AEV250 Series DC
Contactor Specication
Application
AEV250 Series is used for charging (pile) station, battery power supply,
DC power control, circuit protection and other electric vehicle power switch
controls. Also it could be widely used in uninterruptible power supply and
other electronic control systems.
Features
HIGH CURRENT AND HIGH VOLTAGE
Contact chamber is led with inert gas to minimize arcing, up to 900VDC
load is available.
COMPACT STRUCTURE, LOW NOISE
Contact design yields reduced unit size, low noise while carrying or switching currents.
COIL ECONOMIZER
Built-in coil economizer – only 1.7W hold power @12VDC and it limits back EMF to 0V.
HIGH SAFETY
There is no arc leakage due to tight sealing.
HIGH RELIABLE CONTACT
Stable contact resistance no matter how harsh environment with sealed contacts.
NO SPECIAL REQUIREMENT FOR MOUNTING
Light weight actuator is less impacted by gravity with no special mounting orientation requirements.
VARIOUS APPLICATION
Application includes battery switch and standby equipment, DC power control, circuit protection, etc.
COMPLY WITH EU ROHS DIRECTIVE (2011/65/EU)
Nomenclauture
Series code:
AEV250” = AEV250 Series
Coil Voltage Code::
“M” = 12 - 24 VDC
Options (applied in this order):
Blank = Std. Options (Bottom Mount, Without Aux.
Contact & Polarized Load Terminals)
A” = With Aux. Contact (SPST-NO)
“N” = Non-Polar Load Terminals
“P” = Potted PCB
Example AEV250 M AN
1
AEV250 Series DC
Contactor Specication
2
Performance Data
MAIN CONTACT LIFE
Contact arrangement 1 Form X (SPST-NO DM) Resistive load life See chart below
Rated Operating Voltage 12-900VDC Mechanical life 1,000,000 cycles
Continuous (Carry) Current 250A (65˚C) AUX. CONTACT
Max short circuit current 2,000A @320VDC, 1 cycle*1 Aux. Contact arrangement 1 Form A
Dielectric 2200Vrms Aux. Contact Current Max 2A@30VDC/
Withstanding Voltage 3A@125VAC
Insulation Resistance Terminal to Terminal/ Aux. Contact Current Min 100mA@8V
Terminal to coil
New: Min 100 MΩ@500Vdc
End of life: Min 50 MΩ@500Vdc
Voltage Drop (@250A) ≤50mV Aux. Contact 0.417ohms@30VDC/
Resistance Max 0.150ohms @125VAC
ENVIRONMENTAL DATA OPERATE / RELEASE TIME
Shock,11ms 20G Peak Close (includes bounce) 25ms, Max.
½ sine, operating
Vibration, Sine, Peak, 20G 80 to 2,000Hz Release 12ms, Max
(@2000A includes arc)
Operating
Ambient Temperature -40 to +85˚C
Altitude <4000m
Weight 0.95 Lb (0.43 kg)
COIL DATA
Voltage (will operate) 9-36VDC
Voltage (Max.) 36VDC
Pickup voltage (Max.) 9VDC
Dropout voltage (Min.) 6VDC
Inrush Current (Max.) 3.8A
Holding Current (Avg.) 0.13A@12VDC / 0.07A@24VDC
Note:
*1: Does not meet dielectric & IR after test.
AEV250 Series DC
Contactor Specication
Note:
Estimates based on extrapolated
data. User is encouraged to conrm
performance in application.
Estimated Electrical Life:
Polarity Sensitive Type
Estimated Electrical Life:
Non-Polarity Sensitive Type
Estimated
Life (Cycles)
Load Current (A)
Continuous carry current range
3
Electrical life
Estimated Make & Break Resistive Load Ratings for polarized type
Polar type electrical Load Life
Ratings for Typical EV Applications
Voltage (V) 900 750 450
Current (A) 250 250 250
Life (Cycle) 70 250 1000
Voltage (V) 450 650
Current (A) 250 250
Life (Cycle) 2000 500
MAKE/BREAK LIFE CAPACITIVE & RESISTIVE LOADS AT 320VDC*1 *2
@90% pre-charge (make only), see chart below 50,000 cycles
@Min 80% pre-charge (make only), see chart below 50 cycles
250A make/break (2 consecutive (reverse polarity) *1 4 cycles
2,500A (break only) *¹ 1 cycle
Note:
*1: Resistive load includes L=25uH. Load @2500A, test @200uH
*2: Life based on projected Weibull Life with 95% reliability.
AEV250 Series DC
Contactor Specication
AEV250 Capacitive Make Test Curves for Pre-Charged Motor Controller
Outline Dimensions: in. (mm)
4
80% Minimum
Pre Charge
90% Nominal
Pre Charge
Note:
No Polarity mark on non-polarity “N” type
Two M8x1.25 Screw Terminal
2 Washers2 Lock Washers, 2 Nuts
Torque: 80-100 lb.in (8.8-11 N.m)
Two #10 Mounting Holes
Torque15-30 lb.in1.7-3.3N.m
+A1 Positive
Terminal
Optional Aux.
Contact
White Wires
Wire Length
390±10mm
Coil Wires
Red Wire (+)
Black Wire(-)
-A2 Negative Terminal
1.07±0.01
[26.7±0.3]
Φ0.23±0.01
[Φ5.8±0.3]
Φ2.29±0.02
[Φ58.2±0.6]
0.57±0.01
[14.2±0.3]
15.4±0.4
[390.0±10.0]
Φ2.04±0.02
[Φ52.0±0.6]
0.51±0.01
[12.7±0.3]
2.07±0.01
[51.6±0.3]
2.50±0.02
[62.4±0.6]
2.74±0.02
[68.4±0.6]
2.90±0.02
[72.6±0.6]
1.68±0.01
[41.9±0.3]
3.23±0.02
[80.7±0.6]
2.24±0.02
[56.0±0.6]
AEV250 Series DC
Contactor Specication
Application Note:
1. Be sure to use washer to prevent screws from loosening. Tighten the screw torque range is specied as below.
Exceeding the maximum torque can lead to product rupture.
Contact torque (M8): 80 - 100 lb.in (8.8 - 11 N.m)
Mounting torque: 15 - 30 lb.in (1.7 - 3.3 N.m)
2. Please refer to drawing for polarity sensitive type during connecting; No orientation for non-polar type.
3. Do not use dropped products.
4. Avoid to install the product in a strong magnetic eld (Close to the transformer or magnet), or near an object
with heat radiation.
5. Electrical life
Please use under load capability and life cycle so as not to cause a function failure. (Please also treat the
contactor as a product with specied life and replace it when necessary). It is possible to make parts burn
around the contactor once operating failure happens. So it is necessary to take layout into account to make sure
power shall be cut off within 1 second.
6. Lifetime of internal gas diffusion
The contactor is sealed and lled with gas, lifetime of gas diffusion is determined by temperature in contact
chamber (Ambient temperature + Temperature rising by contact energizing). Therefore environment
temperature should be from -40 to +85˚C.
7. Do not let particle and oil stain on the main terminal with which the load shall make a reliable contact. Or it will
cause a lot of heat.
1741 Industrial Drive, No. 14 • Sterling, IL 61081
Tel: 815-632-3150 • Fax: 815-632-3449
www.altranmagnetics.com • sales@altranmagnetics.com
5