Digital Power Monitor with PMBus Interface ADM1293/ADM1294 Data Sheet FEATURES FUNCTIONAL BLOCK DIAGRAMS SENSEP SENSEN ADM1293 VCC INTERNAL SUPPLY VIN RANGE SELECT MUX LDO VCAP ADC EN VAUX ADDRESS DECODER ADR1 ADR2 PMBUS AND LOGIC GPO1/ALERT1/CONV GPO2/ALERT2 GND 11891-001 Monitor current and two voltages High accuracy current monitoring at low sense voltage 0.33% accurate at 20 mV sense voltage over temperature Common-mode sense voltage from 0 V to 20 V (ADM1293) Support high-side and low-side current sensing Integrated shunt regulator for wide supply input (ADM1294) Reports current, voltage, and power Power accumulation for energy metering Bidirectional current sensing Digitally programmable overcurrent alert Multifunctional pins with user configurable functions ADC conversion enable input Multisource alert output User-controllable GPO Peak detect registers for current, voltage, and power PMBus fast mode compliant interface Separate SDA I/O for easy isolated communication Two address pins for 16 unique IC addresses Available in 4 mm x 4 mm, 16-lead LFCSP and 14-lead TSSOP Operation temperature range ADM1293 TA = -40C to +105C ADM1294 TJ = -40C to +105C SCL SDAI SDAO Figure 1. ADM1293 Functional Block Diagram VSHUNT ADM1294 VCAP LDO ADDRESS DECODER VEE IC POWER SUPPLY ADR1 ADR2 GPO1/ALERT1/CONV VIN RANGE SELECT MUX VAUX ADC EN PMBUS AND LOGIC GPO2/ALERT2 SDAI SDAO SCL VEE Power monitoring/power budgeting Central office equipment Telecommunications and data communications equipment PCs/servers SENSEN 11891-002 APPLICATIONS SENSEP Figure 2. ADM1294 Functional Block Diagram GENERAL DESCRIPTION The ADM1293 and ADM1294 are high accuracy integrated digital power monitors that offer digital current, voltage, and power monitoring using an on-chip, 12-bit analog-to-digital converter (ADC), communicated through a PMBusTM compliant I2C interface. These devices acquire the current by measuring the voltage difference across the external sense resistor. This voltage is amplified and digitized by an internal 12-bit ADC. The same ADC can also sample the primary input voltage and an auxiliary input voltage. The internal digital block can perform multiplication of the current and primary input voltage for power calculation. The ADM1293/ADM1294 also feature a power accumulator for energy metering. An industry-standard PMBus interface allows a master controller to read back these data from the device. The master controller can then combine this information with a known sense resistor value to calculate the current, voltage, power, and energy consumption over time on the monitored rail. Rev. B In conditions such as overcurrent, overvoltage, undervoltage, and overpower, the ADM1293/ADM1294 devices can generate an interrupt signal to the microprocessor through the GPOx/ALERTx outputs. The threshold for these conditions is digitally programmed via PMBus. The ADM1293 is designed for high-side supply monitoring with a voltage monitoring range from 0 V to 20 V. The ADM1294 is designed for low-side supply monitoring. Its integrated shunt regulator allows it to be powered and to monitor supply in wide voltage ranges. The ADM1293/ADM1294 are available in 4 mm x 4 mm 16-lead LFCSP and 14-lead TSSOP packages with a specified operating ambient temperature range from -40C to +105C for the ADM1293 and an operating junction temperature range from -40C to +105C for the ADM1294. Document Feedback Information furnished by Analog Devices is believed to be accurate and reliable. However, no responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other rights of third parties that may result from its use. Specifications subject to change without notice. No license is granted by implication or otherwise under any patent or patent rights of Analog Devices. Trademarks and registered trademarks are the property of their respective owners. One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A. Tel: 781.329.4700 (c)2014-2015 Analog Devices, Inc. All rights reserved. Technical Support www.analog.com ADM1293/ADM1294 Data Sheet TABLE OF CONTENTS Features .............................................................................................. 1 Digital Comparator Mode ......................................................... 29 Applications ....................................................................................... 1 Application Diagrams .................................................................... 30 Functional Block Diagrams ............................................................. 1 PMBus Command Reference........................................................ 32 General Description ......................................................................... 1 PMBus Command Descriptions .................................................. 33 Revision History ............................................................................... 3 Clear Faults Register .................................................................. 33 Specifications..................................................................................... 4 PMBus Capability Register ....................................................... 33 Electrical Characteristics ............................................................. 4 IOUT OC Warning Limit Register .......................................... 33 Serial Bus Timing Characteristics .............................................. 7 VIN OV Warning Limit Register ............................................. 33 Absolute Maximum Ratings ............................................................ 8 VIN UV Warning Limit Register ............................................. 34 Thermal Characteristics .............................................................. 8 PIN OP Warning Limit Register .............................................. 34 ESD Caution .................................................................................. 8 Status Byte Register .................................................................... 34 Pin Configurations and Function Descriptions ........................... 9 Status Word Register .................................................................. 34 Typical Performance Characteristics ........................................... 11 IOUT Status Register ................................................................. 35 Theory of Operation ...................................................................... 14 Input Status Register .................................................................. 35 Powering the ADM1293 ............................................................ 14 Manufacturer Specific Status Register ..................................... 36 Powering the ADM1294 ............................................................ 14 Read EIN Register ...................................................................... 36 Optional Power Monitor Inputs Filtering ............................... 16 Read EOUT Register .................................................................. 37 Power Monitor ............................................................................ 16 Read VIN Register...................................................................... 37 PMBus Interface ............................................................................. 18 Read IOUT Register ................................................................... 37 Device Addressing ...................................................................... 18 Read PIN Register ...................................................................... 37 SMBus Protocol Usage ............................................................... 19 PMBus Revision Register .......................................................... 38 Packet Error Checking ............................................................... 19 Manufacturer ID Register ......................................................... 38 Partial Transactions on I C Bus ................................................ 19 Manufacturer Model Register................................................... 38 SMBus Message Formats ........................................................... 19 Manufacturer Revision Register ............................................... 38 Group Commands...................................................................... 21 Maximum IOUT Register ......................................................... 38 Information Commands............................................................ 21 Peak VIN Register ...................................................................... 39 Status Commands....................................................................... 21 Peak VAUX Register .................................................................. 39 GPOx and ALERTx Pin Setup Commands ............................ 22 Power Monitor Control Register .............................................. 39 Power Monitor Commands ...................................................... 22 Power Monitor Configuration Register................................... 40 Warning Limit Setup Commands ............................................ 24 Alert 1 Configuration Register ................................................. 41 PMBus Direct Format Conversion .......................................... 24 Alert 2 Configuration Register ................................................. 41 Energy Meter Value Conversion .............................................. 26 Device Configuration Register ................................................. 42 Energy Meter Value to PMBus Standard Data Conversion .. 27 Maximum PIN Register............................................................. 42 Voltage and Current Conversion Using LSB Values .............. 27 Read PIN (Extended) Register ................................................. 43 ALERTx Pin Behavior .................................................................... 28 Read EIN (Extended) Register ................................................. 43 Warnings ...................................................................................... 28 Read VAUX Register .................................................................. 43 Generating an Alert.................................................................... 28 VAUX OV Warning Limit Register ......................................... 43 Handling/Clearing an Alert ...................................................... 28 VAUX UV Warning Limit Register ......................................... 44 SMBus Alert Response Address (ARA) .................................. 28 Minimum IOUT Register.......................................................... 44 Example Use of SMBus ARA .................................................... 29 Minimum PIN Register ............................................................. 44 2 Rev. B | Page 2 of 48 Data Sheet ADM1293/ADM1294 Read EOUT (Extended) Register ..............................................44 Hysteresis Status Register........................................................... 45 Hysteresis Low Threshold Level Register ................................45 Outline Dimensions ........................................................................ 46 Hysteresis High Threhsold Level Register ...............................45 Ordering Guide ........................................................................... 