3RU11, 3RB10, 3RB12 Overload relays
SIRIUS System Manual
A5E40534713002A/RS-AA/001 4-61
4.7.3 3RB12 electronic overload relays
Ty p e 3RB12 46 3RB12 53 3RB12 57 3RB12 62
Width 70 mm 120 mm 145 mm 230 mm
General specifications
Tripped at Overload, phase loss, phase imbalance (>40 % in acc. with NEMA),
ground fault, and operation of thermistor motor protection1)
Tripping class In acc. with IEC 60 947-4-1 CLASS 5, 10, 15, 20, 25, and 30; adjustable by means of a 6-way rotary
switch
Phase loss sensitivity Ye s
Overload warning Yes, as of 1.5 x Ie given a symmetric load, and as of 0.85 x Ie given an
asymmetric load
Resetting and recovery
Resetting options after tripping Manual, remote, and automatic resetting 1)
Recovery time With automatic RESET min. When tripped by overcurrent: 5 (stored permanently)
When tripped by thermistor: time until the motor temperature 5K
sinks under the operating temperature
When tripped by ground fault: no automatic reset
With manual RESET min. When tripped by overcurrent: 5 (stored permanently)
When tripped by thermistor: time until the motor temperature 5K
sinks under the operating temperature
When tripped by ground fault: immediate
With remote RESET min. When tripped by overcurrent: 5 (stored permanently)
When tripped by thermistor: time until the motor temperature 5K
sinks under the operating temperature
When tripped by ground fault: immediate
Configuration
Indication of operating status on device Yes, with 3 LEDs; green "Ready" LED, red "Overload" LED, and red
"Ground fault" LED 2)
TEST function Yes, with combined TEST/RESET button 2)
RESET button Yes, with combined TEST/RESET button 2)
STOP button Yes, with combined TEST/RESET button 2)
For the safe operation of motors with
increased safety protection
EC special test certificate number in
compliance with directive 94/9/EC
PTB 01 ATEX 3220
Ambient temperatures
Storage/transportation °C -40 to +80
Operation °C -25 to +70
Temperature compensation °C Up to 70
Permissible rated current at Internal cubicle temperature of 60 °C % 100 (current reduction is not required at above +60 °C)
Internal cubicle temperature of 70 °C % 100 (current reduction is not required at above +60 °C)
Repetition terminals
Terminal for contactor coil Not required
Auxiliary switch repetition terminal Not required
Degree of protection In acc. with IEC 60 529/DIN VDE 0470
Part 1
IP20 (≤ 100 A max. set current Ie
IP00 (≤ 100 A max. set current Ie
Shock protection In acc. with DIN VDE 0106 Part 100 Protected
against finger
touch
Protected against finger touch with cover
Sinus shock resistance In acc. with IEC 68 Part 2-27 g/ms 15/11
EMC noise immunity
Conducted
disturbance neutralization - burst
In acc. with IEC 61 000-4-4:
(corresponds to severity grade 3)
kV 2
Conducted
disturbance neutralization - surge
In acc. with IEC 61 000-4-5:
(corresponds to severity grade 3)
kV 2
Electrostatic discharge In acc. with IEC 61 000-4-2:
(corresponds to severity grade 3)
kV 8
Field-related disturbance neutralization In acc. with IEC 61 000-4-3:
(corresponds to severity grade 3)
V/m 10
EMC emitted interference Limit value class B in acc. with EN 55 011
Resistance to extreme climates (atmospheric humidity) %100
Dimensions See dimensional drawings
Site altitude m Up to 2000 above sea level
Construction type/mounting
Stand-alone
installation
3
)
Direct mounting/stand-alone installation without
additional terminal bracket
4
)
1) Tripped at ground fault only in the case of devices with the order number suf-
fixes 20 and 30 or in conjunction with the external summation current transformer
3) Snap-on attachment to 35 mm rail or screw-on attachment with
accessories
2) For a detailed explanation, see Section 4.2, "Applications and use". 4) For screw-on attachment