© 2003 TELEDYNE RELAYS (800) 284-7007 • www.teledynerelays.com XV 1
XV\032003\Q1
Single Output to 30A 420 Vac
No Heat Sink, Hybrid Relay
FEATURES/BENEFITS
Industry standard package
Combines the best of solid-state and
electromechanical relays
Tight zero-cross window for low EMI
Control LED
Internal output protection
High immunity to surges
DESCRIPTION
The Series XV relay combines the best of solid-state
and electromechanical technology. The relay is
designed in a touch-proof hockey-puck package. The
XV relay switches current up to 30A without a heat
sink. Visual control status is provided as a standard.
Elimination of the heat sink conserves space and
makes the XV ideal for numerous applications.
APPLICATIONS
Interface applications
Heating Control
Light/Lamp control
Contactor driver
Fan speed control
HVAC controls
APPROVALS
Model XV46D30K is UL recognized.
UL File Number: E128555.
Part Number Description
XV46D30K 30A, 420 Vac
Part Number Explanation
Series XV
NOTES
1) Line V oltage (nominal): 46 = 420 Vac
2) Switch Type: D = Zero-cross turn-on
3) Control Range: K = 20–30 Vdc, *C = 12 Vdc also available
MECHANICAL SPECIFICATION
Figure 1 – XV relay; dimensions in inches (mm)
INPUT (CONTROL) SPECIFICATION
Min Max Units
Control Range* 20 30 Vdc
Input Current Range 31 41 mAdc
Must Turn-Off Voltage 10 Vdc
Input Resistance (T ypical) 640 Ohms
Reverse V oltage Protection 30 Vdc
Control Frequency 1 Hz
TYPICAL APPLICATION
Figure 2 – XV relay
XV 46 D 30 K
1.77 (45)
1.75 (44.5)
2.41 (61.3)
1.70 (43.2)
1.00 (25.4)
M4 1.10 (28)
.35 (9)
1.87 (47.6)
.27
(6.8)
M3.5
WEIGHT: 5.64 oz (160g)
Ø.19 (Ø4.7)
A1+
SSR
EMR
Supply
t1
t2
t3
LED V
L
Vc
Load
A1-
T
1
L
1
CONTROL CHARACTERISTIC
Figure 3 – XV relay
Control Voltage (V)
Input Current (mA)
0
5
10
15
20
25
30
35
40
45
1005 15 3020 25 35
XV 2 SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE © 2003 TELEDYNE RELAYS
XV\032003\Q1
OUTPUT (LOAD) SPECIFICATION
Min Max Unit
Operating Range 12 420 Vrms
Peak V oltage 800 Vpeak
Load Current Range 0.1 30 Arms
Motor Load Current 7.5 Arms
Maximum Surge Current Rating (Non-Repetitive)
(See Figure 4) 240 Apeak
On-State Voltage Drop 0.3 V
Zero-Cross Window (Typical) ±12 V
Off-State Leakage Current (60Hz) 2 mA
Turn-On Time (60Hz) 12 ms
Turn-Off T ime (60Hz) 20 ms
Off-State dv/dt 500 V/µs
Maximum di/dt (Non-repetitive) 50 A/µs
Operating Frequency 40 440 Hz
I2t for fuse matching (<8.3ms) 288 A2S
ENVIRONMENTAL SPECIFICATION
Min Max Unit
Operating Temperature –40 90 °C
Storage Temperature –40 100 °C
Input-Output Isolation 4000 Vrms
Output-Case Isolation 4000 V
Life Expectancy See Figure 5
Series XV
SURGE CURRENT
NOTES:
1. Electrical Specifications at 25°C unless otherwise specified.
2. For 800Hz applications, contact factory.
3. For additional/custom options, contact factory.
Figure 4 – XV relay
Figure 5 – XV relay
110100 10001
50
100
150
200
250
0
Number of Cycles
Apeak
0100 200 300 400 500
1
2
3
4
5
Load Voltage (V)
At maximum rated current
(Resistive load)
10 Operations
6
LIFETIME EXPECTANCY
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Teledyne Relays:
XV46D30K