47 REVISION HISTORY 3/15--Rev. A to Rev. B Changes to Power Monitor Section ..............................................16 Added Table 7 ..................................................................................17 Changes to Energy Meter Value Conversion Section.................26 Changes to Table 23 ........................................................................36 Changes to Table 24 ........................................................................37 Changes to Table 42 ........................................................................43 Changes to Table 48 ........................................................................44 Changes to Ordering Guide ...........................................................47 10/14--Rev. 0 to Rev. A Changes to Figure 19 ......................................................................14 Added Table 7; Renumbered Sequentially ...................................20 8/14--Revision 0: Initial Version Rev. B | Page 3 of 48 ADM1293/ADM1294 Data Sheet SPECIFICATIONS ELECTRICAL CHARACTERISTICS For the ADM1293: VCC = 2.95 V to 20 V, VSENSEP = 0 V to 20 V, VCC VSENSEP, VCC VSENSEN, TA = -40C to +105C, unless otherwise noted. For the ADM1294: VEE = -48 V, shunt regulation current = 10 mA, VSENSEP = VEE = 0 V, pin voltages are referenced to the VEE pin, TJ = -40C to +105C, unless otherwise noted. All minimum/maximum specifications apply over the entire recommended operating range, unless otherwise noted. Typical values are specified at TA = 25C. Table 1. Parameter POWER SUPPLY ADM1293 Operating Voltage Range Undervoltage Lockout (UVLO) UVLO Hysteresis Quiescent Current ADM1294 Typical Operating Voltage Voltage Transient Immunity Shunt Regulation Voltage Symbol Min VOP3 VUVLO_3 2.95 2.4 VSHUNT 11.5 Undervoltage Lockout UVLO Hysteresis Quiescent Current Power Directly Without Shunt SENSEP AND SENSEN PINS ADM1293 Input Current Input Imbalance ADM1294 Input Current Input Imbalance VUVLO_4 2.4 VCAP PIN Internally Regulated Voltage VIN PIN Input Current VAUX PIN Input Current GPO1/ALERT1/CONV PIN Output Low Voltage Typ Max Unit 20 2.7 120 3.3 V V mV mA VSHUNT 13 V V V 2.7 120 3.6 11.5 V mV mA V 5 25 25 nA nA Per individual pin, VSENSEP = VSENSEN = VCC = 20 V ISENSEx = ISENSEP - ISENSEN, VSENSE = 20 mV, VSENSEP = VVSHUNT 0.05 -1 1 A A VSENSEP = VSENSEN 25 mV, per individual pin, VVSHUNT = 12 V ISENSEx = ISENSEP - ISENSEN, VSENSE = 20 mV, VSENSEP = 0 V, VVSHUNT = 12 V 2.7 2.74 V 0 A IVCAP 100 A, CVCAP = 1 F IVIN 20 100 A nA VVIN = 20 V, VRANGE = 0 V to 21 V VVIN = 1.2 V, VRANGE = 0 V to 1.2 V IVAUX 100 nA VVAUX = 1.2 V, VAUX sampling enabled VOL_GPO1 0.4 1.5 100 1 V V nA A V V s IGPO1 = 1 mA IGPO1 = 5 mA VGPO1 2 V, GPO1 output high-Z VGPO1 = 20 V, GPO1 output high-Z Configured as CONV pin Configured as CONV pin Configured as CONV pin V V nA A IGPO2 = 1 mA IGPO2 = 5 mA VGPO2 2 V, GPO2 output high-Z VGPO2 = 20 V, GPO2 output high-Z 90 ICC3 VOP4 2.95 200 12.3 90 ICC4 VDIR 2.95 IIN_SENSE3 ISENSE3 IIN_SENSE4 ISENSE4 VVCAP 2.66 Leakage Current Input High Voltage Input Low Voltage Glitch Filter GPO2/ALERT2 PIN Output Low Voltage Leakage Current VIH VIL 1.1 0.8 1 VOL_GPO2 0.4 1.5 100 1 Rev. B | Page 4 of 48 Test Conditions/Comments VCC rising Reference to VEE IIN = 3.3 mA to 30 mA, maximum IIN dependent on TA and JA (see the Powering the ADM1294 section) VSHUNT rising VSHUNT = 13 V Data Sheet Parameter GRADE A DEVICE CURRENT AND VOLTAGE MONITORING Current Sense Absolute Error Current Sense Range (CSR) = 25 mV ADM1293/ADM1294 Symbol Min Typ 0.04 CSR = 50 mV CSR = 100 mV CSR = 200 mV Voltage Sense Absolute Error VIN VAUX Power Absolute Error GRADE B DEVICE CURRENT AND VOLTAGE MONITORING Current Sense Absolute Error CSR = 25 mV CSR = 50 mV 0.1 Max Unit Test Conditions/Comments 0.33 % 128 sample averaging, VSENSEP = 0 V to 18 V (unless otherwise noted) VSENSE = VSENSEP - VSENSEN = 20 mV, TA = -40C to +85C 0.38 0.72 2.65 1 0.35 0.44 0.59 1 2 5 0.26 0.4 0.23 0.3 0.21 0.27 % % % % % % % % % % % % % % % % 0.35 0.26 0.2 0.24 0.2 0.24 0.48 % % % % % % % 0.54 0.5 % % 0.54 0.48 % % 0.53 % VSENSE = 20 mV VSENSE = 20 mV, 16 sample averaging VSENSE = 20 mV, one sample averaging VSENSE = 20 mV, VSENSEP = 18 V to 20 V VSENSE = 25 mV VSENSE = 15 mV VSENSE = 10 mV VSENSE = 5 mV VSENSE = 2.5 mV VSENSE = 1 mV VSENSE = 40 mV VSENSE = 20 mV VSENSE = 80 mV VSENSE = 40 mV VSENSE = 160 mV VSENSE = 80 mV 128 sample averaging VVIN = 10 V to 20 V, VRANGE = 21 V VVIN = 3.6 V to 7.4 V, VRANGE = 7.4 V VVIN = 0.6 V to 1.2 V, VRANGE = 1.2 V, TA = -40C to +85C VVIN = 0.6 V to 1.2 V, VRANGE = 1.2 V VVAUX = 0.6 V to 1.2 V, TA = -40C to +85C VVAUX = 0.6 V to 1.2 V VSENSE = 20 mV, SENSEP = VIN = 12 V, VRANGE = 21 V, TA = -40C to +85C VSENSE = 20 mV, SENSEP = VIN = 12 V, VRANGE = 21 V VSENSE = 20 mV, SENSEP = VIN = 3.3 V, VRANGE = 7.4 V, TA = -40C to +85C VSENSE = 20 mV, SENSEP = VIN = 3.3 V, VRANGE = 7.4 V VSENSE = 20 mV, SENSEP = 20 mV, VIN = 0.8 V, VRANGE = 1.2 V, TA = -40C to +85C VSENSE = 20 mV, SENSEP = 20 mV, VIN = 0.8 V, VRANGE = 1.2 V 0.75 0.84 1.6 5.8 2.2 0.8 1 1.3 4.5 11 0.57 0.9 % % % % % % % % % % % % 128 sample averaging (unless otherwise noted) VSENSE = VSENSEP - VSENSEN = 20 mV, TA = -40C to +85C VSENSE = 20 mV VSENSE = 20 mV, 16 sample averaging VSENSE = 20 mV, one sample averaging VSENSE = 20 mV, VSENSEP = 18 V to 20 V VSENSE = 25 mV VSENSE = 15 mV VSENSE = 10 mV VSENSE = 2.5 mV VSENSE = 1 mV VSENSE = 40 mV VSENSE = 20 mV Rev. B | Page 5 of 48 ADM1293/ADM1294 Parameter CSR = 100 mV Data Sheet Symbol Min Typ Max 0.55 0.7 0.5 0.6 Unit % % % % 0.8 0.6 0.45 0.6 0.45 0.6 1.2 1.2 1.2 % % % % % % % % % 144 165 s 64 73 s 64 73 s 0.8 V A k A V A CSR = 200 mV Voltage Sense Absolute Error VIN VAUX Power Absolute Error ADC CONVERSION TIME ADRx PINS Address Set to 00 Input Current for Address 00 Address Set to 01 Address Set to 10 Address Set to 11 Input Current for Address 11 SERIAL BUS DIGITAL I/O Input High Voltage Input Low Voltage SDAO Output Low Voltage Input Leakage Nominal Bus Voltage Capacitance for I/O Pins Input Glitch Filter 0 -40 135 -1 2 -22 150 3 VIH VIL VOL ILEAK_PIN VDD CPIN tSP 165 +1 10 1.1 0.8 0.4 +10 +5 5.5 -10 -5 2.7 5 0 50 V V V A A V pF ns Rev. B | Page 6 of 48 Test Conditions/Comments VSENSE = 80 mV VSENSE = 40 mV VSENSE = 160 mV VSENSE = 80 mV 128 sample averaging VVIN = 10 V to 20 V, VRANGE = 21 V VVIN = 3.6 V to 7.4 V, VRANGE = 7.4 V VVIN = 0.6 V to 1.2 V, VRANGE = 1.2 V, TA = -40C to +85C VVIN = 0.6 V to 1.2 V, VRANGE = 1.2 V VVAUX = 0.6 V to 1.2 V, TA = -40C to +85C VVAUX = 0.6 V to 1.2 V VSENSE = 20 mV, SENSEP = VIN = 12 V, VRANGE = 21 V VSENSE = 20 mV, SENSEP = VIN = 3.3 V, VRANGE = 7.4 V VSENSE = 20 mV, SENSEP = 20 mV, VIN = 0.8 V, VRANGE = 1.2 V Includes time for power multiplication One sample of IOUT, from command received to valid data in register One sample of VIN, from command received to valid data in register One sample of VAUX, from command received to valid data in register Connect to VEE VADRx = 0 V to 0.8 V Resistor to VEE No connect state, maximum leakage current allowed Connect to VCAP VADRx = 2.0 V to VCAP, must not exceed the maximum allowable current draw from VCAP SDAI, SDAO, SCL IOL = 4 mA Device is not powered 3 V to 5 V 10% Data Sheet ADM1293/ADM1294 SERIAL BUS TIMING CHARACTERISTICS Table 2. Parameter fSCLK tBUF tHD;STA tSU;STA tSU;STO tHD;DAT tSU;DAT tLOW tHIGH tR1 tF 1 Description Clock frequency Bus free time Start hold time Start setup time Stop setup time SDA hold time SDA setup time SCL low time SCL high time SCL, SDA rise time SCL, SDA fall time Min Typ 1.3 0.6 0.6 0.6 300 100 1.3 0.6 20 20 Max 400 Unit kHz s s s s ns ns s s ns ns 900 300 300 tR = (VIL(MAX) - 0.15) to (VIH3V3 + 0.15) and tF = 0.9 VDD to (VIL(MAX) - 0.15), where VIH3V3 = 2.1 V, and VDD = 3.3 V. Serial Bus Timing Diagram tLOW SCL tR tF VIH VIL tHD;DAT tHIGH tSU;STA tSU;DAT tSU;STO tHD;STA VIH VIL P tBUF S S Figure 3. Serial Bus Timing Diagram Rev. B | Page 7 of 48 P 11891-003 SDAO/SDAI ADM1293/ADM1294 Data Sheet ABSOLUTE MAXIMUM RATINGS Pin voltages on the ADM1293 are referenced to the GND pin and pin voltages on the ADM1294 are referenced to the VEE pin. Table 3. Parameter VCC Pin VSHUNT Pin VCAP Pin SCL Pin SDAI Pin SDAO Pin ADR1 Pin ADR2 Pin GPO1/ALERT1/CONV Pin GPO2/ALERT2 Pin VIN Pin VAUX Pin SENSEP Pin SENSEN Pin Continuous Current into VSHUNT Pin Continuous Current into Any Other Pin Storage Temperature Range Operating Ambient Temperature Range ADM1293 Operating Junction Temperature Range ADM1294 Junction Temperature Range Lead Temperature, Soldering (10 sec) Junction Temperature Rating -0.3 V to +25 V -0.3 V to +14 V -0.3 V to +4 V -0.3 V to +6.5 V -0.3 V to +6.5 V -0.3 V to +6.5 V -0.3 V to VCAP + 0.3 V -0.3 V to VCAP + 0.3 V -0.3 V to +25 V -0.3 V to +25 V -0.3 V to +25 V -0.3 V to +4 V -0.3 V to +25 V -0.3 V to +25 V 30 mA 10 mA -65C to +150C THERMAL CHARACTERISTICS JA is specified for the worst case conditions, that is, a device soldered in a circuit board for surface-mount packages. Table 4. Thermal Resistance Package Type 16-Lead LFCSP 14-Lead TSSOP ESD CAUTION -40C to +105C -40C to +105C -40C to +110C 300C 150C Stresses at or above those listed under Absolute Maximum Ratings may cause permanent damage to the product. This is a stress rating only; functional operation of the product at these or any other conditions above those indicated in the operational section of this specification is not implied. Operation beyond the maximum operating conditions for extended periods may affect product reliability. Rev. B | Page 8 of 48 JA 50.58 122.73 Unit C/W C/W Data Sheet ADM1293/ADM1294 13 VIN 14 NIC 16 VAUX 12 SENSEP ADM1293 11 SENSEN ADR1 3 TOP VIEW (Not to Scale) 10 NIC 9 SCL 7 GPO2/ALERT2 GPO1/ALERT1/CONV 8 SDAI 5 SDAO 6 ADR2 4 VAUX 1 14 GND 2 13 VIN VCAP 3 12 SENSEP 11 SENSEN 10 GPO2/ALERT2 VCC NOTES 1. NIC = NOT INTERNALLY CONNECTED. 2. EXPOSED PAD. SOLDER THE EXPOSED PAD TO THE BOARD TO IMPROVE THERMAL DISSIPATION. THE EXPOSED PAD CAN BE CONNECTED TO GND. ADR1 4 ADR2 5 ADM1293 TOP VIEW (Not to Scale) SDAI 6 9 GPO1/ALERT1/CONV SDAO 7 8 SCL 11891-005 1 VCAP 2 11891-004 VCC 15 GND PIN CONFIGURATIONS AND FUNCTION DESCRIPTIONS Figure 5. ADM1293 TSSOP Pin Configuration Figure 4. ADM1293 LFCSP Pin Configuration Table 5. ADM1293 Pin Function Descriptions Pin No. LFCSP 16 TSSOP1 1 Mnemonic VAUX 1 2 VCC 2 3 3 4 VCAP ADR1 4 5 ADR2 5 6 SDAI 6 7 SDAO 7 8 8 9 SCL GPO1/ALERT1/CONV 9 10 GPO2/ALERT2 10 N/A NIC 11 12 13 11 12 13 SENSEN SENSEP VIN 14 15 EPAD N/A 14 N/A NIC GND EPAD 1 Description Auxiliary Voltage Monitoring Input. This pin reads back the auxiliary input voltage using the internal ADC. An external divider is required to monitor voltages higher than 1.2 V. Positive Supply Input. An undervoltage lockout (UVLO) circuit resets the device when a low supply voltage is detected. A 0.1 F decoupling capacitor must be placed close to the VCC pin. Internal Regulated Supply. Place a capacitor with a value of 1 F or greater on this pin to maintain accuracy. PMBus Address. This pin can be tied low, tied to VCAP, left floating, or tied low through a resistor. Combine with the ADR2 pin to set up to 16 different PMBus addresses. PMBus Address. This pin can be tied low, tied to VCAP, left floating, or tied low through a resistor. Combine with the ADR1 pin to set up to 16 different PMBus addresses. PMBus Serial Data Input. This is a split version of the SDA for easy use with optocouplers. Tie this pin directly to the SDAO pin if a bus split is not required. PMBus Serial Data Output. This is a split version of the SDA for easy use with optocouplers. Tie this pin directly to the SDAI pin if a bus split is not required. PMBus Serial Clock. Open-drain input. Requires an external resistive pull-up. General-Purpose Digital Output (GPO1). Alert (ALERT1). This pin can be configured to generate an alert signal when one or more warning conditions are detected. Conversion (CONV). This pin can be used as an input signal to control when a power monitor ADC sampling cycle begins. This pin defaults to an alert output at power up. There is no internal pull-up on this pin. General-Purpose Digital Output (GPO2). Alert (ALERT2). This pin can be configured to generate an alert signal when one or more warning conditions are detected. This pin defaults to an alert output at power up. There is no internal pull-up on this pin. Not Internally Connected. This pin is not internally connected. Negative Current Sense Input. Positive Current Sense Input. Primary Voltage Monitoring Input. This pin reads back the primary input voltage using the internal ADC. The internal divider allows this pin to directly monitor a 20 V supply. An external divider is required to monitor voltages higher than 20 V. Not Internally Connected. This pin is not internally connected. Chip Ground. This pin must connect to the lowest potential. Exposed Pad. Solder the exposed pad to the board to improve thermal dissipation. Connect the exposed pad to GND. N/A means not applicable. Rev. B | Page 9 of 48 13 VIN 14 NIC Data Sheet 12 SENSEP 1 VCAP 2 AD1294 ADR1 3 TOP VIEW (Not to Scale) 11 SENSEN 10 NIC SCL 7 GPO1/ALERT1/CONV 8 SDAI 5 SDAO 6 GPO2/ALERT2 NOTES 1. NIC = NOT INTERNALLY CONNECTED. 