source input will be less than
0.25Ω, compliant to EN61000-3-2 for harmonic
currents
0.85 0.98
OUTPUT
parameter conditions/description min typ max units
line regulation low line to high line ±1 %
load regulation all other outputs
12 V aux. output
±1
±20
%
%
temperature coefcient 0.25 mV/°C
transient response 25% Imax to Imax , 0.1 A/µs slew rate, ±5% max. deviation, 1 ms recovery
start-up 1 s
rise time 0.2 20 ms
hold-up 16 ms
adjustability ±5 %
fan drive 12 Vdc / 500 mA for external fan
PROTECTIONS
parameter conditions/description min typ max units
over voltage protection 130 %
over current protection automatically recovers 150 %
short circuit protection auto recovery with no damage from a short on any
output
SAFETY & COMPLIANCE
parameter conditions/description min typ max units
isolation voltage primary to secondary (for 1 second):
primary to earth ground (for 1 second):
5,656
5,656
Vdc
Vdc
safety approvals UL 60950-1/60601-1, NEMKO EN 60950-1/EN 60601-1, CE
EMI/EMC
EN 55022:1998 (Class B, conducted), EN 61000-3-2: 2000, EN 61000-3-3: A1:2001, EN 55024 (IEC
61000-4-2: 1995, IEC 61000-4-3: 1995, IEC 61000-4-4: 1995, IEC 61000-4-5: 1995, IEC 61000-4-6:
1996, IEC 61000-4-11: 1994)
leakage current measured per IEC 60950-1, paragraph 5.1,
test voltage of 120 Vac/60 Hz 275 µA
MTBF with 400 LFM forced air, MIL-HDBK-217E-1, 75%
of rated full load, 25°C ambient 200,000 hrs
RoHS 2011/65/EU
For more information, please visit the product page | If your application requires forced air, view our Dc Fans