1
Alle Rechte vorbehalten. All rights reserved.
© Siemens AG 2002
Überstromauslöser 3WX31 41 – 1JC02
für Niederspannungs-Leistungsschalter 3WN1/5, 3WS1 3WX31 41 – 2JC02
Solid st ate overcurrent release 3WX31 41 3JC02
for 3WN1/5, 3WS1 low-voltage circuit-breaker 3WX31 41 – 4JC02
3WX31 41 – 4JD02
3WX31 41 – 5JC02
3WX31 41 – 6JE02
3WX31 41 – 6JC02
3WX31 41 – 5JC12
3WX31 41 – 6JE12
Fig. 1 3WN1/5, 3WS1 Auslöser 3WX31 41 – 1
Ausführung: "azn"
3WN1/5, 3WS1 release 3WX31 41 ("azn")
Fig. 2 3WN1/5, 3WS1 Auslöser 3WX31 41 – 6
Ausführung: "azng"
3WN1/5, 3WS1 release 3WX31 41 – 6 ("azng")
Betriebsanleitung / Operating Instructions Bestell-Nr./Order No.: 3ZX1812-0WX31-0AN5 / 9259 9499 174 0E
2
Contents.............................................................Page
Technical data .................................................................... 3
Trip unit models ................................................................. 3
Construction and mode of operation ................................. 4
Current ratings and setting ranges ............................... 5 - 6
Release functions........................................................ 7 - 17
Display and signalling ............................................... 18 - 21
Communication ................................................................ 21
Remote operation............................................................. 22
Mechanical lockout ........................................................... 22
Function test..................................................................... 22
Maintenance ..................................................................... 23
Installation ................................................................. 2 3 - 25
Block diagrams ..........................................................26 - 27
Inhalt .................................................................. Seite
Technische Daten............................................................... 3
Auslöser-Ausführungen...................................................... 3
Aufbau und Wirkungsweise ............................................... 4
Nennströme und Einstellbereiche................................. 5 - 6
Auslösefunktion ........................................................... 7 - 1 7
Anzeigen und Meldungen.......................................... 18 - 21
Kommunikation ................................................................ 21
Fernauslösung.................................................................. 22
Wiedereinschaltsperre ..................................................... 22
Funktionsprüfung ............................................................. 22
Wartung............................................................................ 23
Montage..................................................................... 23 - 25
Übersichts-Schaltpläne ............................................. 2 6 - 27
ContentsInhalt
3
Technische Daten · Auslöser-Ausführungen Trip Unit · Release models
Technische Daten Technical data
Leistungsaufnahme: für Auslösefunktion keine /
für Anzeigen siehe Seite 19
Frequenzbereich: 40 … 400 Hz
Arbeitstemperaturbereich: -20 bis +70 °C 1)
Lagertemperaturbereich: -40 bis +70 °C
Gewicht: ca 0,75 kg
Abmessungen: Breite: 60 mm
Höhe: 250 mm
Tiefe: 140 mm
1) Die in Fig. 6 bis 10 dargestellten Kennlinien und Toleranzbänder gelten für
Umgebungstemperaturen von -5 bis +55 °C. Der Auslöser kann darüber
hinaus auch bei Umgebungstemperaturen von -20 bis +70 °C betrieben
werden. Dabei kann bei Temperaturen unter -5 °C ein zusätzlicher Fehler
von +5%, bei Temperaturen unter +55 °C ein zusätzlicher Fehler von -5% in
der Stromachse auftreten.
Power input: for protective functions not required /
for display see page 19
Frequency range: 40 … 400 Hz
Operating temperature range: -20 bis +70 °C 1)
Storage temperature range: -40 bis +70 °C
Approx. weight: 0.75 kg
Dimensions: Width: 60 mm
Height: 250 mm
Depth: 140 mm
1) The characteristics and tolerance bands shown in Figs. 5 and 7 to 10 apply
for ambient temperatures of -5 to + 55 °C. The trio unit can be operated at
ambient temperatures between -20 and +70 °C. However, an additional
error of + 5% may occur on the current axis at temperatures below -5 °C (or
of -5% above +55 °C respectively).
Auslöser-Ausführungen / Trip unit models
Tabelle 1 Funktionsübersicht der Auslöser-Ausführungen (x = Funktion verfügbar)
Table 1 Summary of the functions of the various trip unit models (x = function available)
Ausführung
10. Stelle 3WN…
Funktion
3WX31 41 –
Stromabhängig verzögerte Auslösung "a"
Nennbetriebsstrom einstellbar
Trägheitsgrad 10 s fest
Nennbetriebsstrom einstellbar
Trägheitsgrad einstellbar
Nennbetriebsstrom fein einstellbar
Trägheitsgrad einstellbar
Thermisches Gedächtnis zuschaltbar
Phasenausfallempfindlichkeit zuschaltbar
Phasenausfallempfindlichkeit (fest)
Kurzverzögerte Auslösung "z"
Ansprechstrom einstellbar
Verzögerungszeit einstellbar
mit I2t-Kennlinie zuschaltbar
mit Zeitverkürzter Selektivitätssteuerung zu-
schaltbar (Eingabe und Ausgabe Blockiersignal)
mit Zeitverkürzter Selektivitätssteuerung
(nur Ausgabe Blockiersignal)
Unverzögerte Auslöung "n"
Rush-unempfindlich 10 ms
unverzögert
Erdschluß-Auslösung "g"
Ansprechstrom einstellbar, Ansprechzeit
einstellbar, mit I2t-Kennlinie (zuschaltbar) und
zeitverkürzter Selektivitätssteuerung (zuschaltbar)
Stromanzeige mit LCD
Anzeigen und Fehlermeldungen, Übertemperatur
Phasen-Unsymmetrie
Störung
Überlast
"a"-Auslösung
"z/n"-Auslösung
"g"-Auslösung
Fernauslösung
Überstrom-Prüfbuchse
Erdschluß-Prüfbuchse
im Schalter eingebaut
Kommunikation
Wiedereinschaltsperre
Model
3WN… 10th character
Function
3WX31 41 –
Inverse-Time Delay Trip "a"
Rated current adjustable
Fixed time delay 10 s
Rated current adjustable
Time Delay adjustable
Rated current fine adjustable
Time delay adjustable
Thermal memory (On-Off Switch)
Phase loss sensivity (On-Off Switch)
Phase loss sensivity (fixed)
Short -Time Delay Trip "z"
Reponse current adjustable
Delay time adjustable
I2t-characteristic (On-Off Switch)
with zone selective interlocking (On-Off
Switch) (input and output blocking signal)
with zone selective interlocking send blocking
signal only
Instantaneous Trip "n"
Rush-insensitive 10 ms
Not delayed
Ground Fault Trip "g"
Response current adjustable, Response Time
adjustable with I2t-characteristic (On-Off Switch)
and zone selective interlocking (On-Off Switch)
LCD Current Display
Warning and Alarm Signals,Overtemperature
Phase unbalance
Fault
Overload
"a"-Trip
"z/n"-Trip
"g"-Trip
Remote Tripping
Overcurrent Test Connector
Ground Fault Test connector
mounted in breaker
Communication
Mechanical Reclosing Lockout
als Zubehör erhältlich/available as option
1JC
1
B
2JC
2
P
3JC
3
D
4JC
4
M
5JC
5
R
5JC12
5
R
6JC
X
6
S/T
4JD
X
7
U
6JE
8
V/W
6JE12
8
V/W
XXX X XXXX
XXXX
XX XX
XX
XXX X XXXX
XXX
XX XX
XX X
XX
XXX
XXXXX X XXXX
XXX X XX
XXX
XX
XXXX
XX
XXXXXXXX
XX XX
X
X
X
X
X
X
X
X
XX
XXX
XX
XXX
XXX X
XXX
X
4
Aufbau und Wirkungsweise Construction and mode of operation
Hinweis:
Überstromauslöser niemals unter Last (eingeschalteter
Schalter) ziehen.
Die 3WN1/5, 3WS1-Leistungsschalter dürfen nie ohne
Überstromauslöserbaustein betrieben werden, da sonst
an den W andlern im Leerlauf eine unzulässig hohe Span-
nung erzeugt wird!
Note:
Do not withdraw the trip unit under load (with the breaker
closed).
Do not operate 3WN1/5, 3WS1 circuit-breakers without
overcurrent release module since otherwise the volt-
age at the current transformers would rise to values
beyond the permissible limit s under no-load conditions.
Aufbau und Wirkungsweise
Der 3WN Überstromauslöser ist ein in Digitaltechnik mit
Mikroprozessor aufgebautes elektronisches Auslösesystem.
Das Auslösesystem besteht aus den Komponenten:
Stromwandler
Überstromauslöserbaustein
Auslösemagnet
Wiedereinschaltsperre
Die Stromwandler sind dem jeweiligen Schalternennstrom
angepaßt und, ebenso wie der Auslösemagnet und die
Einschaltsperre, fest im Schalter angeordnet.
Der Überstromauslöser ist für alle Nennströme der gleiche
und ist als steckbare Einheit ausgeführt. Er darf niemals
unter Last (eingeschalteter Schalter) gezogen werden.
Die Stromwandler werden sowohl als Meßwertgeber als
auch für die Energieversorgung des Auslösers eingesetzt, so
daß für den Betrieb keine Fremdenergie notwendig ist.
Für die Aktivierung des Auslösers ist ein bestimmter Min-
dest-Laststrom erforderlich, der folgende Größe hat:
Bei einphasigem Strom 0,35 x Wandlernennstrom
zweiphasigem Strom 0,25 x Wandlernennstrom
dreiphasigem Strom 0,2 x Wandlernennstrom
Bei Schaltern mit Erdschluß-Auslösung in allen Fällen
0,2 x Wandlernennstrom
Der Überstromauslöser gliedert sich in die Funktionsgrup-
pen (Übersichtsschaltpläne Fig. 15 und 16)
Signalaufbereitung
Signalverarbeitung (Mikroprozessor)
Ausgangsstufe
Anzeigen und Meldungen
Stromversorgung.
Der Auslösemagnet erhält vom Überstromauslöser des Auslöse-
befehl und bewirkt die mechanische Entklinkung des Schalters.
Die Wiedereinschaltsperre ist ein zweiter Magnet, der nur
unter bestimmten Bedingungen betätigt wird.
Der 3WN1/5, 3WS1 Auslöser wird in 8 verschiedenen Aus-
führungen geliefert, welche die in Tabelle 1 zusammenge-
faßten Funktionen enthalten.
Construction and mode of operation
The 3WN trip unit is static microprocessor-based overcur-
rent release consisting of the following components:
Current transformer
Solid-state overcurrent release
Trip actuator
Mechanical reclosing lockout
The current transformers are selected for the current rating of
the relevant breaker in which they are incorporated together with
the trip magnet and mechanical resetting device.