2. EXPOSED PAD. SOLDER THE EXPOSED PAD TO THE BOARD TO IMPROVE THERMAL DISSIPATION. THE EXPOSED PAD CAN BE CONNECTED TO VEE. Figure 6. ADM1294 LFCSP Pin Configuration VAUX 1 14 VEE VSHUNT 2 13 VIN VCAP 3 12 SENSEP 11 SENSEN 10 GPO2/ALERT2 ADR1 4 ADR2 5 ADM1294 TOP VIEW (Not to Scale) SDAI 6 9 GPO1/ALERT1/CONV SDAO 7 8 SCL 11891-007 9 ADR2 4 11891-006 VSHUNT 15 VEE 16 VAUX ADM1293/ADM1294 Figure 7. ADM1294 TSSOP Pin Configuration Table 6. ADM1294 Pin Function Descriptions Pin No. LFCSP 16 TSSOP1 1 Mnemonic VAUX 1 2 VSHUNT 2 3 3 4 VCAP ADR1 4 5 ADR2 5 6 SDAI 6 7 SDAO 7 8 8 9 SCL GPO1/ALERT1/CONV 9 10 GPO2/ALERT2 10 11 12 13 N/A 11 12 13 NIC SENSEN SENSEP VIN 14 15 EPAD N/A 14 N/A NIC VEE EPAD 1 Description Auxiliary Voltage Monitoring Input. This pin reads back the auxiliary input voltage using the internal ADC. An external divider is required to monitor voltages higher than 1.2 V. Shunt Regulated Positive Supply to Chip. Connect this pin to the positive supply rail. A shunt resistor in series is required to limit the input current if the supply voltage is higher than the shunt regulation voltage. A 1 F decoupling capacitor to VEE is recommended on the VSHUNT pin. Internal Regulated Supply. Place a capacitor with a value of 1 F or greater on this pin to maintain accuracy. PMBus Address. This pin can be tied low, tied to VCAP, left floating, or tied low through a resistor. Combine with the ADR2 pin to set up to 16 different PMBus addresses. PMBus Address. This pin can be tied low, tied to VCAP, left floating, or tied low through a resistor. Combine with the ADR1 pin to set up to 16 different PMBus addresses. PMBus Serial Data Input. This is a split version of the SDA for easy use with optocouplers. Tie this pin directly to the SDAO pin if a bus split is not required. PMBus Serial Data Output. This is a split version of the SDA for easy use with optocouplers. Tie this pin directly to the SDAI pin if a bus split is not required. PMBus Serial Clock. Open-drain input. Requires an external resistive pull-up. General-Purpose Digital Output (GPO1). Alert (ALERT1). This pin can be configured to generate an alert signal when one or more warning conditions are detected. Conversion (CONV). This pin can be used as an input signal to control when a power monitor ADC sampling cycle begins. This pin defaults to an alert output at power up. There is no internal pull-up on this pin. General-Purpose Digital Output (GPO2). Alert (ALERT2). This pin can be configured to generate an alert signal when one or more warning conditions are detected. This pin defaults to an alert output at power up. There is no internal pull-up on this pin. Not Internally Connected. This pin is not internally connected. Negative Current Sense Input. Positive Current Sense Input. Primary Voltage Monitoring Input. This pin reads back the primary input voltage using the internal ADC. The internal divider allows this pin to directly monitor a 20 V supply. An external divider is required to monitor voltages higher than 20 V. Not Internally Connected. This pin is not internally connected. Chip Ground Pin. This pin must connect to the lowest potential. Exposed Pad. Solder the exposed pad to the board to improve thermal dissipation. Connect the exposed pad to VEE. N/A means not applicable. Rev. B | Page 10 of 48 Data Sheet ADM1293/ADM1294 TYPICAL PERFORMANCE CHARACTERISTICS 120 3.5 VCC = 20V 2.0 ADM1293 ADM1294 1.5 1.0 11891-008 0.5 0 0 5 10 15 VCC/VSHUNT VOLTAGE (V) 60 40 20 0 5 0 5 VSENSEP = VSENSEN = VCC TOTAL SENSEx PIN INPUT CURRENT (nA) 3.0 2.5 2.0 1.5 1.0 11891-009 0.5 -20 0 25 85 4 3 2 1 0 -1 -2 -3 -4 -5 2.95 105 5.00 TEMPERATURE (C) 15.00 20.00 Figure 12. ADM1293 Total SENSEP and SENSEN Pins Input Current vs. SENSEP and SENSEN Pin Voltage 14.0 13.5 VSHUNT AT IIN = 30mA VSHUNT AT IIN = 3.3mA 12.5 12.0 11.5 11.0 10.5 -20 0 25 TEMPERATURE (C) 85 VSENSEP = VSENSEN = VCC/VSHUNT 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 -40 105 Figure 10. VSHUNT Regulation Voltage vs. Temperature 11891-013 TOTAL SENSEx PIN INPUT CURRENT (nA) 1.0 11891-010 VSHUNT REGULATION VOLTAGE (V) 10.00 VOLTAGE ON SENSEx PINS (V) Figure 9. ICC vs. Temperature 10.0 -40 20 15 Figure 11. ADM1293 SENSEP/SENSEN Pins Input Current vs. SENSEP and SENSEN Pin Voltage VCC = VSHUNT = 3.3V 13.0 10 VOLTAGE ON SENSEx PINS (V) 3.5 ICC (mA) 80 20 Figure 8. ICC vs. Pin Voltages 0 -40 ISENSEP ISENSEN 11891-012 ICC (mA) 2.5 100 11891-011 SENSEx PIN INPUT CURRENT (nA) 3.0 -20 0 25 TEMPERATURE (C) 85 105 Figure 13. Total SENSEP and SENSEN Input Current vs. Temperature Rev. B | Page 11 of 48 ADM1293/ADM1294 Data Sheet 8 40 VSENSEP = 0V VSENSEP = 12V 20 0 -20 -40 -80 -200 11891-014 -60 -150 -100 0 50 100 VSENSEP - VSENSEN (mV) 150 -50 IVIN RANGE = 0V TO 1.2V IVIN DISABLED IVAUX RANGE = 0V TO 1.2V IVAUX DISABLED 4 2 0 -2 -4 -6 0 200 2 4 6 8 10 12 14 16 18 20 VOLTAGE ON VIN AND VAUX PINS (V) Figure 17. VIN/VAUX Input Currents vs. VIN/VAUX Voltage Figure 14. SENSEP and SENSEN Pins Input Current Imbalance vs. SENSEP and SENSEN Pins Differential Voltage 10 5 VIN AND VAUX PIN INPUT CURRENTS 4 VCC = VSENSEP = 3.3V VSENSEP - VSENSEN = 20mV 3 ISENSEN - ISENSEP (nA) 6 2 1 0 -1 -2 -3 -5 -40 -20 0 25 TEMPERATURE (C) 85 6 4 2 0 -2 VIN = 12V, RANGE = 21V, UNIT: A VIN = 0.6V, RANGE=1.2V, UNIT: nA VAUX = 0.6V, SAMPLING ENABLED, UNIT: nA VAUX = 0.6V, SAMPLING DISABLED, UNIT: nA -4 -6 -8 11891-015 -4 8 11891-018 ISENSEN - ISENSEP (nA) 60 11891-017 VIN AND VAUX PIN INPUT CURRENTS (nA) 80 -10 -40 105 -10 20 50 80 TEMPERATURE (C) Figure 18. VIN/VAUX Input Currents vs. Temperature Figure 15. SENSEN and SENSEP Input Current Imbalance vs. Temperature 12 4.5 11 GRADE A, TA = -40C TO +105C GRADE B, TA = -40C TO +105C 3.5 MAXIMUM ERROR (%) 9 2.5 1.5 8 7 6 5 4 3 0.5 -0.5 1 0 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 5 10 15 20 25 CURRENT SENSE VOTLAGE (mV) VOLTAGE ON VIN PIN (V) Figure 16. VIN Input Current vs. VIN Pin Voltage, VRANGE = 0 V to 7.4 V or 0 V to 21 V 11891-019 2 11891-016 VIN PIN INPUT CURRENT (A) 10 Figure 19. Worst Case Current Sense Error vs. Current Sense Voltage with 128 Sample Averaging, VSENSEP = 0 V to 18 V, over Full Operating Temperature Range Rev. B | Page 12 of 48 Data Sheet 00 DECODE 01 DECODE 10 DECODE 2.5 11 DECODE 2.5 GPOx LOW VOLTAGE (V) 2.0 1.5 1.0 0 -25 1.5 GPO1 GPO2 1.0 0.5 0.5 -20 -15 -10 -5 IADRx (A) 0 5 11891-020 VADRx (V) 2.0 Figure 20. VADRx vs. IADRx 11891-021 3.0 ADM1293/ADM1294 0 0 2 4 6 8 10 SINK CURRENT (mA) Figure 21. GPOx Output Low Voltage vs. Sink Current Rev. B | Page 13 of 48 12 ADM1293/ADM1294 Data Sheet THEORY OF OPERATION POWERING THE ADM1293 POWERING THE ADM1294 A supply voltage from 2.95 V to 20 V is required to power the ADM1293 via the VCC pin. The VCC pin provides the majority of the bias current for the device. The internal shunt regulator allows ADM1294 to be powered directly from a high voltage source. The shunt regulator is disabled when the supply voltage on the VSHUNT pin is below shunt regulation voltage level. After the supply rises above the shunt regulation level, the shunt regulator starts to regulate the voltage on the VSHUNT pin to approximately 12 V. An external current limiting resistor is required to limit the current entering the VSHUNT pin, as shown in Figure 25. RTN RSHUNT VIN RSENSE 12V SENSEP VEE SENSEN LOAD 0.1F GND The shunt regulator also maintains a stable supply voltage during transient events on the input supply, protecting the ADM1294 from experiencing overvoltage stress. Figure 22. Powering the ADM1293 from a Monitoring Rail To protect the ADM1293 from unnecessary resets due to transient supply glitches, add an external resistor, as shown in Figure 23. Choose the values of the resistor in conjunction with the decoupling capacitor such that a time constant is provided that can filter any expected glitches. However, use a resistor that is small enough to keep voltage drops due to quiescent current to a minimum. Shunt Current Limiting Resistor Selection The current limiting resistor value must be calculated correctly to provide sufficient current/voltage to power the ADM1294, while keeping the power low enough to prevent the IC from overheating. Calculate the current limiting resistance upper limit by RSENSE 3.3V SENSEP RSENSE Figure 25. Powering the ADM1294 in a -48 V System 11891-022 ADM1293 LOAD ADM1294 SENSEN -48V VIN VCC VSHUNT 0.1F 11891-025 To ensure correct operation of the ADM1293, the voltage on the VCC pin must be greater than or equal to the voltage on the SENSEP pin. No sequencing of the VCC and SENSEP rails is necessary. The voltage on SENSEP pin can drop to as low as 0 V for normal operation, provided that a voltage of at least 2.95 V is connected to the VCC pin. For a monitoring supply rail above 3 V, connect both the VCC pin and the SENSEP pin to the same voltage rail via separate traces to prevent accuracy loss in the sense voltage measurement (see Figure 22). R SHUNT _ MAX = V INPUT _ MIN - V OP4 _ MIN I CC4 _ MAX SENSEN SENSEP 22 where: VINPUT_MIN is the minimum supply input voltage before the current limiting resistor. VOP4_MIN is the minimum operating voltage of the ADM1294. ICC4_MAX is the maximum supply current of the ADM1294. VIN LOAD ADM1293 11891-024 VCC 0.1F GND Figure 23. Transient Glitch Protection Using an RC Network For monitoring rails below 2.95 V to 0 V, a separate supply is required to provide power to the ADM1293, as shown in Figure 24. RSENSE 1V SENSEP SENSEN VIN VCC ADM1293 0.1F GND LOAD 11891-023 3.3V When the ADM1294 is in shunt regulation mode, if the supply voltage decreases to a point where the current flowing through the current limiting resistor is not enough to power the IC, the ADM1294 automatically exits the fixed voltage regulation mode and enters into current regulation mode. In current regulation mode, the device lowers the voltage on the VSHUNT pin to maintain the current required to power itself. The VSHUNT pin voltage can be decreased to the minimum operating voltage of the ADM1294. The smooth transition in and out of shunt regulation mode helps to increase the RSHUNT_MAX value, and as a result, extends the range of the suitable current limiting resistors. Figure 24. Powering the ADM1293 from a Separate Supply Rev. B | Page 14 of 48 Data Sheet ADM1293/ADM1294 The worst case power dissipation across the current limiting resistor is Calculate the current limiting resistance lower limit by V INPUT _ MAX - V SHUNT _ MAX where: VINPUT_MAX is the maximum supply input voltage before the current limiting resistor. VSHUNT_MAX is the maximum shunt regulation voltage of the ADM1294. ISHUNT_MAX is the maximum current allowed into the shunt regulator. It is related to the maximum allowable power dissipation of the device in a given design, which is limited by the maximum junction temperature of the device. I SHUNT _ MAX = (V PR_WORST = I SHUNT _ MAX PDISS _ MAX - VSHUNT _ MIN ) 2 INPUT _ MAX RSHUNT (75 V - 11.5 V )2 = = 0.54 W 7.5 k The user may need multiple resistors in series or in parallel to meet the power level that is required. Example 2: A system has a 180 V supply that can vary between -160 V to +200 V. The system maximum ambient temperature is 105C. An ADM1294 in the LFCSP package monitors the supply. It is soldered on a JEDEC 2S2P board, with a minimal footprint and a 3 x 3 thermal via array. V INPUT _ MIN - V OP4 _ MIN R SHUNT _ MAX = VSHUNT _ MAX = 160 V - 2.95 V and PDISS _ MAX = JA where: TJ_MAX is the maximum junction temperature of the ADM1294. TA_MAX is the maximum ambient temperature of the system. JA is the junction to ambient thermal resistance of the ADM1294. Example 1: A system has a -48 V supply that can vary between -35 V to -75 V. The system maximum ambient temperature is 85C. An ADM1294 in an LFCSP package monitors the supply. It is soldered on a JEDEC 2S2P board, with a minimal footprint and a 3 x 3 thermal via array. Note that because the ADM1294 uses low-side sensing, as shown in Figure 25, all of the voltages are expressed by referencing to the negative supply input. R SHUNT_MAX = V INPUT_MIN - V OP 4 _MIN = 35 V - 2 .95 V I CC 4 _MAX P DISS _ MAX = T JMAX - T AMAX JA I SHUNT _ MAX = PDISS _ MAX = = 110C - 85C 50.58C 0.494 W I SHUNT _ MAX = 38 mA = 75 V - 13 V = RSHUNT _ MIN = 110C - 105C 50.58C 0.1 W = 0.1 W = 7.7 mA 13 V VINPUT _ MIN - VSHUNT _ MAX = I SHUNT _ MAX 200 V - 13 V = 24.3 k 7.7 mA The user can select a current limiting resistor with a value between 43.6 k and 24.3 k. This example uses a 39 k resistor. The worst case power dissipation across the current limiting resistor is: (V - VSHUNT _ MIN ) 2 INPUT _ MAX RSHUNT = (200 V - 11.5 V )2 39 k = 0.91 W The user may need multiple resistors in series or in parallel to meet the power level that is required. Additional Options of Powering the ADM1294 If the supply input range is too wide to choose a suitable current limiting resistor or causing too much power loss, a source follower circuit can be used to generate the supply voltage for the ADM1294, as shown in Figure 26. 13 V V INPUT _ MIN - V SHUNT _ MAX PDISS _ MAX V SHUNT _ MAX = 8 .9 k = 0.494 W = JA I SHUNT _ MAX = PR_WORST = 3 . 6 mA V SHUNT _ MAX R SHUNT _ MIN = T JMAX - T AMAX P DISS _ MAX = TJ _ MAX - TA _ MAX = 43.6 k 3.6 mA I CC4 _ MAX = 1.63 k VIN 38 mA RZ The user can select a current limiting resistor with a value between 8.9 k and 1.63 k. It is recommended to select one at the higher end to reduce power dissipation. After a value is chosen, for example, 7.5 k, the user must check its worst-case power dissipation. In this example, the worst case is when the input supply is at its maximum value. R1 M1 VSHUNT 0.1F 5.6V ADM1294 VEE 11891-026 R SHUNT _ MIN = Figure 26. Powering the ADM1294 Through a Source Follower Circuit Rev. B | Page 15 of 48 ADM1293/ADM1294 Data Sheet In this circuit, RZ limits the current into the Zener diode, the NMOSFET (or an NPN transistor in the case of an emitter follower) buffers the voltage created by the Zener to supply the ADM1294. The NMOS must be able to withstand the voltage drop of the supply voltage and the worst case power dissipation. The worst case power dissipation is expressed as RSENSE 12V 3.3V SENSEP ADM1293 VAUX 11891-028 VIN SENSEN PFET_WORST = (VINPUT_MAX - VZENER + VTH) x ICC4_MAX where: VINPUT_MAX is the maximum supply input voltage before the current limiting resistor. VZENER is the Zener diode reverse breakdown voltage. VTH is the threshold of the NMOSFET or base to emitter voltage in the case of an NPN emitter follower. ICC4_MAX is the maximum supply current of the ADM1294. Figure 28. Power Monitor Input Filters for the ADM1293 VIN ADM1294 VISO VIN SDA1 SDA2 SCL1 SCL2 3.3V/5V SDA SDAI GNDISO -48V POWER MONITOR POWER + I2C ISOLATOR SDAO SCL RSENSE Figure 29. Power Monitor Input Filters for the ADM1294 ADM3260 SCL PROCESSOR GNDP 11891-027 ADM1294 SENSEP -48V -48V RTN VSHUNT VAUX 11891-029 SENSEN Another option to supply power to the ADM1294 is to use the ADM3260 I2C and a power isolator, as shown in Figure 27. 3.3V/5V_ISO 3.3V (REFERENCE TO -48V) RTN VEE Figure 27. Powering the ADM1294 Using the ADM3260 I2C and Power Isolator Isolation is usually required in -48 V systems because there can be a large voltage difference between different ground planes in the system. The ADM1294 is referenced to -48 V, whereas the microcontroller unit (MCU) is usually referenced to 0 V. In almost all cases, the I2C signals must be isolated. Any other ADM1294 digital input and output signals that enter or exit the MCU must also be isolated. The ADM3260 isolator can transfer power and a bidirectional I2C digital signal across an isolation barrier of up to 2.5 kV. The output voltage from the ADM3260 can power the ADM1294 directly as well as providing pull-up resistance for the I2C bus lines. See the ADM3260 data sheet for more information about this device. OPTIONAL POWER MONITOR INPUTS FILTERING The internal ADC on both the ADM1293 and ADM1294 uses the current sense input pins, SENSEP and SENSEN, to measure the load current. Additional antialiasing filtering can be placed on the power monitor pins to reduce current monitoring noise. Similarly, RC filters can be used on the voltage sensing inputs, VIN and VAUX, to reduce voltage sensing noise. The ADM1293/ADM1294 feature an integrated ADC that accurately measures the current sense voltage, the input voltage, and optionally, an auxiliary input voltage. The measured input voltage, and current being delivered to the load are multiplied together to give a power value that can be read back. Each power value is also added to an energy accumulator that can be read back to allow an external device to calculate the energy consumption of the load. The ADM1293/ADM1294 can report the measured current, input voltage, and auxiliary voltage. The PEAK_VIN, PEAK_VAUX, MIN_IOUT, MAX_IOUT, MIN_PIN, and MAX_PIN commands are used to read the peak readings since the value was last cleared. An averaging function of up to 128x is provided for the voltage, current, and power. This function allows a number of samples to be averaged together by the ADM1293/ADM1294. This function reduces the need for postprocessing of sampled data by the host processor. The number of samples that can be averaged is 2N, where N is in the range of 0 to 7. The power averaging is calculated independently of voltage and current averaging value to give the most accurate result. For example, if the two consecutive voltage measurement results are 12.00 V and 12.08 V, and the corresponding current measurement results are 10.0 A and 10.8 A, and the 2x averaging results for voltage and current are 12.04 V and 10.4 A, respectively, then the 2x power averaging result is 12 x 10 + 12.08 x 10.8 = 125.232 W 2 Not 12.04 x 10.4 = 125.216 W. Rev. B | Page 16 of 48 Data Sheet ADM1293/ADM1294 The power monitor current sense amplifier is bipolar and can measure both positive and negative currents. The current sense amplifier has four selectable input ranges: 25 mV, 50 mV, 100 mV, and 200 mV. Operating closer to the full range results in higher current measurement accuracy and higher insertion loss across the sense resistor. The power monitor voltage sensing input, VIN, has three selectable input ranges: 0 V to 1.2 V, 0 V to 7.6 V, and 0 V to 21 V. Configuring the VIN pin to the 0 V to 1.2 V range gives the pin a direct connection to the internal ADC, and results in minimum leakage current into the pin. It is the recommended configuration for use with external resistor dividers. The VAUX input has a fixed 0 V to 1.2 V voltage monitoring range. Both the current and voltage sensing ranges can be configured using the PMON_CONFIG command. The two basic modes of operation for the power monitor are single shot and continuous. In single shot mode, the ADC samples the input voltage and current a number of times, depending on the averaging value selected by the user. The ADM1293/ADM1294 return a single value corresponding to the average voltage and current measured. When configured for continuous mode, the power monitor continuously samples the voltage and current, making the most recent sample available to be read. When the GPO1/ALERT1/CONV pin is set to convert (CONV) mode, an external hardware signal triggers the single shot sampling of one or more parts at the same time. Each time that current sense and input voltage measurements are taken, a power calculation is performed that multiplies the two measurements together. This can be read from the device using the READ_PIN command, returning the input power. At the same time, the calculated power value is added to the power accumulator register that may increment a rollover counter if the value exceeds the maximum accumulator value. The power accumulator register also increments a power sample counter. The power accumulator and power sample counter are read using the same READ_EIN command to ensure that the accumulated value and sample count are from the same point in time. The bus host reading the data assigns a time stamp when the data is read. By calculating the time difference between consecutive uses of READ_EIN and determining the delta in power consumed, it is possible for the host to determine the total energy consumed over that period. Single shot mode can be triggered in a number of ways. The simplest is by selecting the single shot mode using the PMON_CONFIG command and writing to the convert bit using the PMON_CONTROL command. The convert bit can also be written as part of a PMBus group command. Using a group command allows multiple devices to be written to as part of the same I2C bus transaction, with all devices executing the command when the stop condition appears on the bus. In this way, several devices can be triggered to sample at the same time. Table 7. ADM1293 and ADM1294 Model Options Model ADM1293-1A ADM1293-1B ADM1294-1A ADM1294-1B ADM1293-2A ADM1294-2A Build in Shunt Regulator No No Yes Yes No Yes Monitoring Accuracy Grade A B A B A A Rev. B | Page 17 of 48 Energy Meter Implementation Custom Custom Custom Custom PMBus Standard PMBus Standard ADM1293/ADM1294 Data Sheet PMBus INTERFACE The I2C bus is a common, simple serial bus used by many devices to communicate. It defines the electrical specifications, the bus timing, the physical layer, and some basic protocol rules. SMBus is based on I2C and aims to provide a more robust and fault tolerant bus. Functions such as bus timeout and packet error checking are added to help achieve this robustness, along with more specific definitions of the bus messages that read and write data to devices on the bus. PMBus is layered on top of SMBus and, in turn, on I2C. Using the SMBus defined bus messages, PMBus defines a set of standard commands that control a device that is part of a power chain. The ADM1293/ADM1294 command set is based upon the PMBusTM Power System Management Protocol Specification, Part I and Part II, Revision 1.2. This version of the standard is provides a common set of commands for communicating with dc-to-dc type devices. However, many of the standard PMBus commands can be mapped directly to the functions of a digital power monitor. Part I and Part II of the PMBus standard describe the basic commands and how they are used in a typical PMBus setup. The following sections describe how the PMBus standard and the ADM1293/ADM1294 specific commands are used. DEVICE ADDRESSING The PMBus device address is seven bits in size. There are no default addresses for any of the models; any device can be programmed to any of 16 possible addresses. Two quad level ADRx pins map