The trip unit has a plug-type housing and is suitable for all
current ratings. Do not withdraw under load (with the breaker
closed).
The current transformers can be used both as sensors and
for power supply of the trip unit. No external power source is
therefore required.
To activate the trip unit the load current must have the
following minimum values:
Single-phase current: 0,35 x rated CT current
Two-phase current 0,25 x rated CT current
Three-phase current 0,2 xrated CT current
All breakers with earth-fault tripping feature:
0,2 xrated CT current
The trip unit has the following function groups (see also block
diagrams, Fig. 15 and 16)
Signal conditioning
Signal processing (microprocessor)
Output stage
Display and signalling
Power supply.
The trip actuator receives the tripping signals from the trip
unit and effects mechanical unlatching of the breaker.
Another magnet is used for mechanical lockout and is only
activated under special conditions.
The 3WN1/5, 3WS1 release is available in 8 versions with the
tripping functions listed in Table 1.
5
Nennströme und Einstellbereiche
Der Nennstrom IN des Auslösers ist gleich dem Primär-Nennst-
rom der angeschlossenen Stromwandler. Für die 3 Schalter-
baugrößen sind Wandler mit den in Tabelle 2 angegebenen
Nennströmen lieferbar.
Die Skalenwerte der Einstellströme der verschiedenen Auslö-
sefunktionen sind entweder in Vielfachen des Wandlernenn-
stromes IN oder in Vielfachen des Einstellstromes Ir der strom-
abhängig verzögerten Auslösung angegeben.
Die Einstellung geschieht mit Stufenschaltern in festen Schrit-
ten (Zwischeneinstellungen ergeben undefinierte Werte).
Die einzelnen Strom- und Zeiteinstellbereiche sind in Tabelle 3
zusammengefaßt.
Fig. 3 und 4 zeigt die Frontplatte eines Auslösers 3WX31 41–1
bzw. 3WX31 41–6 mit den Bedienungs- und Anzeigeorganen.
Nennströme und Einstellbereiche
Current ratings and setting ranges
The rated current IN of the release is identical to the rated
primary current of the current transformers connected. The
current transformers for the 3 breaker sizes are available
with the current ratings specified in Table 2.
The scale intervals of the setting currents for the various
operating functions are either a multiple of the rated CT cur-
rent IN or a multiple of the setting current Ir for inverse-time
operation.
Stepping switches are used for setting (Intermediate posi-
tions will result in undefined values).
The setting ranges for current and time are listed in Table 3.
Figs. 3 and 4 show the front panels of release models 3WX31
41–1 and 3WX31 41–6, complete with controls and display.
Current ratings and setting ranges
1.1 Wahl des Einstellstromes der stromabhängig verzögerten
Auslösung
Selection of setting current for inverse-time delay operation
3.1 Einstellung des Ansprechstromes der unverzögerten Auslösung
Setting of response current for instantaneous operation
9.1 Überstrom-Prüfbuchse (X12)
Overcurrent test socket
Fig. 3 Auslöser 3WX31 41—1, Ausführung "an"
3WN release 3WX31 41—1, ("an")
1.1
3.1
9.1
6
Nennströme und Einstellbereiche Current ratings and setting ranges
Legend for fig. 4
Inverse-time function ("a" release)
1.1 Setting current
1.2 Setting of time lag class characteristic
1.3 LED for trip indication
1.4 Fine Setting
Short-time-delay function ("z" release)
2.1 Setting of response current
2.2 Setting of time lag
2.3 LED for trip indication
Short-circuit function ("n" release)
3.1 Setting of operating current
2.3 LED for trip indication
Earth-fault-activated function ("g" release)
4.1 Setting of response current
4.2 Setting of time lag
4.3 LED for trip indication
Selector switch for additional functions
(position 0 = function ineffective
position 1 = function effective)
5.1 Thermal memory for inverse-time delay
operation
5.2 l2t characteristic for short-time-delay
operation
5.3 Zone selective interlocking for short-
time-delay and earth-fault-activated
operation
5.4 l2t characteristic for earth-fault-activated
operation of release 3WX31 41—6JE
5.5 Phase failure protection on release
3WX31 41—5, —6JE
LEDs for the following indications
6.1 Overtemperature
6.2 Phase unbalance
6.3 Fault
7.1 Liquid Crystal Display to
Phase Current Metering
7.2 Pushbutton for current measurement
7.3 Plug for circuit-breaker for setting the
measuring range
8.1 Resetting button for stored messages
9.1 Overcurrent test socket (X 12)
Legende zu Fig. 4
Stromabhängig verzögerte
Auslösung ("a")
1.1 Wahl des Einstellstromes
1.2 Einstellung des Trägheitsstromes
1.3 Leuchtdiode für Auslösemeldung
1.4 Feinstellung
Kurzverzögerte Auslösung ("z")
2.1 Einstellung des Ansprechstromes
2.2 Einstellung der Verzögerungszeit
2.3 Leuchtdiode für Auslösemeldung
Kurzschluß Auslösung ("n")
3.1 Einstellung des Ansprechstromes
2.3 Leuchtdiode für Auslösemeldung
Erdschluß-Auslösung ("g")
4.1 Einstellung des Ansprechstromes
4.2 Einstellung der Verzögerungszeit
4.3 Leuchtdiode für Auslösemeldung
Wahlschalter für Zusatzfunktionen
(Stellung 0: Funktion unwirksam
Stellung 1: Funktion wirksam)
5.1 Thermisches Gedächtnis für strom-
abhängig verzögerte Auslösung
5.2 l2t -Kennlinie für kurzverzögerte
Auslösung
5.3 Zeitverkürzte Selektivitäts-Steuerung
für kurzverzögerte und Erdschluß-
Auslösung
5.4 l2t-Kennlinie für Erdschluß-Auslösung
bei Auslöser 3WX31 41–6JE
5.5 Phasenausfallschutz bei Auslöser
3WX31 41–5, –6JE
Leuchtdiode für Meldung
6.1 Übertemperatur
6.2 Phasen-Unsymmetrie
6.3 Störung
7.1 Flüssigkristallanzeige für Betriebs-
strommessung
7.2 Taster für Strommessung
7.3 Verschlußstopfen für Schalter zur
Meßbereichseinstellung
8.1 Rückstellknopf für gespeicherte
Meldungen
9.1 Überstrom-Prüfbuchse (X12)
Fig. 4 Auslöser 3WX31 41—6 Ausführung "azng"
3WN release 3WX31 41—6 ("azng")
Schalterbaugröße I/1 I/2 II III IV
Breaker size Wandler-Nennstrom IN
CT rated current IN
A
315 500
400 630 1600
500 800 1250 2000
630 1000 1600 2500
800 1250 2000 3200 5000
1000 1600 2500 4000 6000
Tabelle 3 Einstellbereiche der Auslösefunktionen
Table 3 Setting ranges of release functions
Stromabhängig verzögerte Auslösung "a" Kurzverzögerte Auslösung "z"
Inverse-time delay function ("a" release) Short-time-delay function ( "z" release)
3WX31 41 3WX31 41
–1 bis/to –6 –1JC, –2JC –3JC, –4JC, –4JD, –3 bis/ –3JC, –4JC, –4JD, –6JC
und/and –6JC –5JC, –6JE to –6 –5JC,–6JE
IrTcTcIdtdtd
x INss x Irms ms
0,4…1 10 2…30 2…12 10, 80, 150, 220, 10, 30, 50, 80, 150,
400, 500 220, 330, 400, 500
Kurzschluß Auslösung "n" Erdschluß Auslösung "g"
Short-circuit function ("n" release) Earth-fault-activated function ("g" release)
Rush unempfindlich unverzögert
rush-insensitive undelayed
3WX31 41 3WX31 41 3WX31 41
–1 und/and –2 –3 bis/to –6 –6JE und/and –6JC
IiIiIgtg
x Irx INx INms
2…12 10 2…20, × 0,2…0,7 100…400
7.1
5.4
5.3
5.2
5.1
1.1
1.4
1.2
2.1
2.2
3.1
4.1
4.2
9.1
7.2
6.1
6.2
6.3
1.3
2.3
4.3
8.1
I N: Wandler-Nennstrom
I r: Einstellstrom der stromabhängig verzögerten Auslösung ("a")
Tc: Trägheitsgrad der stromabhängig verzögerten Auslösung
Id: Ansprechstrom der kurzverzögerten Auslösung ("z")
td: Verzögerungszeit der kurzverzögerten Auslösung
Ii: Ansprechstrom der Kurzschluß-Auslösung ("n")
Ig: Ansprechstrom der Erdschluß-Auslösung ("g")
tg: Verzögerungszeit der Erdschluß-Auslösung
Tabelle 2 Zuordnung von Wandler-Nenn-
strömen und Schalterbaugrößen
Table 2 CT rated current and corresponding
breaker size
I N: CT rated current
I r: Setting current of inverse-time delay function ("a" release)
Tc: Time lag class characteristic of inverse-time delay function
Id: Operating current of short-time delay function ("z" release)
td: Time lag of short-time delay function
Ii: Operating current of short-circuit release ("n" release)
Ig: Operating current of earth-fault-activated function ("g" release)
tg: Time lag of earth-fault-activated function
7.3
7
Stromabhängig verzögerte Auslösung ("a"-Auslösung)
Die stromabhängig verzögerte Auslösung dient dem Schutz
von Verbrauchern und Leitungen vor Überlast.
Auslösekennlinien und Einstellbereiche:
Der Einstellstrom Ir der stromabhängig verzögerten Auslö-
sung ist in 13 Stufen, bzw. bei den Auslösern -4JD und -6JE
in 1/100 Stufen von
0,4 bis 1 x IN
wählbar (IN = Wandlernennstrom), außer bei den Überstrom-
auslösern mit den Primärnennströmen 315 A und 400 A der
schalterinternen Stromwandler, bei denen die Einstellung
des Einstellstromes Ir < 0,5 x IN zu vermeiden ist.
Damit wird auch bei ein- oder zweipoliger Überlast die stromab-
hängige Auslösung sichergestellt. Der Trägheitsgrad Tc, ist die Aus-
lösezeit bei dem 6-fachen Wert des Einstellstromes Ir.
Dieser ist bei den Auslösern 3WX31 41-1, -2 und -6JC auf 10 s fest
eingestellt und bei den Auslösern 3WX31 41-3 bis -6 in 6 Stufen von
2 bis 30 s
einstellbar. Die Auslösekennlinien sind in Fig. 6 dargestellt.