to the 16 possible device addresses. Table 8. ADRx Pin Connections ADRx State Low Resistor High-Z High ADRx Pin Connection Connect to GND 150 k resistor to GND No connection (floating) Connect to VCAP Table 9. Setting I2C Addresses via the ADR1 Pin and the ADR2 Pin Base Address (Binary) 011 1 ADR2 Pin State Ground Ground Ground Ground Resistor to ground Resistor to ground Resistor to ground Resistor to ground Floating Floating Floating Floating High High High High ADR1 Pin State Ground Resistor to ground Floating High Ground Resistor to ground Floating High Ground Resistor to ground Floating High Ground Resistor to ground Floating High ADR2 Logic State 00 00 00 00 01 01 01 01 10 10 10 10 11 11 11 11 X means don't care. Rev. B | Page 18 of 48 ADR1 Logic State 00 01 10 11 00 01 10 11 00 01 10 11 00 01 10 11 Address (Binary)1 0110000X 0110001X 0110010X 0110011X 0110100X 0110101X 0110110X 0110111X 0111000X 0111001X 0111010X 0111011X 0111100X 0111101X 0111110X 0111111X Address (Hex) 0x30 0x31 0x32 0x33 0x34 0x35 0x36 0x37 0x38 0x39 0x3A 0x3B 0x3C 0x3D 0x3E 0x3F Data Sheet ADM1293/ADM1294 Within a group command, the host can choose whether to send a PEC byte as part of the message to the ADM1293/ADM1294. SMBus PROTOCOL USAGE All I2C transactions on the ADM1293/ADM1294 are performed using SMBus defined bus protocols. The following SMBus protocols are implemented by the ADM1293/ADM1294: PARTIAL TRANSACTIONS ON I2C BUS If there is a partial transaction on the I2C bus, for example, spurious data interpreted as a start command, the ADM1293/ ADM1294 I2C bus does not lock up, thinking it is in the middle of an I2C transaction. A new start command is recognized even in the middle of another transaction. Send byte Receive byte Write byte Read byte Write word Read word Block read SMBus MESSAGE FORMATS Figure 30 to Figure 38 show all of the SMBus protocols that are supported by the ADM1293/ADM1294, together with the PEC variant. In these figures, unshaded cells indicate that the bus host is actively driving the bus; shaded cells indicate that the ADM1293/ADM1294 is driving the bus. PACKET ERROR CHECKING The ADM1293/ADM1294 PMBus interface supports the use of the packet error checking (PEC) byte, which is defined in the SMBus standard. The PEC byte is transmitted by the ADM1293/ ADM1294 during a read transaction or sent by the bus host to the ADM1293/ADM1294 during a write transaction. The ADM1293/ADM1294 support the use of PEC with all the SMBus protocols that it implements. Figure 30 to Figure 38 use the following abbreviations: The use of the PEC byte is optional. The bus host can decide whether to use the PEC byte with the ADM1293/ADM1294 on a message by message basis. There is no need to enable or disable PEC in the ADM1293/ADM1294. S is the start condition. Sr is the repeated start condition. P is the stop condition. R is the read bit. W is the write bit. A is the acknowledge bit (0). A is the acknowledge bit (1). A, the acknowledge bit, is typically active low (Logic 0) if the transmitted byte is successfully received by a device. However, when the receiving device is the bus master, the acknowledge bit for the last byte read is a Logic 1, indicated by A. The PEC byte is used by the bus host or the ADM1293/ADM1294 to detect errors during a bus transaction, depending on whether the transaction is a read or a write. If the host determines that the PEC byte read during a read transaction is incorrect, it can decide to repeat the read if necessary. If the ADM1293/ADM1294 determine that the PEC byte sent during a write transaction is incorrect, it ignores the command (does not execute it) and sets a status flag. SLAVE ADDRESS W A DATA BYTE A S SLAVE ADDRESS W A DATA BYTE A P PEC A P PEC A P 11891-030 S MASTER TO SLAVE SLAVE TO MASTER Figure 30. Send Byte and Send Byte with PEC SLAVE ADDRESS R A DATA BYTE A S SLAVE ADDRESS R A DATA BYTE A P 11891-031 S MASTER TO SLAVE SLAVE TO MASTER Figure 31. Receive Byte and Receive Byte with PEC S SLAVE ADDRESS W A COMMAND CODE A DATA BYTE A SLAVE ADDRESS W A COMMAND CODE A DATA BYTE A P PEC A P 11891-032 S MASTER TO SLAVE SLAVE TO MASTER Figure 32. Write Byte and Write Byte with PEC Rev. B | Page 19 of 48 ADM1293/ADM1294 S SLAVE ADDRESS W A COMMAND CODE A Sr SLAVE ADDRESS R A DATA BYTE A SLAVE ADDRESS W A COMMAND CODE A Sr SLAVE ADDRESS R A DATA BYTE A P PEC A P 11891-033 S Data Sheet MASTER TO SLAVE SLAVE TO MASTER Figure 33. Read Byte and Read Byte with PEC SLAVE ADDRESS W A COMMAND CODE A DATA BYTE LOW A DATA BYTE HIGH A S SLAVE ADDRESS W A COMMAND CODE A DATA BYTE LOW A DATA BYTE HIGH A P PEC A P 11891-034 S MASTER TO SLAVE SLAVE TO MASTER Figure 34. Write Word and Write Word with PEC S SLAVE ADDRESS W DATA BYTE HIGH S A SLAVE ADDRESS COMMAND CODE A Sr SLAVE ADDRESS R A DATA BYTE LOW A A COMMAND CODE A Sr SLAVE ADDRESS R A DATA BYTE LOW A R A BYTE COUNT = N A A BYTE COUNT = N A P W DATA BYTE HIGH A PEC A P 11891-035 A MASTER TO SLAVE SLAVE TO MASTER Figure 35. Read Word and Read Word with PEC S SLAVE ADDRESS W DATA BYTE 1 S A DATA BYTE 2 A SLAVE ADDRESS W DATA BYTE 1 COMMAND CODE A SLAVE ADDRESS A COMMAND CODE DATA BYTE 2 DATA BYTE N A Sr A SLAVE ADDRESS A P R DATA BYTE N A A PEC P 11891-036 A A Sr MASTER TO SLAVE SLAVE TO MASTER Figure 36. Block Read and Block Read with PEC ONE OR MORE DATA BYTES S DEVICE 1 ADDRESS W A COMMAND CODE 1 A LOW DATA BYTE Sr DEVICE 2 ADDRESS W A COMMAND CODE 2 A LOW DATA BYTE A HIGH DATA BYTE A ONE OR MORE DATA BYTES A HIGH DATA BYTE A ONE OR MORE DATA BYTES DEVICE N ADDRESS W A COMMAND CODE N A LOW DATA BYTE A HIGH DATA BYTE A P 11891-037 Sr MASTER TO SLAVE SLAVE TO MASTER Figure 37. Group Command ONE OR MORE DATA BYTES S DEVICE 1 ADDRESS W A COMMAND CODE 1 A LOW DATA BYTE Sr DEVICE 2 ADDRESS W A COMMAND CODE 2 A LOW DATA BYTE Sr DEVICE N ADDRESS W A COMMAND CODE N A LOW DATA BYTE A HIGH DATA BYTE A PEC 1 A A PEC 2 A A PEC N A P ONE OR MORE DATA BYTES A HIGH DATA BYTE ONE OR MORE DATA BYTES HIGH DATA BYTE 11891-038 A MASTER TO SLAVE SLAVE TO MASTER Figure 38. Group Command with PEC Rev. B | Page 20 of 48 Data Sheet ADM1293/ADM1294 GROUP COMMANDS The PMBus standard defines what are known as group commands. Group commands are single bus transactions that send commands or data to more than one device at the same time. Each device is addressed separately, using its own address; there is no special group command address. A group command transaction can contain only write commands that send data to a device. It is not possible to use a group command to read data from devices. From an I2C protocol point of view, a normal write command consists of the following: * * * * I2C start condition Slave address bits and a write bit (followed by an acknowledge from the slave device) One or more data bytes (each of which is followed by an acknowledge from the slave device) I2C stop condition to end the transaction A group command differs from a nongroup command in that after the data is written to one slave device, a repeated start condition is placed on the bus, followed by the address of the next slave device and data. This continues until all of the devices have been written to, at which point the stop condition is placed on the bus by the master device. The format of a group command and a group command with PEC is shown in Figure 37 and Figure 38. Each device that is written to as part of the group command does not immediately execute the command written. The device must wait until the stop condition appears on the bus. At that point, all devices execute their commands at the same time. Using a group command, it is possible, for example, to turn multiple PMBus devices on or off simultaneously. In the case of the ADM1293/ADM1294, it is also possible to issue a power monitor command that initiates a conversion, causing multiple ADM1293/ADM1294 devices to sample together at the same time. INFORMATION COMMANDS CAPABILITY Command Host processors can use the CAPABILITY command to determine the I2C bus features that are supported by the ADM1293/ADM1294. The features that can be reported include the maximum bus speed, whether the device supports the PEC byte, and the SMBALERT reporting function. PMBUS_REVISION Command The PMBUS_REVISION command reports the version of Part I and Part II of the PMBus standard. MFR_ID, MFR_MODEL, and MFR_REVISION Commands The MFR_ID, MFR_MODEL, and MFR_REVISION commands return ASCII strings that facilitate detection and identification of the ADM1293/ADM1294 on the bus. These commands are read using the SMBus block read message type. This message type requires that the ADM1293/ADM1294 return a byte count corresponding to the length of the string data that is to be read back. STATUS COMMANDS The ADM1293/ADM1294 provide a number of status bits that are used to report warnings detected. These status bits are located in four different registers that are arranged in a hierarchy. The STATUS_BYTE and STATUS_WORD commands provide 8 bits and 16 bits of high level information, respectively. The STATUS_BYTE and STATUS_WORD commands contain the most important status bits, as well as pointer bits that indicate whether any of the three other status registers must be read for more detailed status information. Warnings in the ADM1293/ADM1294 are generated from a digital comparison between the power monitor measurements to the threshold values set by the various limit commands. A warning can be used to control the state of the ALERTx output pins, or to generate a SMBALERT interrupt signal through one of the ALERTx pins. When a status bit is set, it always means that the status condition is active or was active at some point in the past. When a warning bit is set, it is latched until it is explicitly cleared using the CLEAR_FAULTS command. Some other status bits are live, that is, they always reflect a status condition and are never latched. STATUS_BYTE and STATUS_WORD Commands The STATUS_BYTE and STATUS_WORD commands can be used to obtain a snapshot of the overall device status. These commands indicate whether it is necessary to read more detailed information using the other status commands. The low byte of the word returned by the STATUS_WORD command is the same byte returned by the STATUS_BYTE command. The high byte of the word returned by the STATUS_WORD command provides a number of bits that can be used to determine which of the other status commands must be issued to obtain all active status bits. STATUS_INPUT Command The STATUS_INPUT command returns a number of bits relating to voltage warnings on the VIN pin as well as the overpower warning. STATUS_IOUT Command The STATUS_IOUT command returns a number of bits relating to current warnings on the monitoring rail. STATUS_MFR_SPECIFIC Command The STATUS_MFR_SPECIFIC command is a standard PMBus command, but the contents of the byte returned are specific to the ADM1293/ADM1294. It returns a number of bits relating to voltage warnings on the VAUX pin. Rev. B | Page 21 of 48 ADM1293/ADM1294 Data Sheet CLEAR_FAULTS Command The following quantities are then calculated: The CLEAR_FAULTS command clears warnings bits when they are set. Warning bits are latched when they are set. In this way, a host can read the bits any time after the warning condition occurs and determine which problem actually occurred. * * * If the CLEAR_FAULTS command is issued and the warning condition is no longer active, the status bit is cleared. If the condition is still active--for example, if the input voltage is below the undervoltage threshold of the VIN pin--the CLEAR_FAULTS command attempts to clear the status bit, but that status bit is immediately set again. GPOX AND ALERTx PIN SETUP COMMANDS Two multipurpose pins are provided on the ADM1293/ ADM1294: GPO1/ALERT1/CONV and GPO2/ALERT2. These pins can be configured over the