Die Auslösekennlinien gelten unabhängig davon, ob eine 1-
, 2- oder 3phasige Belastung vorliegt.
Die Auslösezeiten sind unabhängig von Vorbelastungen mit
Strömen unterhalb des 1,12fachen Einstellstromes, d. h. es
besteht im Gegensatz zu herkömmlichen Bimetallauslösern
kein Unterschied zwischen "kalter" und "warmer" Kennlinie.
Bei den Auslösern 3WX31 41-1, -2 et -6JE, ist der Einstell-
strom Ir der stromabhängig verzögerten Auslösung in 60
Stufen von 0,41 bis 1,0 x IN wählbar.
Dazu ist mit dem Schalter 1.1 die Zehntel-Stelle und mit dem
Schalter 1.4 die Hundertstel-Stelle zu wählen (siehe Fig. 4).
Beispiel 1: Schalter 1.1 auf 0.7, Schalter 1.4 auf 0.05
Ir= (0.7 + 0.05) x IN
= 0.75 x IN
Beispiel 2: Schalter 1.1 auf 0.9, Schalter 1.4 auf 0.1
Ir= (0.9 + 0.1) x IN
= 1 x IN
"Thermisches" Gedächtnis
Nach einer Überlastauslösung ist sofortiges Wiedereinschal-
ten des Leistungsschalters möglich.
Wenn beim Wiedereinschalten erneut ein Überstrom fließt, wird
normalerweise wieder die volle Auslösezeit entsprechend der
eingestellten Auslösekennlinie wirksam. Es sind daher wieder-
holt Motorenanläufe mit voller Anlaufzeit möglich.
Wenn dieses Verhalten nicht erwünscht ist, kann mit dem Schalter
5.1 (Fig. 4) das "thermische" Gedächtnis eingeschaltet werden. Mit
dieser Zusatzfunktion erhält man beim Wiedereinschalten eine
verkürzte Auslösezeit, deren Länge von der Wartezeit bis zum
Wiedereinschalten abhängt. Sofortiges Wiedereinschalten ergibt
eine nahezu unverzögerte Auslösung, nach etwa 10 Minuten
Wartezeit wird wieder die volle Auslösezeit erreicht.
Phasenausfallempfindlichkeit
Mit der Phasenausfallempfindlichkeit können Motoren vor unzuläs-
siger Erwärmung durch Zweiphasenlauf geschützt werden.
Die Phasenausfallempfindlichkeit wird mit dem Schalter 5.4
(Fig. 4) eingeschaltet. Sie wird wirksam, wenn der Strom in einer
Phase unter 50% des Wertes der anderen Phasen sinkt.
Dadurch wird eine Parallelverschiebung der Auslösekennlinien um
20% nach links (in Richtung kleinerer Ströme) bewirkt. Die strom-
abhängig verzögerte Auslösung arbeitet dann so, als ob sie auf
einen Wert von 80% des Einstellstromes Ir eingestellt wäre.
Auslösefunktionen
Inverse-time delay operation ("a" release)
The inverse-time delay function serves to protect loads and
lines in the overload.
Operating characteristics and setting ranges:
The setting current Ir for inverse- time operation is adjustable
in 13 steps, and for the releases -4JD and -6JE in 1/100 steps
between
0,4 and 1 x IN
(IN = transformer rated current), respectively, except on the
overcurrent releases (with primary rated current 315 A and
400 A) of the breaker-internal current transformers, on which
the current setting Ir < 0,5 x IN is to be avoided.
Thus, a single-pole or two-pole overload properly trips the
inverse-time delay unit. The time lag class Tc , is defined as
the operating time at 6 times the setting current Ir.
This is fixed on 3WX31 41-1, -2 y -6JC, and 10 s and is
adjustable in 6 steps between
2 and 30 s
in models 3WX31 41-3 a -6. The tripping characteristics
which are shown in Fig. 6 are identical for single-phase, two-
phase or three-phase loads.
Preceding load currents of less than 1.12 times setting
current have no effect on the operating time, i. e. unlike in
conventional bimetal releases, the warm-state and cold-
state characteristics are identical.
The current Ir of releases 3WX31 41-4JD and -6JE for inverse
time delay operation can be selected in 60 steps of 0,41 to 1,0 x IN.
For this purpose, the one-tenth position must be selected with
switch 1.1 and the one-hundreth with switch 1.4 (see Fig. 4).
Example 1: Switch 1.1 to 0.7, Switch 1.4 to 0.05
Ir= (0.7 + 0.05) x IN
= 0.75 x IN
Example 2: Switch 1.1 to 0.9, Switch 1.4 to 0.1
Ir= (0.9 + 0.1) x IN
= 1 x IN
"Thermal" memory
After overload tripping the circuit-breaker can be instantly
reclosed.
In general, the full operating time corresponding to the preset
tripping characteristics takes effect, if overcurrent recurs
after reclosing. Several consecutive motor starts (full time)
are therefore possible without the release operating.
If this not desirable, a "thermal memory" can be cut in by
switch 5.1 (Fig. 4). After reclosing the response time then
corresponds to the time interval between wait-time and
reclosing. If a circuit-breaker is reclosed immediately, it is
practically instantly retripped. After approx. 10 min. wait-
time the full response time is restored.
Phase Loss Sensitivity
With phase failure protection, motors can be protected against
impermissible temperature rise by means of two-phase running.
The phase failure protection is switched on by means of
switch 5.4 (Fig. 4). It becomes effective when the current in
one phase falls below 50% of the value in the other.
This causes a parallel shift of the tripping characteristics by
20% to the left (in the direction of lower currents). The
inverse-time delay release then functions as though it had
been set at value of 80% of the setting current Ir.
Operating functions
8
Kurzverzögerte Auslösung ("z"-Auslösung)
Die kurzverzögerte Auslösung dient der selektiven Abschal-
tung von fehlerbehafteten Abzweigen in Verteileranlagen.
Stromunabhängig verzögerte Auslösung
Einstellbereiche und Kennlinien:
Die stromunabhängig verzögerte Auslösung arbeitet mit konstanter
Verzögerungszeit. Der Ansprechstrom /d ist in 9 Stufen von
2 bis 12 x /r
einstellbar (/r = Einstellstrom der stromabhängig verzögerten
Auslösung). Die Verzögerungszeit td ist in 9 Stufen von
10 bis 500 ms
einstellbar.
Die Auslösekennlinien sind in Fig. 6a dargestellt.
l2td -Kennlinie
Um bessere Selektivität mit nachgeschalteten Sicherungen
zu erreichen, kann anstelle der konstanten Verzögerungs-
zeit mit dem Schalter 5.2 (Fig. 4) auf eine l2td-Kennlinie um-
geschaltet werden. Durch das Umschalten erhält man eine
Kennlinie mit stromabhängiger Verzögerungszeit bei kon-
stantem l2td-Wert (Fig. 6b).
Die l2td-Kennlinie gilt nur bis zum Schnittpunkt mit der je-
weils eingestellten Verzögerungszeit td. Bei höheren Strö-
men ist wieder die konstante Zeit td wirksam.
Zeitverkürzte Selektivitäts-Steuerung
Mit der zeitverkürzten Selektivitäts-Steuerung kann in Ver-
teileranlagen mit mehreren hintereinander geschalteten
Schaltern eine selektive Auslösung erreicht werden, ohne
daß die mit der üblichen zeitgestaf felten Selektivität verbun-
denen, unter Umständen unerwünscht langen, V erzögerungs-
zeiten auftreten.
Die zeitverkürzte Selektivitäts-S teuerung wird mit dem Schal-
ter 5.3 (Fig. 4) eingeschaltet und arbeitet nur, wenn nicht
gleichzeitig die l2td-Kennlinie eingeschaltet ist.
Durch das Aktivieren der zeitverkürzten Selektivitäts-Steue-
rung wird die Funktion der stromunabhängig verzögerten
Auslösung wie folgt verändert:
Die Verzögerungszeit wird auf 50 ms herabgesetzt, unabhän-
gig von einem auf der Skala eingestellten höheren Wert td.
Der Auslöser gibt ein Ausgangssignal (Blockiersignal) an den
übergeordneten Schalter ab, wenn der Strom-Ansprechwert der
stromunabhängig verzögerten Auslösung überschritten wird.
Das an den Signaleingang des übergeordneten Schalters
angelegte Blockersignal bewirkt eine vorübergehende Sper-
rung der stromunabhängig verzögerten Auslösung bis zum
Ablauf der eingestellten Verzögerungszeit td.
Der Auslöser 3WX31 41–4JD gibt ein Ausgangssignal (Blok-
kiersignal) ab, wenn der Stromansprechwert der stromun-
abhängig verzögerten Auslösung überschritten wird. Er kann
jedoch keine Blockiersignale von untergeordneten Schaltern
empfangen. Die Auslöser 3WX31 41–5JE und –6JE können
Blockiersignale sowohl abgeben wie empfangen. Die Auslö-
ser 3WX31 41–1, –2, –3, –4JC und –6JE bieten nicht die
Möglichkeit der Zeitverkürzten Selektivitätssteuerung.
Auslösefunktionen Operating functions
Short-time-delay operation ("z"-release)
The short-time delay operation is used for selective tripping
of faulted feeders in distribution systems.
Definite-time delay operation
Setting ranges and characteristics:
The response current Id is adjustable in 9 steps between
2 and 12 x /r
(/r = response current for inverse-time operation). This func-
tion uses a time lag td which is adjustable in 9 steps between
10 and 500 ms
The tripping characteristics are shown in Fig. 6a.
l2td characteristic
To improve the selectivity obtained by the load-side fuses,
change-over from a fixed time lag to an l2td characteristic
can be effected by switch 5.2 (Fig. 4).
The characteristic is then set for inverse-time lag at con-
stant l2td (Fig. 6b).
The l2td characteristic only take effect up to the point of in-
tersection with the preset time lag td. At higher currents time
lag td turns constant again.
Zone selective interlocking
If used in distribution systems with several circuit-breakers
connected in series, zone selective interlocking helps to avoid
undesirable long delays which may occur with time-graded
selectivity.
Zone selective interlocking is selected by switch 5.3 (Fig. 4)
and only becomes effective if an l2td characteristic is not
preset simultaneously.
By activating zone selective interlocking the definite-time
delay tripping functions are changed as follows:
The time lag is reduced to 50 ms irrespective of a possibly
higher td value preset on the scale.
The release outputs a blocking signal to the upstream cir-
cuit-breaker, if the current response value for definite-time
delay operation is exceeded;
The blocking signal applied to the input of the upstream cir-
cuit-breaker temporarily blocks definite-time operation until
the preset time lag td has elapsed.