PMBus in one of three output modes, as follows: * * * General-purpose digital output Output for generating an SMBALERT when one or more warning status bits become active in the PMBus status registers Digital comparator In digital comparator mode, the current, voltage, and power warning thresholds are compared to the values read or calculated by the ADM1293/ADM1294. The comparison result sets the output high or low according to whether the value is greater or less than the warning threshold that has been set. For an example of how to configure these pins to generate an SMBALERT and how to respond and clear the condition, see the Example Use of SMBus ARA section. ALERT1_CONFIG and ALERT2_CONFIG Commands Using combinations of bit masks, the ALERT1_CONFIG and ALERT2_CONFIG commands select the status bits that, when set, generate an SMBALERT signal to a processor, or control the digital comparator mode. The GPO1/ALERT1/CONV and GPO2/ALERT2 pins must be configured in SMBALERT or digital comparator mode in the DEVICE_CONFIG register. If configured in GPO mode, the pin is under software control. If this mode is set, the SMBALERT masking bits are ignored. POWER MONITOR COMMANDS The ADM1293/ADM1294 provide a high accuracy, 12-bit current, voltage, and power monitor. The power monitor can be configured in a number of different modes of operation and can run in either continuous mode or single shot mode with a number of different sample averaging options. The power monitor can measure the following quantities: * * * Input voltage (VIN) Output current (IOUT) Auxiliary input voltage (VAUX) Input power (PIN) Energy flow in forward direction (EIN) Energy flow in reverse direction (EOUT) PMON_CONFIG Command The power monitor can run in a number of different modes. The PMON_CONFIG command is used to set up the power monitor. The settings that can be configured are as follows: * * * * * * * Single shot or continuous sampling VIN/VAUX sampling enable/disable Current and voltage sample averaging Power sample averaging Simultaneous sampling enable/disable VIN monitoring range selection Current monitoring range selection Modifying the power monitor settings while the power monitor is sampling is not recommended. To ensure correct operation of the device and to avoid any potential spurious data or the generation of status alerts, stop the power monitor before changing any of these settings. PMON_CONTROL Command Power monitor sampling can be initiated via hardware or via software using the PMON_CONTROL command. This command can be used with single shot or continuous mode. READ_VIN, READ_VAUX, and READ_IOUT Commands The ADM1293/ADM1294 power monitor always measures the voltage developed across the sense resistor to provide a current measurement. ADM1293/ADM1294 supports bidirectional current monitoring and the data returned by the READ_IOUT command is expressed in twos complement format with the MSB indicating the direction of the current flow. A MSB of 0 indicates positive current flow (from the SENSEP pin to the SENSEN pin), and a MSB of 1 indicates reverse current flow (from the SENSEN pin to the SENSEP pin). The input voltage measurement from the SENSEP pin is also enabled by default. The auxiliary input voltage present on the VAUX pin is available if enabled with the PMON_CONFIG command. READ_PIN, READ_PIN_EXT, READ_EIN, and READ_EIN_EXT Commands The 12-bit VIN input voltage and 12-bit IOUT current measurement values are multiplied by the ADM1293/ADM1294 to give the input power value. This is accomplished by using fixed point arithmetic, and produces a 24-bit value. It is assumed that the numbers are in the 12.0 format, meaning that there is no fractional part. This 24-bit extended precision power value can be read from the ADM1293/ADM1294 using the READ_PIN_EXT command. Rev. B | Page 22 of 48 Data Sheet ADM1293/ADM1294 The 16 most significant bits of the 24-bit value can be read using the READ_PIN command. Similar to READ_IOUT, both the READ_PIN and the READ_PIN_EXT commands are expressed in twos complement format with the MSB indicating the direction of the power flow. READ_EIN, READ_EIN_EXT, READ_EOUT, and READ_EOUT_EXT Commands There are two sets of power accumulators inside the ADM1293/ADM1294 to support bidirectional energy metering function. The forward flowing power data (from the SENSEP pin to the SENSEN pin, with an MSB of 0) is accumulated in the READ_EIN register and the negative flowing power data (from the SENSEN pin to the SENSEP pin, with an MSB of 1) is accumulated in the READ_EOUT register. Each time a power calculation is performed, the 24-bit power value is added to a corresponding unsigned 24-bit energy accumulator register. Each time this energy accumulator register rolls over from 0xFFFFFF to 0x000000, a 16-bit rollover counter is incremented. The rollover counter is straight binary, with a maximum value of 0xFFFF before it rolls over. A 24-bit straight binary power sample counter is also incremented by 1 each time a power value is calculated and added to the energy accumulator. The READ_EIN_EXT and READ_EOUT_EXT commands return the full 24 bits of the energy accumulator, the full 16 bits of the rollover counter, and the full 24 bits of the sample counter. The use of the longer rollover counter means that the time interval between reads of the device can be increased from seconds to minutes, without losing any data. By disabling VIN sampling, a constant value of 1 is assigned to the VIN register. This allows IOUT data to be duplicated in the PIN register, as PIN = IOUT x 1 = IOUT and transforms the power accumulators to current accumulators/coulomb counters. READ_EIN and READ_EOUT Commands in the PMBus Standard The definition and implementation of the READ_EIN and READ_EOUT commands on the ADM1293/ADM1294 devices are slightly different from the ones described in the PMBus Standard. Pay special attention to the differences to avoid a calculation error. In terms of the definition, the READ_EIN and READ_EOUT commands described in the PMBus standard are used to return the accumulated power values entering and then exiting the PMBus device. Together they allow the host to calculate the power and energy consumption of the PMBus device. This is useful for devices with dynamic power loss such as a dc-to-dc converter. These registers can be read back either in standard data format by the READ_EIN and the READ_EOUT commands, or extended precision data format by the READ_EIN_EXT and the READ_EOUT_EXT commands, depending on the level of accuracy required for the energy accumulator and the desire to limit the frequency of reads from the ADM1293/ADM1294. As dedicated power monitors, the power consumption of the ADM1293/ADM1294 devices is fairly constant and generally very small compared to the power they are trying to monitor. Therefore, instead of monitoring their own power consumption, the READ_EIN and READ_EOUT commands on the ADM1293/ADM1294 are designed to return the accumulated bidirectional power data on the monitored supply rail. They allow the user to calculate the energy flow on the rail in both directions. A bus host can read these values, and by calculating the delta in the power accumulated, the delta in the number of samples, and the time delta since the last read, the host can calculate the average power since the last read, as well as the energy consumed since the last read. As for implementation, the power accumulation data described in the PMBus standard are expressed in signed, 16-bit, twos complement format. The rollover counter increases by 1 each time the energy accumulator register rolls over from 0x7FFF to 0x0000. The time delta is calculated by the bus host based on when it sends its commands to read from the device, and is not provided by the ADM1293/ADM1294. The power accumulators on the ADM1293/ADM1294 devices are defined to accumulate power in one specific direction. This removes the need for the sign bit and the power accumulation data on the ADM1293/ADM1294 devices is expressed as an unsigned 16-bit value. As a result, the rollover counter increases by 1 each time the energy accumulator register rolls over from 0xFFFF to 0x0000. To avoid data loss, the bus host must read at a rate that ensures the rollover counter does not wrap around more than once, and if the counter does wrap around, that the next value read for PIN is less than the previous one. The READ_EIN and READ_EOUT commands return the top 16 bits of the energy accumulator, the lower 8 bits of the rollover counter, and the full 24 bits of the sample counter. Rev. B | Page 23 of 48 ADM1293/ADM1294 Data Sheet PEAK_VIN, PEAK_VAUX, MIN_IOUT, MAX_IOUT, MIN_PIN, and MAX_PIN Commands VAUX_OV_WARN_LIMIT and VAUX_UV_WARN_LIMIT Commands In addition to the standard PMBus commands for reading voltage, current, and power, the ADM1293/ADM1294 provide commands that report the maximum peak voltage, the maximum and minimum current, and the power values recorded. The VAUX_OV_WARN_LIMIT and VAUX_UV_WARN_ LIMIT commands set the OV and UV thresholds on the output voltage, as measured at the VAUX pin. The ADM1293/ADM1294 devices support bidirectional current and power monitoring. Both current and power data are expressed in twos complement format with the MSB being the sign bit indicating the direction of the current/power flow. For current and power, the maximum values are defined as the most positive values recorded (flowing from the SENSEP pin to the SENSEN pin) or least negative values recorded (flowing from the SENSEN pin to the SENSEP pin), and the minimum values are defined as the most negative or least positive values recorded. For example, if the current readback ranges between 3 A and 5 A, the MAX_IOUT command returns 5 A and the MIN_IOUT command returns 3 A. If the current readback ranges between -3 A and -5 A, the MAX_IOUT command returns -3 A and the MIN_IOUT command returns -5 A. The IOUT_OC_WARN_LIMIT command sets the overcurrent threshold for the current flowing through the sense resistor. Theses peak values are updated only after the power monitor has sampled and averaged the current and voltage measurements. Individual peak values are cleared by writing a value of 0 with the corresponding command. WARNING LIMIT SETUP COMMANDS The ADM1293/ADM1294 power monitor can monitor a number of different warning conditions simultaneously and report any current, voltage, or power values that exceed the user defined thresholds using the status commands. All comparisons performed by the power monitor require the measured value to be strictly greater or less than the threshold value. At power-up, all threshold limits are set to either minimum scale (for undervoltage conditions) or to maximum scale (for overvoltage, overcurrent, or overpower conditions). This effectively disables the generation of any status warnings by default; warning bits are not set in the status registers until the user explicitly sets the threshold values. VIN_OV_WARN_LIMIT and VIN_UV_WARN_LIMIT Commands The VIN_OV_WARN_LIMIT and VIN_UV_WARN_LIMIT commands set the overvoltage (OV) and undervoltage (UV) thresholds on the input voltage, as measured at the VIN pin. IOUT_OC_WARN_LIMIT Command If the threshold is a positive value, a more positive current measurement value is required to trigger the overcurrent warning. If the threshold is a negative value, a more negative current measurement value is required to trigger the overcurrent warning. PIN_OP_WARN_LIMIT Command The PIN_OP_WARN_LIMIT command sets the overpower threshold for the power that appears on the rail being monitored. If the threshold is a positive value, a more positive power measurement value is required to trigger the overpower warning. If the threshold is a negative value, a more negative power measurement value is required to trigger the overpower warning. PMBus DIRECT FORMAT CONVERSION The ADM1293/ADM1294 uses the PMBus direct format to represent real-world quantities such as voltage, current, and power values. A direct format number takes the form of a 2-byte, twos complement, binary integer value. It is possible to convert between direct format value and realworld quantities using the following equations. Equation 1 converts from real-world quantities to PMBus direct values, and Equation 2 converts PMBus direct format values to real-world values. Y = (mX + b) x 10R (1) X = 1/m x (Y x 10 - b) (2) -R where: Y is the value in PMBus direct format. X is the real-world value. m is the slope coefficient, a 2-byte, twos complement integer. b is the offset, a 2-byte, twos complement integer. R is a scaling exponent, a 1-byte, twos complement integer. The same equations are used for voltage, current, and power conversions (with the exception of accumulated power conversion), the only difference being the values of the m, b, and R coefficients that are used. Table 10 lists all the coefficients required for the ADM1293/ADM1294. The current and power coefficients shown are dependent on the value of the external sense resistor used in a given application. This means that an additional calculation must be performed to take the sense resistor value into account to obtain the coefficients for a specific sense resistor value. Rev. B | Page 24 of 48 Data Sheet ADM1293/ADM1294 Table 10. PMBus Conversion to Real-World Coefficients Coefficients Voltage (V) Current (A) Power (W) 1 2 Voltage Range (V)1 0 to 1.2 0 to 7.4 0 to 21 N/A N/A N/A N/A 0 to 1.2 0 to 1.2 0 to 1.2 0 to 1.2 0 to 7.4 0 to 7.4 0 to 7.4 0 to 7.4 0 to 21 0 to 21 0 to 21 0 to 21 Current Sense Range (mV)1 N/A N/A N/A 25 50 100 200 25 50 100 200 25 50 100 200 25 50 100 200 m2 3333 5552 19,604 8000 x RSENSE 4000 x RSENSE 20,000 x RSENSE 10,000 x RSENSE 10,417 x RSENSE 5208 x RSENSE 26,042 x RSENSE 13,021 x RSENSE 17,351 x RSENSE 8676 x RSENSE 4338 x RSENSE 21,689 x RSENSE 6126 x RSENSE 30,631 x RSENSE 15,316 x RSENSE 7658 x RSENSE b -1 -5 -50 -100 -100 -1000 -1000 0 0 0 0 0 0 0 0 0 0 0 0 R 0 -1 -2 -2 -2 -3 -3 -1 -1 -2 -2 -2 -2 -2 -3 -2 -3 -3 -3 N/A means not applicable. The sense resistor value, used in the calculations to obtain the coefficients, is expressed in milliohms. The sense resistor value used in the calculations to obtain the coefficients is expressed in milliohms. The m coefficients are defined as 2-byte twos complement numbers in the PMBus standard; therefore, the maximum positive value that can be represented is 32,767. If the m value is greater than that, and is to be stored in PMBus standard form, then divide the m coefficients by 10, and increase the R coefficient by a value of 1. For example, if a 10 m sense resistor is used, the m coefficient for power is 6123, and the R coefficient is -1. Example 1: IOUT_OC_WARN_LIMIT requires a current-limit value expressed in direct format. Assume the current sense range is 25 mV. If the required current limit is 10 A and the sense resistor is 2 m, the first step is to determine the voltage coefficient. This is m = 8000 x 2, giving 16,000. Using Equation 1, and expressing X in units of amperes, Y = ((16,000 x 10) -100) x 10-2 Y = -1601 = (signed 16 bits) 0xF9BF? = (unsigned) 63935d Writing a value of 63935d with the IOUT_OC_WARN_LIMIT command sets an overcurrent warning at -10 A. Example 3: the READ_IOUT command returns a direct format value of 125, representing the current flowing through a sense resistor of 1 m. The current sense range is 50 mV. To convert this value to the current flowing, use Equation 2, with m = 4000 x 1. X = 1/4000 x (125 x 102 + 100) X = 3.15 A This means that when READ_IOUT returns a value of 125, 3.15 A is flowing in the sense resistor. A positive values means the current is flowing in the forward direction from the SENSEP pin to the SENSEN pin. Example 4: the READ_PIN command returns a direct format value of 12,635, representing the power measured through a sense resistor of 0.25 m. The voltage range is 0 V to 21 V and the current sense range is 0 mV to 25 mV. Y = 1599 Writing a value of 1599 with the IOUT_OC_WARN_LIMIT command sets an overcurrent warning at 10 A. Example 2: IOUT_OC_WARN_LIMIT requires a current-limit value expressed in direct format. Assume the current sense range is 25 mV. If the required current limit is -10 A and the sense resistor is 2 m, the first step is to determine the voltage coefficient. This is m = 8000 x 2, giving 16,000. Using Equation 1, and expressing X in units of amperes, Y = ((16,000 x -10) -100) x 10-2 To convert this value to the current flowing, use Equation 2, with m = 6126 x 0.25 = 1531.5 X = 1/1531.5 x (12635 x 102 - 0) X = 825 W This means that, when READ_PIN returns a value of 12,635, 825 W is being delivered on the rail. Rev. B | Page 25 of 48 ADM1293/ADM1294 Data Sheet Note that the READ_PIN_EXT command returns the 24-bit extended precision versions of the 16-bit values returned by the READ_PIN command. The direct format values must be divided by 256 before being converted with the coefficients shown in Table 10. ENERGY METER VALUE CONVERSION On the ADM1293 and ADM1294, the accumulated power value in the energy metering registers is stored as an unsigned integer. The total energy accumulated can be derived by treating the rollover count value as the most significant extension to the power accumulator value. Example 1: The READ_EIN command has been issued to an ADM1293 or ADM1294 device twice by a processor with 1000 ms in between reads. The data returned from the first read is * * * SAMPLE_COUNT: 0x00602C EIN_ROLLOVER_COUNT: 0xF8 EIN_ENERGY_COUNT: 0x2FDC Start by determining the total power accumulated in the energy meter register at each read. By treating the rollover count value as the most significant extension to the power accumulator value, the total power accumulated at the first read is 0x1A02FE. Similarly, the total power accumulated at the second read is 0xF82FDC. The power delta between the two reads is 0xF82FDC - 0x1A02FE = 0xDE2CDE * * * The data returned from the second read is * * * Total Power = RolloverCount x MaximumEnergyCount + EnergyCount Where the maximum energy count is the maximum value of the energy count register before roll over happens. And for the ADM1293-2 and ADM1294-2, the maximum energy count is 0x7FFF. The total power accumulated at the time of the first read is 0x1A x 0x7FFF + 0x02FE = 0xD02E4 The total power accumulated at the time of the second read is 0xF8 x 0x7FFF + 0x2FDC = 0x7C2EE4 The power delta between the two reads is 0x00602C - 0x004000 = 0x202C The average power per sample between the two reads is The average power per sample between the two reads is 0xDE2CDE0x202C = 0x6E7 = 1767d To convert this to a real-world value, the first step is to determine the m coefficient, that is, m = 6126 x 0.25 = 1531.5. 0x6F2C00 / 0x202C = 0x374 = 884d To convert this to a real-world value, the first step is to determine the m coefficient, that is, m = 6126 x 0.25 = 1531.5. Using Equation 2 X = 1/1531.5 x (884 x 102 - 0) X = 115.38 W Energy = 115.38 W x 1 sec = 115.38 J SAMPLE_COUNT: 0x00602C EIN_ROLLOVER_COUNT: 0xF8 EIN_ENERGY_COUNT: 0x2FDC And the sample count delta is 0x00602C - 0x004000 = 0x202C The energy consumed between the two reads is equal to the average power by time. SAMPLE_COUNT: 0x004000 EIN_ROLLOVER_COUNT: 0x1A EIN_ENERGY_COUNT: 0x02FE 0x7C2EE4 - 0xD02E4 = 0x6F2C00 And the sample count delta is X = 1/1531.5 x (1767 x 102 - 0) The data returned from the first read is Start by determining the total power accumulated in the energy meter register at each read. The sense resistor is 0.25 m, the voltage range is 0 V to 21 V, and the current sense range is 0 mV to 25 mV. Assuming the rollover counter did not roll over between the two reads, the processor is required to determine the energy consumption on the rail being monitored during this time. Using Equation 2 Example 2: The READ_EIN command has been issued to an ADM1293-2 or ADM1294-2 device twice by a processor with 1000 ms in between reads. The sense resistor is 0.25 m, the voltage range is 0 V to 21 V, and the current sense range is 0 mV to 25 mV. Assuming the rollover counter did not roll over between the two reads, the processor is required to determine the energy consumption on the rail being monitored during this time. SAMPLE_COUNT: 0x004000 EIN_ROLLOVER_COUNT: 0x1A EIN_ENERGY_COUNT: 0x02FE The data returned from the second read is * * * On the ADM1293-2 and ADM1294-2, the accumulated power value in the energy metering registers is presented in twos complement format as defined in the PMBus standard. X = 57.72 W The energy consumed between the two reads is equal to the average power by time. Energy = 57.72 W x 1 sec = 57.72 J Rev. B | Page 26 of 48 Data Sheet ADM1293/ADM1294 ENERGY METER VALUE TO PMBus STANDARD DATA CONVERSION with the exact LSB values, somewhat more accurate numerical conversions can be provided. Although the energy meter function on the ADM1293-1/ ADM1294-1 devices is implemented differently to the PMBus standard, some simple data preprocessing steps can be added to the processor firmware if the user wants to use the same software code written for the PMBus standard EIN_READ and EOUT_READ commands with the ADM1293-1/ADM1294-1 devices. The two data preprocessing steps are To convert an ADC code to current in amperes, use the following formulas: 1. 2. Treating ENERGY_COUNT as an unsigned integer. Multiply ROLLOVER_COUNT by 2. VOLTAGE AND CURRENT CONVERSION USING LSB VALUES The direct format voltage and current values returned by the READ_VIN, READ_VAUX, and READ_IOUT commands and the corresponding peak versions are the data output directly by the ADM1293/ADM1294 ADCs. Because the voltages and currents are 12-bit ADC output codes, they can also be converted to real-world values when there is knowledge of the size of the LSB on the ADC. The m, b, and R coefficients defined for the PMBus conversion are required to be whole integers by the standard and have, therefore, been rounded slightly. Using this alternative method, V SENSE = LSB CURRENT x ( I I OUT = ADC + 1) V SENSE R SENSE where: VSENSE = VSENSEP - VSENSEN. LSBCURRENT is the size of the current sense voltage LSB for a given current sense range. IADC is the 12-bit ADC code. IOUT is the measured current value in amperes. RSENSE is the value of the sense resistor in ohms. To convert an ADC code to a voltage, use the following formula: V M = LSB VOLTAGE x (V ADC + 0.5 ) where: VM is the measured value in volts. LSBVOLTAGE is the size of the voltage sensing LSB for a given input voltage range. VADC is the 12-bit ADC code. Table 11. LSB Values LSB Type LSB Voltage (mV) LSB Current Sensing (V) 1 Voltage Range (V)1 0 to 1.2 0 to 7.4 0 to 21 N/A N/A N/A N/A Current Sense Range (mV)1 N/A N/A N/A 25 50 100 200 N/A means not applicable. Rev. B | Page 27 of 48 LSB Value 0.3 1.801 5.101 12.5 25 50 100 ADM1293/ADM1294 Data Sheet ALERTx PIN BEHAVIOR WARNINGS HANDLING/CLEARING AN ALERT The sources of a warning are defined as follows: When warnings are configured on the GPO1/ALERT1/CONV or GPO2/ALERT2 pins, the pin becomes active to signal an interrupt to the processor. The pin is active low, unless inversion is enabled. The GPO1/ALERT1/CONV or GPO2/ALERT2 signal performs the functions of an SMBALERT. * * * * * * * * CML, a communications error occurred on the I2C bus IOUT OC warning from the ADC VIN UV warning from the ADC VIN OV warning from the ADC VAUX UV warning from the ADC VAUX OV warning from the ADC PIN overpower (OP) warning from the VIN x IOUT calculation Hysteretic output warning from the ADC Note that the GPO1/ALERT1/CONV and GPO2/ALERT2 pins can become active independently but they are always made inactive together. A processor can respond to the interrupt in one of two ways. * A value of 1 in a status register bit field always indicates a warning condition. Warning bits in the status registers are latched when set to 1. Use the CLEAR_FAULTS command to clear a latched bit to 0. GENERATING AN ALERT A host device can periodically poll the ADM1293/ADM1294 using the status commands to determine whether a warning is active. However, this polling is very inefficient in terms of software and processor resources. The ADM1293/ADM1294 have two output pins (GPO1/ALERT1/CONV and GPO2/ALERT2) that can be used to generate interrupts to a host processor. By default at power-up, the open-drain GPO1/ALERT1/CONV and GPO2/ALERT2 outputs are high impedance; therefore, the pins can be pulled high through a resistor. The GPO1/ALERT1/ CONV and GPO2/ALERT2 pins are disabled by default on the ADM1293/ADM1294. Any one or more of the warnings listed in the Warnings section can be enabled and cause an alert, making the corresponding GPO1/ALERT1/CONV or GPO2/ALERT2 pin active. By default, the active state of the GPO1/ALERT1/CONV and GPO2/ALERT2 pins are low. For example, to use GPO2/ALERT2 to monitor the VAUX UV warning from the ADC, the followings steps must be performed: 3. 