Release 3WX31 41–4JD outputs a blocking signal when the
current response value for definite-time delay operation is
exceeded. But it cannot receive blocking signals from sec-
ondary switches. Releases 3WX31 41–5JE and –6JE can
both initiate and receive blocking signals. Releases 3WX31
41–1, –2, –3, –4JC and –6JE do not offer the possibility of
zone selective interlocking.
9
Mode of operation of the zone selective interlocking (Fig. 5)
The releases of the breakers to be graded are interconnect-
ed by control leads, i.e. the signal output (s) of a down-
stream breaker (s) is (are) connected to the signal input of
the upstream breaker.
The time lags are graded as usual, e.g. breakers 31, 32, 33
are set for 10 ms, breakers 21, 22 for 80 ms, breaker 11 for
150 ms.
In the event of a short-circuit in point A the releases of break-
ers 21 and 11 are activated. Breaker 11 receives a blocking
signal from breaker 22 and is not tripped, whereas breaker
22 receives no blocking signal and his tripped after 50 ms. If
breaker 22 is faulted and fails to break the circuit, breaker
11 opens after 150 ms (= time lag td preset) in spite of a
blocking signal being present.
In the event of a short-circuit in point B no current flows in
any of the downstream circuit-breakers. Breaker 11 does
not therefore receive any blocking signal and his tripped af-
ter 50 ms. Without a discriminating tripping function with
shortened grading breaker 11 would only open after 150 ms.
The time gain is even greater the more grading levels exist
and the longer the resulting time lags are.
Wirkungsweise der zeitverkürzten Selektivitäts-Steuerung
(Fig. 5)
Der Auslöser der zu staffelnden Schalter sind durch Signal-
leitungen untereinander verbunden, und zwar jeweils der Si-
gnalausgang eines nachgeordneten Schalters (oder mehre-
rer) mit dem Signaleingang des übergeordneten Schalters.
Die Verzögerungszeiten werden wie üblich gestaffelt einge-
stellt, z.B. die Schalter 31, 32, 33 auf 10 ms, Schalter 21, 22
auf 80 ms und Schalter 11 auf 150 ms.
Bei einem Kurzschluß am Punkt A sprechen die Auslöser
der Schalter 22 und 1 1 an. Der Schalter 11 erhält vom Schal-
ter 22 das Blockiersignal und löst nicht aus, der Schalter 22
erhält kein Blockiersignal und löst nach 50 ms aus. Sollte
der Schalter 22 wegen eines Defektes den Strom nicht ab-
schalten, würde der Schalter 11 trotz des anstehenden Blok-
kiersignals nach 150 ms (= eingestellte Zeit td) auslösen.
Bei einem Kurzschluß am Punkt B durchfließt der Strom kei-
nen der nachgeordneten Schalter. Der Schalter 11 erhält
daher kein Blockiersignal und löst nach 50 ms aus. Ohne
zeitverkürzte Selektivitäts-Steuerung würde der Schalter 11
dagegen erst nach 150 ms auslösen. Dieser Zeitvorteil wird
um so größer, je mehr Staffelebenen in ausgedehnten Anla-
gen vorhanden sind und je länger die dadurch erforderli-
chen Verzögerungszeiten werden.
Operating functionsAuslösefunktionen
A
B
11
X5/4
X5/3
X5/4
X5/3
X5/2
X5/1
X5/4
X5/3
X5/2
X5/1
X5/2 X5/2
X5/1
X5/2
X5/1
21
31 32 33
22
X5/1
Fig. 5 Verteileranlage mit Zeitverkürzter Selektivitäts-Steuerung
Distribution system with zone selective interlocking
X5/1 - X5/2: Signalausgang
X5/1 - X5/2: signal output
X5/3 - X5/4: Signaleingang
X5/3 - X5/4: signal input
10
Auslösefunktionen Operating functions
Fig. 6a Auslösekennlinien der stromabhängig verzögerten und kurzverzögerten Auslösung
Operating characteristic of inverse-time and short-time function ("a" and "z" releases)
Kurzverzögerte Auslösung stromunabhängig verzögert
Short-time delay function definite-time delayed
2x
3x
5 x
a
d
ms
500
400
300
220
150
80
50
30
10
4x
6x
z
8x
12x
30 s
17 s
10 s
6 s
3,5 s
2s
60
min
30
20
10
5
2
1
1000
500
200
100
50
20
10
5
2
1
0,5
0,2
0,1
0,05
0,02
0,01
0,005
s
15 20 30 40 50 60 80 100
11,5 2 3 4 5 6 8 10 150
Öffnungszeit/Opening time
Strom
Current
Einstellstufen für Id
als Vielfaches von Ir
(5 x Ir nicht dargestellt)
Setting range of Id
as multiple of Ir
(5 x Ir not demonstrated)
Verzögerungszeiten
td = 30, 50, 220 und
400 ms nicht dargestellt
Delay times
td = 30, 50, 220 and
400 ms not demonstrated
11
Auslösefunktionen Operating functions
Fig. 6b Auslösekennlinien der stromabhängig verzögerten und kurzverzögerten Auslösung
Operating characteristic of inverse-time and short-time function ("a" and "z" releases)
Kurzverzögerte Auslösung I2-abhängig verzögert
Short-time delay function I2-dependently delayed
60
min
30
20
10
5
2
1
1000
500
200
100
50
20
10
5
2
1
0,5
0,2
0,1
0,05
0,02
0,01
0,005
s
15 20 30 40 50 60 80 100
11,5 2 3 4 5 6 8 10 150
2x
3x
5 x
a
d
ms
500
400
300
220
150
80
10
4x
6x
z
8x
12x
30 s
17 s
10 s
6 s
3,5 s
2s
Öffnungszeit/Opening time
Strom
Current
Einstellstufen für Id
als Vielfaches von Ir
(5 x Ir nicht dargestellt)
Setting range of Id
as multiple of Ir
(5 x Ir not demonstrated)
Verzögerungszeiten
td = 220 und 400 ms nicht
dargestellt
Delay times
td = 220 and 400 ms not
demonstrated
12
Kurzschluß-Auslösung ("n"-Auslösung)
Rush unempfindliche Kurzschluß-Auslösung
Auslöser Ausführung "an"
Einstellbereich:
Der Ansprechstrom Ii ist in 9 Stufen von
2 bis 12 x Ir
einstellbar (Ir = Einstellstrom der stromabhängig verzöger-
ten Auslösung).
Verzögerungszeit:
Zur Unterdrückung von kurzzeitigen Einschwingvorgängen ist
eine Verzögerungszeit von 10 ms fest vorgegeben (Fig. 7).
Unverzögerte Auslösung
Auslöser Ausführung "azn/azng"
Einstellbereich:
Der Ansprechstrom Ii ist in 8 Stufen von
2 bis 20 x IN, bzw. ×
einstellbar (IN = Wandlernennstrom). In einer weiteren, mit ×
bezeichneten Schalterstellung ist die unverzögerte Auslösung
außer Funktion. Der Kurzschlußschutz wird dann nur noch durch
die stromunabhängig verzögerte Auslösung bewirkt. Bei der
Wahl dieser Schalterstellung ist daher zu beachten, daß der
maximale zu erwartende Kurzschlußstrom den Nennkurzzeit-
strom des zugehörigen Schalters nicht überschreitet.
Die Öffnungszeit der unverzögerten Auslösung beträgt etwa
30 ms (Fig. 8).
Erdschluß-Auslösung ("g"-Auslösung)
Das Erdschluß-Signal wird mit einem Summenstrom-Wand-
ler aus den Sekundärströmen der 3 (bzw. 4, wenn der Neu-
tralleiter mit auf Erdschluß überwacht wird) Stromwandler
gebildet.
Der 4. W andler ist bei 4poligen Schaltern im Schalter einge-
baut, bei 3poligen Schaltern muß er extern angeordnet wer-
den. Er wirkt nur auf die Erdschluß-Auslösung, nicht jedoch
auf die Überstromauslösung.
Der Summenstrom-Wandler ist im Schalter, jedoch außer-
halb des Auslösergehäuses untergebracht.
Wird das Erdschluß-Signal durch einen externen, anlagen-
seitigen Summenstrom-Wandler erzeugt, muß der interne
Summenstrom-Wandler durch Umlegen einer steckbaren
Drahtbrücke unwirksam gemacht werden (Fig. 16/17).
Einstellbereich:
Der Ansprechstrom Ig der Erdschluß-Auslösung ist in 6 Stu-
fen von
0,2 bis 0,7 x IN
einstellbar (IN = Wandlernennstrom). In einer weiteren, mit
× bezeichneten Schalterstellung ist die Erdschluß-Auslösung
unwirksam.
Für Anwendungsfälle, in denen von den Vorschriften einer
Begrenzung des maximal einzustellenden Ansprechstromes
gefordert wird, kann der Auslöser mit einem eingeengten
Einstellbereich geliefert werden, bei dem die höheren Ein-
stellwerte blockiert sind.
Short-circuit function ("n" release)
Rush-insensitive short-circuit operation
Release design "an"
Setting range:
The response current Ii is adjustable in 9 steps between
2 and 12 x Ir
(Ir = setting current for inverse-time delay operation).
Time lag:
For suppression of short-time transient phenomena a time
lag of 10 ms is preset (Fig. 7).
Instantaneous operation
Release design "azn"/"azng"
Setting range:
The response current Ii is adjustable in 8 steps between
2 and 20 x IN, or ×
(IN = rated CT current). With the switch set to × the instanta-
neous function becomes ineffective. Short-circuit protection
is then only provided by the definite-time delay function.
When selecting this switch position make sure that the max-
imum short-circuit current does not exceed the rated short-
time current of the associated breaker.
The opening time for instantaneous release is approx. 30
ms (Fig. 8).
Earth-fault-activated operation ("g" release)
The earth-fault signal is generated by a summation current
transformer from the secondary currents of the 3 (or 4, if the
neutral conductor is also monitored for earth-faults) current
transformers.
With four-pole breakers the fourth current transformer is incor-
porated in the breaker, with three-pole breakers it must be ar-
ranged externally. The transformer only intervenes if operation
is initiated by an earth-fault and not by overcurrent.
The summation current transformer is mounted inside the
breaker, but outside the release housing.
If the earth-fault signal is generated by an externally mount-
ed summation current transformer, the internal summation
current transformer must be jumpered (Fig. 16/17).
Setting range:
The response current Ig for earth-fault-activated operation
is adjustable in 6 steps between
0,2 and 0,7 x IN
(IN = rated CT current). With the switch set to ×, the earth-
fault-activated function is ineffective.
For applications for which regulations stipulate limitation of
the maximum response current, the release can also be sup-
plied with limited setting range in which the higher setting
values are blocked.
Auslösefunktionen Operating functions
13
Fig. 7 Auslösekennlinien der unverzögerten Auslösung "n"
Operating characteristic of instantaneous function ("n" release)
Auslöser-Ausführung 3WX31 41 —1 und —2
Release versions 3WX31 41 —1 and —2
Auslösefunktionen Operating functions
2x
4x
6x
8x
12x
3x
x
5
n
a
60
min
30
20
10
5
2
1
1000
500
200
100
50
20
10
5
2
1
0,5
0,2
0,1
0,05
0,02
0,01
0,005
s
15 20 30 40 50 60 80 100
11,5 2 3 4 5 6 8 10 150
Öffnungszeit/Opening time
Strom
Current
Einstellstufen für Ii
als Vielfaches von Ir
(5 x Ir nicht dargestellt)
Setting range of Ii
as multiple of Ir
(5 x Ir not demonstrated)
Tc
10 s (festeingestellt)
(fixed)
14
2x 4x 6x 8x 12x 20x
x
16
n
60
min
30
20
10
5
2
1
1000
500
200
100
50
20
10
5
2
1
0,5
0,2
0,1
0,05
0,02
0,01
0,005
s
15 20 30 40 50 60 80 100
11,5 2 3 4 5 6 8 10 150 200 300
Auslösefunktionen Operating functions
Fig. 8 Auslösekennlinien der unverzögerten Auslösung "n"
Operating characteristic of instantaneous function ("n" release)
Auslöser-Ausführung 3WX31 41 —3JC bis –6JC
Release versions 3WX31 41 —3JC to –6JC
Öffnungszeit/Opening time
Strom
Current
Einstellstufen für Ii
als Vielfaches von I N
(16 x IN nicht dargestellt)
Setting range of Ii
as multiple of IN
(16 x IN not demonstrated)
15
Stromunabhängige Verzögerungszeit (tg)
Die Verzögerungszeit tg der Erdschluß-Auslösung ist strom-
unabhängig und in 3 Stufen von
100 bis 400 ms
einstellbar (Fig. 9).
l2tg-Kennlinien
Mit dem Schalter 5.4 (Fig. 4) kann die Erdschluß-Auslösung
von stromunabhängiger Verzögerung auf eine stromabhängi-
ge Verzögerung mit konstantem I2tg-Wert umgestellt werden.
Der Verlauf der I2tg-Kennlinien ist in Fig. 10 dargestellt. Die
I2tg-Kennlinien gelten nur bis zum Schnittpunkt mit der je-
weils eingestellten Verzögerungszeit tg. Bei höheren Strö-
men ist wieder die konstante Zeit tg wirksam.
Intermittierender Erdschluß
Wenn der Erdschlußstrom vor Ablauf der Verzögerungszeit
wieder unter den eingestellten Ansprechwert sinkt, wird die
bereits aufgelaufene Zeit etwa 750 ms lang gespeichert.
Überschreitet der Erdschlußstrom innerhalb dieser Zeit er-
neut den Ansprechwert, wird die Verzögerungszeit von dem
gespeicherten Wert aus weitergezählt. Damit wird erreicht,
daß bei einem intermittierenden Erdschluß trotz der Zeitver-
zögerung eine Auslösung zustande kommt.
Dies gilt jedoch nur dann, wenn die Energieversorgung des
Auslösers nicht unterbrochen wird, d.h. wenn neben dem Erd-
schlußstrom noch ein Laststrom von mindestens 0,7 x IN fließt.
Zeitverkürzte Selektivitäts-Steuerung (für Erdschluß)
Diese Zeitfunktion ist mit der entsprechenden Funktion der
stromunabhängig verzögerten Auslösung gekoppelt und ist in
gleicher Weise auch für die Erdschluß-Auslösung wirksam.
Durch das Einschalten des Funktions-Wahlschalters 5.3
(Fig. 4) wird die Verzögerungszeit der Erdschluß-Auslösung
auf 100 ms herabgesetzt, unabhängig von einem auf der
Skala eingestellten höheren Wert tg.
Beim Auftreten eines Erdschluß-Stromes löst der Auslöser
dementsprechend nach 100 ms aus, sofern er kein Blocki-
ersignal von einem nachgeordneten Schalter erhält. Mit
anstehendem Blockiersignal dagegen wird die Auslösung bis
zum Ablauf der eingestellten Verzögerungszeit tg gesperrt.
Danach löst der Auslöser den Schalter aus, falls der nach-
geordnete Schalter den Fehler nicht abgeschaltet hat.
Das Blockiersignal und die zwischen den Schaltern zu verle-
genden Signalleitungen sind gemeinsam für die stromunab-
hängig verzögerte und für die Erdschluß-Auslösung.
Die zeitverkürzte Selektivitäts-Steuerung arbeitet nur dann,
wenn nicht gleichzeitig die I2tg-Kennlinie eingeschaltet ist.
Definite-time lag class ("tg")
The earth-fault-activated function uses a time lag tg adjust-
able in 3 steps between
100 and 400 ms (Fig. 9).
I2tg-characteristics
The earth-fault-activated function can also be set for inverse-
time lag at constant I2tg instead of for definite-time lag. This
is possible by means of switch 5.4 (Fig. 4).
The I2tg characteristic is shown in Fig. 10 and only takes
effect up to the point of intersection with the preset time lag
tg. With higher currents the definite time lag tg is used again.
Intermittent earth-fault
If an earth-fault current drops below the preset response
value before the time lag has expired, the time already
elapsed is stored for approx. 750 ms. If the earth-fault cur-
rent re-exceeds the response value within that period, the
time lag continuous to count from the value stored.
Safe operation is thus possible even with intermittent earth-
faults provided power supply of the release is not interrupt-
ed, i.e. a minimum load current of 0.2 x IN must flow in
addition to the earth-fault current.
Zone selective interlocking (for earth-fault-activated
operation)
This additional function is coupled to the corresponding
definite-time function and can also be used for earth-fault-
activated operation.
Irrespective of a higher tg value preset on the scale the time
lag for earth-fault-activated operation is reduced to 100 ms
by closing the function selector switch 5.3 (Fig. 4).
If an earth-fault current flows the trigger is activated after 100
ms unless blocked by the blocking signal of a downstream
circuit-breaker, in which case operation is blocked until the
preset time lag tg has elapsed. After this, the circuit breaker
is tripped unless the fault has not been cleared by the
downstream circuit breaker.
The signalling leads between the breakers and the blocking
signals are used both for definite-time and earth-fault-acti-
vated operation.
The zone selective interlocking only becomes effective if the
I2tg characteristics is not preset simultaneously.
Auslösefunktionen Operating functions
16
Auslösefunktionen Operating functions
Fig. 9 Auslösekennlinien der Erdschluß-Auslösung
Operating characteristic of earth-fault-activated function
Stromunabhängige Verzögerung
Definite-time lag
0,2x 0,3x 0,5x 0,7x
g
g
ms
400
250
100
0,4 x 0,6 x
0,1 0,15 0,2 0,3 0,4 0,6 0,8 11,5 2 3 4 5 6 8 10 15
60
min
30
20
10
5
2
1
1000
500
200
100
50
20
10
5
2
1
0,5
0,2
0,1
0,05
0,02
0,01
0,005
s
Öffnungszeit/Opening time
Strom
Current
Einstellstufen für Ig
als Vielfaches von IN
(0,4 und 0,6 x IN nicht dargestellt)
Setting range of Ig
as multiple of IN
(0,4 and 0,6 x IN not demonstrated)
17
Auslösefunktionen Operating functions
Fig. 10 Auslösekennlinien der Erdschluß-Auslösung
Operating characteristic of earth-fault-activated function
I2-abhängigeVerzögerung
I2-time lag
0,2x 0,3x
0,7x
g
g
ms
400
250
100
0,4 x 0,6 x
0,5x
60
min
30
20
10
5
2
1
1000
500
200
100
50
20
10
5
2
1
0,5
0,2
0,1
0,05
0,02
0,01
0,005
s
0,1 0,15 0,2 0,3 0,4 0,6 0,8 11,5 2 3 4 5 6 8 10 15
Öffnungszeit/Opening time
Strom
Current
Einstellstufen für Ig
als Vielfaches von IN
(0,4 und 0,6 x IN nicht dargestellt)
Setting range of Ig
as multiple of IN
(0,4 and 0,6 x IN not demonstrated)
18
Anzeigen und Meldungen Display and signalling
Display and signalling
Current display (only for releases 3WX31 41–5JC and –6JE)
The actual current of the phase carrying the highest load is
displayed by a five-digit seven-segment LCD 7.1 (Fig. 4).
The currents of the other phases can be displayed by briefly
pressing push-button 7.2 (Fig. 4). After the push-button has
been pressed, the display switches to the next phase in the
sequence L1–L2–L3. If the push-button is pressed again
when the phase with the highest load reappears (original
state).
Indication is in amperes from 0.1 x IN to 6 x IN
Like all other protective functions, current measurement is
performed independently of interference voltages. The re-
sult is that the display below the activation limit of the re-
lease remains dark. If a current to be indicated is below 0.1
x IN with the release activated, "– – – – –" appears on the
display; if a current value is above -6 x IN, " –I –I –I –I –I "
When the release is in the overload range ("a" release acti-
vated), the value shown on the display flashes.
To enable current display in amperes, the switch underneath
stopper 7.3 (Fig. 4) must be set to the rated current-trans-
former value of the circuit-breaker (Table 4).
In the case of symmetrical loading of the three phases, the
maximum measuring error is ± 3 % of the reading ± 5 digits
in the range from 0,1 x IN to 1,4 x IN and ± 10 % of the
reading ± 10 digits in the range from 1,4 x IN to 6 x IN.
Anzeigen und Meldungen
Stromanzeige
(nur bei den Auslösern 3WX31 41–5JC und –6JE)
Mit der Flüssigkristall-Anzeige 7.1 (Fig. 4) wird der aktuelle
Strom der am höchsten belasteten Strombahn in Form ei-
ner fünfstelligen Sieben-Segment-Anzeige dargestellt. Die
S tröme der anderen Strombahnen können durch kurzes Drük-
ken des Tasters 7.2 (Fig. 4) angezeigt werden. Nach jedem
Drücken schaltet die Anzeige auf die nächste Strombahn in
der Reihenfolge L1 - L2 - L3. Wird der bei Anzeige des Pha-
senstromes für L3 erneut gedrückt, so erscheint wieder der
S trom der höchstbelasteten S trombahn (Ursprungszustand).
Die Anzeige erfolgt in Ampere im Bereich von 0,1 x IN bis 6 x IN.
Die Strommessung erfolgt, ebenso wie alle Schutzfunktio-
nen, fremdspannungsunabhängig. Daraus ergibt sich, daß
die Anzeige unterhalb der Aktivierungsgrenze des Auslö-
sers dunkel bleibt. Liegt ein anzuzeigender Strom bei ak-
tiviertem Auslöser unter 0,1 x IN, so erscheint in der An-
zeige "– – – – –", liegt ein Strom über 6 x IN, so erscheint
in der Anzeige " –I –I –I –I –I ".
Befindet sich der Auslöser im Überlastbereich (a-Auslösung
aktiviert), so blinkt der in der Anzeige dargestellte Wert.
Um die Stromanzeige in Ampere zu ermöglichen, muß der
unter dem Verschlußstopfen 7.3 (Fig. 4) befindliche Schal-
ter auf den Wandler-Nennstrom des Leistungsschalters ein-
gestellt werden (Tabelle 4).
Bei symmetrischer Belastung der drei Phasen beträgt der
maximale Meßfehler ± 3 % vom abgelesenen Wert ± 5 digit
im Bereich von 0,1 x IN bis 1,4 x IN und ± 10 % vom abgele-
senen Wert ± 10 digit im Bereich von 1,4 x IN bis 6 x IN.
Schalternennstrom/ Schalterstellung/ untere Meßbereichsgrenze/ obere Meßbereichsgrenze/
Rated breaker current Breaker position Lower measuring range limit Upper measuring range limit
[A] [A] [A]
0—
315 1 32 1890
400 2 40 2400
500 3 50 3000
630 4 63 3780
800 5 80 4800
1000 6 100 6000
1250 7 125 7500
1600 8 160 9600
2000 9 200 12000
2500 A 250 15000
3200 B 315 18900
4000 C 400 24000
5000 D 500 30000
6000 E 600 36000
6300 F 630 37800
Tabelle 4: Nennstromeinstellung für Meßfunktion
Table 4 : Rated current setting for measuring function
19
Signalling
7 signalling functions are available for external tele-signals
or for LED display on the front panel of the release.
The indications appear in the event of:
1. Overtemperature (Fig. 4, 6.1)
The temperature in the release housing exceeds 90 °C.
The cause for the excessive temperature must be de-
tected (release, breaker, ambient temperature).
2. Phase unbalance (Fig. 4, 6.2)
The current in one phase has a value of less than 50%
of the current in any other phase.
3. Fault (Fig. 4, 6.3)
The microprocessor monitoring circuit (watchdog) is ac-
tivated (3WX31 41—5 and —6). In this case the reset
button 8.1 (Fig. 4) must be operated. If the signal is not
cancelled, or immediately reappears, the release is de-
fective and must be replaced.
4. Overload
The current of the phase carrying the highest load ex-
ceeds a value of 1,12 x Ir (= setting current for inverse-
time operation).
This indicates that the inverse-time delay function is ac-
tivated and tripping is expected to occur any moment.
Releases 3WX31 41–5 and –6JE indicate the overload
state on the operating current display by rapid flashing
of the measured value indication.
Redirection of cable connection (with overload signal from
signalling unit 3WX31 47-1JA00) from terminal X6.4 to
terminal X11.28 on terminal X11.17 (overcurrent releas-
es with current indication only)
5. Trip indication in response to inverse-time delay opera-
tion (Fig. 4, 1.3)
Tripping was caused by the inverse-time delay function.
6. Trip indication in response to short-circuit operation (Fig. 4, 2.3)
Tripping was caused by the definite-time delay or instan-
taneous function.
7. Trip indication in response to earth-fault-activated oper-
ation (Fig. 4, 4.3)
Tripping was caused by the earth-fault-activated func-
tion.
Displays
LEDs are arranged on the front panel for indications 1 to 3
and 5 to 7 (Fig. 4).
LEDs for indications 1 and 2 are fed from the release. The
LEDs remain lit as long as the displayed status persists and
power supply of the release is not interrupted.
Since LEDs for indications 3 and 5 to 7 signal a post-trip-
ping status, i. e. with the breaker dead, they must be driven
by external voltage source (see remote signals)
Meldungen
Als optische Meldung in Form von Leuchtdioden auf der Front-
platte des Auslösers oder als externes Fernmeldesignal stehen
7 Meldefunktionen zur Verfügung. Die Meldungen werden bei
folgenden Zuständen abgegeben:
1. Übertemperatur (Fig. 4, 6.1)
Die Temperatur innerhalb des Auslösergehäuses über-
schreitet einen Wert von etwa 90 °C. Die Ursache für die
überhöhte Temperatur ist zu untersuchen (Auslöser,
Schalter, Umgebungstemperatur).
2. Phasen-Unsymmetrie (Fig. 4, 6.2)
Der Strom in einer Strombahn hat einen Wert von weni-
ger als 50% des Stromes in einer beliebigen anderen
Strombahn.
3. Störung (Fig. 4, 6.3)
Die Überwachungs-Schaltung des Mikroprozessors
(Watchdog) hat angesprochen (3WX31 41–5 und –6).
In diesem Fall ist der Rückstellknopf 8.1 (Fig. 4) zu betä-
tigen. Wenn sich die Meldung dabei nicht löschen läßt
oder sofort wieder erscheint, ist der Auslöser defekt und
muß ausgewechselt werden.
4. Überlast
Der Strom in der am höchsten belasteten Strombahn
überschreitet den Wert 1,12 x Ir (Einstellstrom der strom-
abhängig verzögerten Auslösung).
Das bedeutet, daß die stromabhängig verzögerte Auslö-
sung aktiviert ist und in absehbarer Zeit mit einer Auslö-
sung zu rechnen ist.
Die Auslöser 3WX31 41–5 und –6JE stellen den Über-
lastzustand auf der Betriebsstromanzeige dar, indem die
Meßwertanzeige rasch blinkt.
Bei Überlastmeldung über Meldegerät 3WX31 47-1JA00
Leitungsverbindung von Klemme X6.4 an Klemme
X11.28 auf Klemme X11.17 entsprechend umverdrahten
(nur bei Überstromauslöser mit Stromanzeige)
5. Auslösemeldung der stromabhängig verzögerten Auslö-
sung (Fig. 4, 1.3)
Eine Auslösung wurde durch die stromabhängig verzö-
gerte oder durch die unverzögerte Auslösung verursacht.
6. Auslösemeldung der Kurzschluß-Auslösung (Fig. 4, 2.3)
Eine Auslösung wurde durch die stromunabhängig ver-
zögerte oder durch die unverzögerte Auslösung verur-
sacht.
7. Auslösemeldung der Erdschluß-Auslösung (Fig. 4, 4.3)
Eine Auslösung wurde durch die Erdschluß-Auslösung
verursacht.
Anzeigen
Für die Meldungen 1 bis 3 und 5 bis 7 sind auf der Front-
platte Leuchtdioden angeordnet (Fig. 4).
Die Leuchtdioden der Meldungen 1 und 2 werden aus dem
Auslöser gespeist. Sie leuchten, solange der gemeldete Zu-
stand besteht und ein zur Energieversorgung des Auslösers
ausreichender Strom fließt.
Die Leuchten der Meldungen 3 und 5 bis 7 melden einen
Zustand nach einer Auslösung, d.h. wenn der Schalter strom-
los ist. Sie werden daher mit Hilfe einer externen S pannungs-
quelle von außen angesteuert (siehe Fernmeldungen).
Anzeigen und Meldungen Display and signalling
20
Fernmeldungen
Jede der 7 Meldefunktionen steht als externes Signal zur
Verfügung. Die Meldung erfolgt kontaktlos über Optokopp-
ler, die Fernmeldekreise werden von einer externen Gleich-
spannungsquelle an den Klemmen X6/9–X6/10 gespeist. An
den Klemmen X6/1 bis X6/7 stehen die Meldesignale als
aktives HIGH-Signal an (Fig. 15/16).
Daten der Fernmeldekreise:
Externe Betriebsspannung UB = 10,8 … 26,4 V
LOW-Signalpegel UL £ 0,5 V
HIGH-Signalpegel UH ³ UB - 2 V
Max. Belastbarkeit 10 mA
Die Meldungen 1 bis 4 stehen als Dauersignal an (solange
der Auslöser aktiviert ist), die Meldungen 5 bis 7 dagegen
nur als Impuls von etwa 20 ms Dauer. Diese Signale müs-
sen durch eine entsprechende Außenschaltung gespeichert
werden. Zum Rücksetzen der externen S peicherglieder vom
Auslöser her ist auf der Frontplatte der Reset-Knopf 8.1
(Fig. 4) vorgesehen. Dieser erzeugt ebenfalls ein aktives
HIGH-Signal, das an der Klemme X6/8 erscheint.
Die externe Ansteuerung der den Auslöse-Meldungen 3 und
5 bis 7 zugeordneten Leuchtdioden erfolgt über den ent spre-
chenden Meldeausgang, indem an diesen von außen ein
aktives HIGH-Signal angelegt wird. Das Signal wird mit ei-
nem Lastwiderstand von etwa 2,5 kOhm belastet.
Meldegerät
Für die Umsetzung der elektronischen Meldesignale des
3WN-Auslösers in Kontaktsignale, die für Stromkreise bis
250 V AC/DC geeignet sind, kann ein externes Meldegerät
angeschlossen werden. Dieses Zusatzgerät übernimmt auch
die Speicherung der impulsförmigen Auslösemeldungen und
die Speisung der entsprechenden Leuchtdioden im Auslöser.
Es stehen drei Ausführungen des Meldegerätes zur V erfügung.
Die einfache Ausführung 3WX31 47–0 überträgt nur die Mel-
dungen 5 und 6, die erweiterte Ausführung 3WX31 47–1 über-
trägt alle Meldungen. Die Ausführung 3WX31 47–2 ist beson-
ders auf die Verwendung mit dem Auslöser 3WX31 41–6JC
vorbereitet und überträgt die Meldungen 5, 6 und 7.
Remote signalling
Each of the 7 signalling functions is available as external
signal. The signals are obtained by optocouplers. The re-
mote signalling circuits are fed from an external direct volt-
age source at terminals X6/9—X6/10. The signals can be
picked off as active HIGH signals at terminals X6/1 to X6/7
(fig. 15/16).
Data of remote signalling circuits:
External operating voltage UB = 10,8 ... 26,4 V
LOW signal level UL £ 0,5 V
HIGH signal level UH ³ UB - 2 V
Max. current capacity 10 mA
Indications 1 to 4 are maintained as long as the release
remains activated, indications 5 to 7 are pulsed with a dura-
tion of approx. 20 ms. They must therefore be stored by an
external circuit. To reset the external memories a reset but-
ton 8.1 (Fig. 4), is provided on the release front panel. The
reset button also generates an active HIGH signal which
can be picked off at terminal X6/8.
The LEDs for indications 3 and 5 to 7 are activated by the
signalling output to which an external active HIGH signal is
applied. The signal is loaded with a loading resistance of
approx. 2.5 kohms.
Signal processing unit
An external signal processing unit can be provided for convert-
ing the electronic signals from the 3WN release into contact
signals suitable for 250 V AC/DC circuits. This additional unit
also stores the pulsed trip signals and activates the associated
LEDs of the release.
Three versions are available . The simple version 3WX31
47—0 only transmits signals 5 and 6, and the extended
version 3WX31 47—1 transmits all signals. Model 3WX31
47—2 has been specially designed for use with release
3WX31 41—6JC and transmits signals 5, 6 and 7.
Anzeigen und Meldungen Display and signalling
21
Kommunikation
Der Leistungsschalter 3WN1/3WS1 wird bei einer Ausstat-
tung mit einem kommunikationsfähigen Überstromauslöser
Ausführung "azn" (Typ 5) bzw. "azng" (Typ 8) in die Lage
versetzt, am PROFIBUS-DP zu kommunizieren.
Die Anbindung des Leistungsschalters 3WN1/3WS1 an den
PROFIBUS-DP erfolgt über die Anschaltung DP / 3WN1/
3WS1 in Verbindung mit einer dem Anwendungsfall zuge-
schnittenen digitalen Ein- Ausgabe- Baugruppe (z.B. ET200).
Die vom Auslöser ermittelten Informationen werden durch
die Anschaltung und die Schalterinformationen durch die E/
A- Baugruppe über den BUS übertragen. Über die E/A- Bau-
gruppe kann auch die Steuerung des Schalters erfolgen.
Communication
Fitting the 3WN1/3WS1 circuit-breaker with an "azn" (Type 5)
or "azng" (T ype 8) communication-cap able overcurrent release
enables it to communicate on the PROFIBUS-DP.
Connection of the 3WN1/3WS1 circuit-breaker to the PROFI-
BUS-DP is effected by means of the DP / 3WN1/3WS1 inter-
face module in combination with a digital input/output module
(for example ET200) tailored to the application in question.
The information determined by the release is transmitted by
the interface, and the circuit-breaker information by the input/
output module via the BUS. Control of the circuit-breaker can
also take place via the input/output module.
Anzeigen und Meldungen Display and signalling
Fig. 11 Schematic structureFig. 11 prinzipieller Aufbau
Profibus DP
Anschaltung/Interface
DP / 3WN 1/ 3WS1
ET 200
Grundg./
Basic unit DE/DA
TTY
3WN1
3WS1
parall. Signale/Parallel signals
Folgende Informationen stehen über dem Profibus DP zur Verfügung :
1 Analogwert für Strom in der maximal belasteten Phase
1 Analogwert für Strom in der Phase 1
1 Analogwert für Strom in der Phase 2
1 Analogwert für Strom in der Phase 3
1 Digitalwert für den Schalterzustand :
a- Auslösung
nz- Auslösung
g- Auslösung(nur AuslöserTyp 8)
Phasenunsymmetrie
Watchdogfehler
Überlast
Temperaturalarm
Über die E/A - Baugruppe sind folgende zusätzliche Informationen
zu erhalten :
Schaltstellung
Einschaltbereitschaftsmeldung
Federspeicherzustand
Weiterhin kann über die E/A - Baugruppe Ein- bzw. Aus geschaltet
werden.
The following information is available via the Profibus DP:
1 analog value for current in the maximum loaded phase
1 analog value for current in Phase 1
1 analog value for current in Phase 2
1 analog value for current in Phase 3
1 digital value for switch state:
a trip
nz trip
g trip (Type 8 release only)
Phase unbalance
Watchdog fault
Overload
Temperature alarm
The following additional information can be obtained via the input/
output module:
Switching position
Ready-to-close signal
Stored-energy spring state
In addition, closing and opening are possible via the input/output
module.
22
Remote operation
For remote tripping of the circuit-breaker the trip magnet
can be activated from an external circuit via terminals X5/
5–X5/6 (Fig. 16/17) .
Operating voltage: 24 V ± 20 % DC
Current input (approx.): 0.8 A
Pulse duration: 10 s max.
Note polarity of operating voltage.
Mechanical lockout
After short-circuit operation ("z" or "n" release) or by choice
after each overcurrent function the mechanical lockout prevents
reclosing of the circuit-breaker. In breakers with stored-energy
mechanism the device also blocks the electrical closing signal.
Function test
The overcurrent test socket 9. 1 (Fig. 3 and 4) and earth
fault socket 2 (Fig. 12) serve to connect an external test
unit. The test unit generates a current which simulates the
CT secondary current and thus permits checking of the re-
lease functions.
The test unit 3WX31 47—5 supplies a YES/NO reply re-
garding reliability of the individual tripping functions. For
more details please refer to Instructions 9259 9769 422.
Fig. 12 3WN circuit-breaker with overcurrent release system (1).
Earth-fault test socket X 15 (2).
Fig. 12 Leistungsschalter 3WN mit elektronischem Auslöser (1).
Erdschlußprüfbuchse X 15 (2).
Fernauslösung · Wiedereinschaltsperre · Funktionsprüfung
Remote operation · Mechanical lockout · Function test
Fernauslösung
Der Auslösemagnet kann über die Klemmen X5/5–X5/6
(Fig. 16/17) zum Zweck der Fernauslösung des Schalters
von außen angesteuert werden.
Betätigungsspannung: 24 V ± 20 % Gleichspannung
Stromaufnahme (etwa): 0,8 A
Kommandodauer: max. 10 s
Die Polarität der Betätigungsspannung muß beachtet werden.
Wiedereinschaltsperre
Die Wiedereinschaltsperre verhindert entweder nach einer Kurz-
schlußauslösung ("z"- oder "n"-Auslösung) oder wahlweise nach
jeder Überstromauslösung das Wiedereinschalten des Schal-
ters. Die Sperre wirkt mechanisch und bei Schaltern mit Spei-
cherantrieben zusätzlich elektrisch durch Blockierung des Ein-
schaltkommandos.
Funktionsprüfung
Die Überstrom-Prüfbuchse 9.1 (Fig. 3 bzw. 4) bzw. Erdschluß-
Prüfbuchse 2 (Fig. 12) dient zum Anschluß eines externen Prüf-
gerätes. Das Prüfgerät erzeugt einen Prüfstrom, der den Wand-
ler-Sekundärstrom nachbildet und gestattet damit die Über-
prüfung der Arbeitsweise des Auslösers.
Das einfache Prüfgerät 3WX31 47–5 ermöglicht eine Ja/
Nein-Aussage über die Funktionsfähigkeit der einzelnen Aus-
lösefunktionen. Näheres siehe Anleitung Nr. 9259 9769 422.
1
2
23
Wartung
Der Überstromauslöser ist wartungsfrei. Es wird empfoh-
len, etwa in jährlichem Abstand mit einem Prüfgerät (siehe
Funktionsprüfung) die korrekte Funktion des Auslösers zu
überprüfen.
Wenn beim Prüfen die Meldung "Störung" auftritt, ist der
Überstromauslöser nicht mehr funktionsfähig und muß aus-
gewechselt werden.
Austausch des Überstromauslösers
Grundsätzlich ist ein Überstromauslöser stets gegen einen
der gleichen Ausführung zu tauschen. Wenn dies im Einzel-
fall nicht möglich ist, weil ein gleichartiger Auslöser nicht
zur Verfügung steht, ist folgendes zu beachten:
1. Einsetzen eines Auslösers mit erweiterten Funktionen
z-Auslösung, Stromanzeige und thermisches Gedächt-
nis sind wirksam, auch wenn der zu ersetzende Auslö-
ser diese Funktion nicht hatte.
Erdschluß-Auslöser , zeitverkürzte Selektivitätssteuerung
(ZSS) und Meldefunktionen sind nicht wirksam, wenn
der zu ersetzende Auslöser diese Funktion nicht hatte.
2. Einsetzen eines Auslösers mit reduzierten Funktionen
Alle Funktionen des neu eingesetzten Auslösers sind wirksam.
Alle Funktionen, die der zu ersetzende Auslöser darüber
hinaus hatte, bleiben unwirksam.
Achtung!
Überstromauslöser niemals unter Last (eingeschal-
teter Schalter) ziehen.
Die Leistungsschalter dürfen niemals ohne eingesetz-
ten Überstromauslöser betrieben werden, da sonst die
eingebauten Stromwandler durch unzulässig hohe In-
duktionsspannungen zerstört werden können.
Bei Erdschlußschutz durch vierten W andler nur Aus-
löser mit Erdschlußfunktion einsetzen.
Funktionsprüfung
Wir empfehlen nach dem Austausch des Auslöserbaustei-
nes die Funktionsprüfung vorzunehmen, siehe Seite 22.
Sollten hierbei S törungen angezeigt werden, ist die einwand-
freie Kontaktierung des Auslöserbausteines mit der S tecker-
leiste zu überprüfen.
Auslösereinstellung
Die Auslöser sind im Werk stückgeprüft. Die Einstellwerte
sind auf Minimalwerte eingestellt.
Vor Inbetriebnahme des Schalters sind die Stufenschalter
auf die erforderlichen Betriebswerte einzustellen.
Montage
Der Überstromauslöser ist mit steckbaren Anschlüssen ausgeführt
und daher leicht auswechselbar . Er wird im Schalter mit zwei Schrau-
ben befestigt. Zum Einsetzen bzw. Herausnehmen des Auslösers
muß die Frontabdeckung des Schalters abgenommen werden.
Wandler und Auslösemagnet sind fest im Schalter montiert.
Die Signal- und Steuerleitungen für den Überstromauslöser,
die an die Klemmleisten X5 und X6 des Leistungsschalters
angeschlossen werden, müssen vor hohen S törspannungen
in benachbarten Leitungen, die z.B. durch das Schalten von
Induktivitäten entstehen, geschützt werden. Es empfiehlt sich
daher die Verwendung von geschirmten Leitungen.
Die Länge der Leitungen darf 300 m nicht überschreiten.
Wartung • Funktionsprüfung
Auslösereinstellung • Montage
Maintenance
The overcurrent release is maintenance-free. We would how-
ever recommend that correct functioning of the release be
checked once a year by means of a test unit (see "function
test").
By testing the "fault" signal indicates that the overcurrent
release no longer operates reliably and must be replaced.
Replacing the overcurrent release
Overcurrent releases must always be replaced by units of
the same type. If no unit of the same type should be availa-
ble, observe the following:
1. Using a release with extended functions
"z" release, current display and thermal memory are op-
erative even if this function has not been included in the
release to be replaced.
Earth-fault activated function, zone-selective interlocking
and signalling functions are not operative if these functions
were not included in the release to be replaced.
2. Using a release with reduced functions.
All the functions of the new release used are operative.
All the functions which the release to be replaced included
in addition remain inoperative.
Caution!
Do not withdraw the overcurrent release under load
(with the breaker closed).
Do not operate 3WN circuit-breakers without over-
current release module since otherwise the voltage
at the current-limits under no-load conditions.
In the case of earth fault protection by means of a
fourth current transformer, use releases with earth
fault function only.
Functional test
A functional test should be carried out on completion of re-
placement of the release module (see page 22).
If faults are indicated, check proper contact making of the
release module with the plug connector.
Setting of the release
The release units are subjected to routine test in the factory.
Adjustable values are set to minimum.
Before putting the breaker into operation, the step selector
switches have to be set to the required service values.
Installation
The overcurrent release has plug-in connections and is thus
easily replaceable. The release is fixed inside the breaker
by two screws. For mounting and dismantling the unit the
breaker front plate must be removed. CT and trip magnet
are permanently installed in the breaker.
The signal and control leads for the overcurrent release,
which are connected to the terminal blocks X5 and X6 of the
circuit-breaker, must be protected against high interference
voltage in neighbouring conductors; these voltages can for
example be caused by the switching of inductances. It is
therefore advisable to use screened leads.
The leads must not be more than 300 m in length.
Maintenance • Functional test
Setting of the release • Installation
24
Ausbau des Überstromauslösers
Sechskantmutter M 3 (4) und Sicherungsscheiben (5)
abschrauben
Überstromauslöser (6) herausziehen
Klammern an der Steckerleiste X11 lösen, Steckerleiste
und Überstromauslöser trennen
Einbau in umgekehrter Reihenfolge durchführen, dabei untere
Kante des Überstromauslösers in Führungsschlitz des sich im
Schalter befindenden Gummisockels einführen
Removing the overcurrent release
Unscrew hexagon nut M 3 (4) and lock washers (5)
Pull out overcurrent release (6)
Undo clamps on plug connector X11, separate plug connector
and overcurrent release
Refit the overcurrent release in reverse order and insert the
lower edge of the overcurrent release at the same time into
the guidance of the rubber base which is in the breaker
Fig. 14 Ausbau des Überstromauslösers
Removing the overcurrent release
4, 5
6
4, 5
Montage Installation
Bedienpult ausbauen
Befestigungsschrauben (1) herausschrauben
Handhebel (2) nach vorne ziehen und Bedienpult (3) abnehmen
Removing control panel
Undo fixing screws (1)
Pull handle (2) forwards and detach control panel (3)
2
3
1
Fig. 13 Bedienpult ausbauen
Removing the control panel
25
X11 X6
10
23 8
29 7
30 6
28 4
NL 1L 2 L 3
L
K
k
l
L
K
k
l
L
K
k
l
2
X14
1X15
X14 7
7
W1
X14 256
23
L
K
k
l
22
X5 78X5 65432 1
21
}
+
X5 910
X14
3X11
1
X11
14
15
16
4
X11 718 21
X11 19 20
X12
8
6
11
X11/ 6
4
2
13
3
1
24
1
4
2
3
X11 5
38910
5
bl
}
}
20a 20b
26
9
S
W2
18
19
9
22
17
11
12
13
15
16
14
24
31
27
25 1
2
3
5
Übersichts-Schaltpläne Block diagrams
4_
1) Bei Anschluß eines externen Summenstromwandlers ist Brücke W1 zu entfernen
und W2 einzusetzen.
2) Bei Überlastmeldung über Meldegerät 3WX31 47–1JA00 Leitungsverbindung von
Klemme X6.4 an Klemme X11.28 auf Klemme X11.17 entsprechend umverdrahten
(nur bei Überstromauslöser mit Stromanzeige).
Fig. 15 Block diagram for 3WN1/5, 3WS1 circuit-breaker , triple-poleFig. 15 Übersichtsschaltplan für 3-poligen Leistungsschalter 3WN1/5,
3WS1
1 Leistungsschalter 3WN1/5, 3WS1
2 Auslösemagnet
3 Ausgangsstufe
4 Überstromauslöser 3WX31 41–6JE
5 Stromanzeige
6 Stromversorgung
7 Summenstromwandler 1)
8 Signalaufbereitung
9 Signalverarbeitung
10 Meldungen
Fernmeldungen:
11 Übertemperatur
12 Störung
13 Phasenunsymmetrie
14 Datenübertragung für Betriebsströme
15 Überlastauslösung
16 Kurzschlußauslösung
17 Erdschlußauslösung
18 Reset
19 externe Betriebsspannung
20a Eing. Zeitverkürzte Selektivitätssteuerung
20b Ausg. Zeitverkürzte Selektivitätssteuerung
21 Fernauslösung
22 externer Summenstromwandler 1)
23 externer 4. Wandler
24 Wiedereinschaltsperre
25 Überlast
X5, X6 Schalterklemmleiste
X11 Auslösersteckleiste
X12 Prüfbuchse Überstrom
X14 Steckerleiste Summenstromwandler
X15 Prüfbuchse Erdschluß
1 3WN1/5, 3WS1 Circuit-breaker
2 Trip magnet
3 Output stage
4 Overcurrent release 3WX31 41–6JE
5 Current indification
6 Power supply
7 Summation current transformer 1)
8 Signal conditioning
9 Signal processing
10 Indications
Remote signalling:
11 Overtemperature
12 Fault
13 Phase unbalance
14 Serial Transmission of Phase Currents
15 Overload trip
16 Short-circuit trip
17 Earth-fault-activated trip
18 Reset
19 External operating voltage
20a Input zone selective interlocking
20b Output zone selective interlocking
21 Remote operation
22 External summation CT 1)
23 External CT No. 4
24 Mechanical lock out
25 Overload
X5, X6 Breaker terminal strip
X11 Release connector
X12 Overcurrent test socket
X14 Summation CT connector
X15 Earth-fault test socket
1) When connecting an external summation current transformer replace
jumper W1 by W2.
2) Redirection of cable connection with overload signal from signalling unit
3WX31 47–1JA00 from terminal X6.4 to terminal X11.28 on terminal X11.17
(overcurrent releases with current indication only).
17 4 25 2)
2)
26
1) Für 4-polige Leistungsschalter 3WN ohne Erdschlußüberwachung entfällt 7 und 23
(Wandleranschlüsse werden dann an X11/1 angeschlossen).
2) Bei Überlastmeldung über Meldegerät 3WX31 47–1JA00 Leitungsverbindung von
Klemme X6.4 an Klemme X11.28 auf Klemme X11.17 entsprechend umverdrahten
(nur bei Überstromauslöser mit Stromanzeige).
1 Leistungsschalter 3WN1/5, 3WS1
2 Auslösemagnet
3 Ausgangsstufe
4 Überstromauslöser 3WX31 41–6JE
5 Stromanzeige
6 Stromversorgung
7 Summenstromwandler 1)
8 Signalaufbereitung
9 Signalverarbeitung
10 Meldungen
Fernmeldungen:
11 Übertemperatur
12 Störung
13 Phasenunsymmetrie
14 Datenübertragung für Betriebsströme
15 Überlastauslösung
16 Kurzschlußauslösung
17 Erdschlußauslösung
18 Reset
19 externe Betriebsspannung
20a Eing. Zeitverkürzte Selektivitätssteuerung
20b Ausg. Zeitverkürzte Selektivitätssteuerung
21 Fernauslösung
23 externer 4. Wandler 1)
24 Wiedereinschaltsperre
25 Überlast
X5, X6 Schalterklemmleiste
X11 Auslösersteckleiste
X12 Prüfbuchse Überstrom
X14 Steckerleiste Summenstromwandler
X15 Prüfbuchse Erdschluß
1 3WN1/5, 3WS1 Circuit-breaker
2 Trip magnet
3 Output stage
4 Overcurrent release 3WX31 41–6JE
5 Current indification
6 Power supply
7 Summation current transformer 1)
8 Signal conditioning
9 Signal processing
10 Indications
Remote signalling:
11 Overtemperature
12 Fault
13 Phase unbalance
14 Serial Transmission of Phase Currents
15 Overload trip
16 Short-circuit trip
17 Earth-fault-activated trip
18 Reset
19 External operating voltage
20a Input zone selective interlocking
20b Output zone selective interlocking
21 Remote operation
23 External CT No. 4 1)
24 Mechanical lock out
25 Overload
X5, X6 Breaker terminal strip
X11 Release connector
X12 Overcurrent test socket
X14 Summation CT connector
X15 Earth-fault test socket
1) For 4-pole 3WN circuit-breakers without earth-fault monitoring, 7 and 23 are not
required (transformer connections made then at X11/1).
2) Redirection of cable connection with overload signal from signalling unit
3WX31 47–1JA00 from terminal X6.4 to terminal X11.28 on terminal X11.17
(overcurrent releases with current indication only).
1
7
NL1 L 3
224
1
4
2
3
9
8
5
X11 310
3
6
8
L
K
k
l
23
L
K
k
l
L
K
k
l
L
K
k
l
X5 910
X14
1
8
9
10
T1
T2
X15
X14 2
7
X14
X14
3
6
5
X11
X11
1
14
15
11
X11/ 6
4
2
13
X11
X12
X5
718 21 19 20
X11
65432 1
+
21
}
X11 X6
10
9
8
7
6
5
4
18
17
16
15
14
12
11
3
2
1
9
13
}
}
20a 20b
19
28
26
25
27
31
30
29
23
24
22
L 2
_4
5
Fig. 16 Übersichtsschaltplan für 4-poligen Leistungsschalter 3WN1/5,
3WS1 mit Erdschlußüberwachung Fig. 16 Block diagram for 3WN1/5, 3WS1 circuit-breaker, 4-pole, with
earth-fault monitoring
Übersichts-Schaltpläne Block diagrams
425
17 2)
2)
27
28
Siemens Aktiengesellschaft Bestell-Nr./Order No.: 3ZX1812-0WX31-0AN5 / 9259 9499 174 0E
Bestell-Ort/Place of order: A&D CD PD Log PCB Berlin
Printed in the Federal Republic of Germany
AG 06.2002 Kb De-En
Herausgegeben vom
Bereich Automatisierungs- und Antriebstechnik
Niederspannungs-Schalttechnik
Schaltwerk Berlin
D - 13623 Berlin
Änderungen vorbehalten
Published by the
Automation & Drives Group
Control and Distribution
Schaltwerk Berlin
D - 13623 Berlin
Federal Republic of Germany
Subject to change