4. 5. Set a threshold level with the VAUX_UV_WARN_LIMIT command. Set the VAUX_UV_WARN_EN2 bit in the ALERT2_CONFIG register. Start the power monitor sampling on VAUX. Ensure the power monitor is configured to sample VAUX in the PMON_CONFIG register. * If only one device is on the bus, the processor can read the status bytes and issue a CLEAR_FAULTS command to clear all the status bits, which causes the deassertion of the GPO1/ALERT1/CONV or GPO2/ALERT2 line. If the cause of the SMBALERT is a power monitor generated warning and that warning persists, providing the power monitor is running continuously, the next sample generates a new SMBALERT after the CLEAR_FAULTS command is issued. If there are several devices on the bus, the processor can issue an SMBus alert response address (ARA) command to find out which device asserted the SMBALERT line. The processor can read the status bytes from that device and issue a CLEAR_FAULTS command. SMBus ALERT RESPONSE ADDRESS (ARA) The SMBus ARA is a special address that is used by the bus host to locate any devices that need to communicate with the bus host. A host typically uses a hardware interrupt pin to monitor the SMBus alert pins of multiple devices. When the host interrupt occurs, the host issues a message on the bus using the SMBus receive byte or receive byte with PEC protocol. The special address used by the host is 0x0C. Any devices that have an SMBALERT signal return their own 7-bit address as the seven MSBs of the data byte. The LSB value is not used and can be either 1 or 0. The host reads the device address from the received data byte and proceeds to handle the alert condition. More than one device may have an active SMBALERT signal and attempt to communicate with the host. In this case, the device with the lowest address dominates the bus and succeeds in transmitting its address to the host. The device that succeeds disables its SMBus alert signal. If the host sees that the SMBus alert signal is still low, it continues to read addresses until all devices that need to communicate have successfully transmitted their addresses. If a VAUX sample is taken that is below the configured VAUX UV value, the GPO2/ALERT2 pin is pulled low, signaling an interrupt to a processor. Rev. B | Page 28 of 48 Data Sheet ADM1293/ADM1294 EXAMPLE USE OF SMBus ARA DIGITAL COMPARATOR MODE The full sequence of steps that occurs when an SMBALERT is generated and cleared is as follows: The GPO1/ALERT1/CONV and GPO2/ALERT2 pins can be configured to indicate if a user defined threshold for voltage, current, or power is being exceeded. In this mode, the output pin is live and is not latched when a warning threshold is exceeded. In effect, the pin acts as a digital comparator, where the threshold is set using the warning limit threshold commands. 1. 2. 3. 4. 5. 6. A warning is enabled using the ALERT2_CONFIG command, and the corresponding status bit for the warning changes from 0 to 1, indicating that the warning has recently become active. The GPO2/ALERT2 pin becomes active (set low) to signal that an SMBALERT is active. The host processor issues an SMBus ARA command to determine which device has an active alert. If there are no other active alerts from devices with lower I2C addresses, this device makes the GPO2/ALERT2 pin inactive (set high) during the no acknowledge bit period after it sends its address to the host processor. If the GPO2/ALERT2 pin stays low, the host processor must continue to issue SMBus ARA commands to devices to determine the addresses of all devices whose status it must check. The ADM1293/ADM1294 continue to operate with the GPO2/ALERT2 pin inactive and the contents of the status bytes unchanged until the host reads the status bytes and clears them, or until a new fault occurs. That is, if a status bit for a fault or warning that is enabled on the GPO2/ALERT2 pin and that was not already active (equal to 1) changes from 0 to 1, a new alert is generated, causing the GPO2/ALERT2 pin to become active again. The ALERTx_CONFIG command is used, similar to the SMBALERT configuration, to select the specific warning threshold to be monitored. The GPO1/ALERT1/CONV or GPO2/ALERT2 pin then indicates if the measured value is above or below the threshold. Rev. B | Page 29 of 48 ADM1293/ADM1294 Data Sheet APPLICATION DIAGRAMS The multifunction pins can be configured to indicate status warnings generated by the ADM1293 either to the microprocessor or directly to the user by driving a LED. These pins can also be configured as an ADC conversion signal input to allow synchronized voltage and current sampling across the system. Figure 39 shows an example application circuit of the ADM1293. With different address pin configurations, up to 16 ADM1293 devices can share the same I2C bus and are controlled by the same bus master. Each device can be used to monitor a supply rail with a voltage ranging from 0 V to 20 V and report voltage, current, power, and energy consumption. Each device can also monitor one additional node on the system using the VAUX input and report the voltage value present on the node. 1V LOAD SENSEP SENSEN VIN 3.3V GPO2/ALERT21 VCC GPO1/ALERT1/CONV2 VCAP ADM1293 SDAO SDA SCL VAUX ADR0 ADR1 GND x16 12V LOAD SENSEP SENSEN VIN GPO2/ALERT21 VCC GPO1/ALERT1/CONV2 VCAP 2.5V ADM1293 MICROPROCESSOR SDAO SDA SCL ADR0 ADR1 GND I V P E 1ALERT2 IS THE ACTIVE PIN FUNCTION IN THIS SETUP. 2CONV IS THE ACTIVE PIN FUNCTION IN THIS SETUP. Figure 39. ADM1293 Typical Application Diagram Rev. B | Page 30 of 48 11891-039 VAUX Data Sheet ADM1293/ADM1294 powered directly from a wide range of supply voltages. The ADM3260 I2C and power isolator are used with another ADM1294. The I2C and power isolator not only greatly simplifies the cross isolation communication design, but also can be used to provide power to the ADM1294 and other circuits on the primary side. Figure 40 shows an example application circuit of the ADM1294. Two of the devices shown are used to monitor a 300 V supply rail and a -48 V supply rail. Both of the devices communicate with the master device across an isolation barrier. Separated SDA lines make it easy to set up the bidirectional communication across the isolation barrier with optocouplers. The internal shunt regulator allows the ADM1294 to be 300V ISOLATED DC-TO-DC 3.3V ISO VSHUNT ADR0 ADR1 GPO21/ALERT2 EN GPO1/ALERT12/CONV 3.3V ISO VIN VAUX ADM1294 3.3V ISO 3.3V ISO 3.3V SDAO SDAI RTD SDAI VCAP SCL VEE ADM3260 SCL SENSEP SENSEN x16 -48V RTN ISOLATED DC-TO-DC -48V VSHUNT ADR0 ADR1 -48V GPO2/ALERT23 VIN 5V GPO1/ALERT1/CONV4 ADM1294 VAUX OPTOCOUPLERS BIDIRECTONAL BUS BUFFERS SDAO SDAI VCAP SCL VEE SENSEN SENSEP 1GPO2 IS THE ACTIVE PIN FUNCTION IN THIS SETUP. 2ALERT1 IS THE ACTIVE PIN FUNCTION IN THIS SETUP. 3ALERT2 IS THE ACTIVE PIN FUNCTION IN THIS SETUP. 4CONV IS THE ACTIVE PIN FUNCTION IN THIS SETUP. Figure 40. ADM1294 Typical Application Diagram Rev. B | Page 31 of 48 11891-040 -48V ADM1293/ADM1294 Data Sheet PMBus COMMAND REFERENCE Register addresses are in hexadecimal format. Table 12. PMBus Commands Summary Address 0x03 0x19 0x4A 0x57 0x58 0x6B 0x78 0x79 0x7B 0x7C 0x80 0x86 0x87 0x88 0x8C 0x97 0x98 0x99 0x9A 0x9B 0xD0 0xD1 0xD2 0xD3 0xD4 0xD5 0xD6 0xD8 0xDA 0xDB 0xDC 0xDD 0xDE 0xDF 0xE3 0xE4 0xE5 0xF2 0xF3 0xF4 Name CLEAR_FAULTS CAPABILITY IOUT_OC_WARN_LIMIT VIN_OV_WARN_LIMIT VIN_UV_WARN_LIMIT PIN_OP_WARN_LIMIT STATUS_BYTE STATUS_WORD STATUS_IOUT STATUS_INPUT STATUS_MFR_SPECIFIC READ_EIN READ_EOUT READ_VIN READ_IOUT READ_PIN PMBUS_REVISION MFR_ID MFR_MODEL MFR_REVISION MAX_IOUT PEAK_VIN PEAK_VAUX PMON_CONTROL PMON_CONFIG ALERT1_CONFIG ALERT2_CONFIG DEVICE_CONFIG MAX_PIN READ_PIN_EXT READ_EIN_EXT READ_VAUX VAUX_OV_WARN_LIMIT VAUX_UV_WARN_LIMIT MIN_IOUT MIN_PIN READ_EOUT_EXT HYSTERESIS_LOW HYSTERESIS_HIGH STATUS_HYSTERESIS Description Clear faults PMBus capability IOUT OC warning limit VIN OV warning limit VIN UV warning limit PIN OP warning limit Status byte Status word IOUT status Input status Manufacturer specific status Read EIN Read EOUT Read VIN Read IOUT Read PIN PMBus revision Manufacturer ID Manufacturer model Manufacturer revision Maximum IOUT Peak VIN Peak VAUX Power monitor control Power monitor configuration Alert 1 configuration Alert 2 configuration Device configuration Maximum PIN Read PIN (extended) Read EIN (extended) Read VAUX VAUX OV warning limit VAUX UV warning limit Minimum IOUT Minimum PIN Read EOUT (extended) Hysteresis low threshold level Hysteresis high threshold level Hysteresis status Rev. B | Page 32 of 48 Reset Not applicable 0xB0 0x07FF 0x0FFF 0x0000 0x7FFF 0x00 0x0000 0x00 0x00 0x00 0x000000000000 0x000000000000 0x0000 0x0000 0x0000 0x22 0x494441 0x32 0xF800 0x0000 0x0000 0x01 0x0714 0x0000 0x0000 0x0000 0x8000 0x000000 0x0000000000000000 0x0000 0x0FFF 0x0000 0x7FF 0x7FFF 0x0000000000000000 0x8000 0x7FFF 0x00 RW W R RW RW RW RW R R R R R R R R R R R R R R R R R RW RW RW RW RW R R R R RW RW R R R RW RW R Data Sheet ADM1293/ADM1294 PMBus COMMAND DESCRIPTIONS CLEAR FAULTS REGISTER Address: 0x03, Reset: 0x, Name: CLEAR_FAULTS The CLEAR_FAULTS command clears fault and warning bits in all the status registers. All faults and warnings are cleared, but may be asserted again if it remains active following the next power monitor conversion cycle or bus communication. This command does not require any data. PMBus CAPABILITY REGISTER Address: 0x19, Reset: 0xB0, Name: CAPABILITY The CAPABILITY command allows the host system to determine the SMBus interface capabilities of the device. Table 13. Bit Descriptions for CAPABILITY Bits 7 Bit Name PEC_SUPPORT [6:5] MAX_BUS_SPEED Settings 1 01 4 SMBALERT_SUPPORT 1 [3:0] RESERVED Description Packet error correction (PEC) support. Always reads as 1. PEC is supported. Maximum bus interface speed. Always reads as 01. Maximum supported bus speed is 400 kHz. SMBALERT support. Always reads as 1. Device supports SMBALERT and the alert response address (ARA). Always reads as 0000b. Reset 0x1 Access R 0x1 R 0x1 R 0x0 Reserved IOUT OC WARNING LIMIT REGISTER Address: 0x4A, Reset: 0x07FF, Name: IOUT_OC_WARN_LIMIT The IOUT_OC_WARN_LIMIT command sets the overcurrent warning limit for the current measured between the SENSEP and the SENSEN pins. If the warning limit is a positive number, an overcurrent condition is triggered by a more positive current readback. If the warning limit is a negative number, an overcurrent condition is triggered by a more negative current readback. Table 14. Bit Descriptions for IOUT_OC_WARN_LIMIT Bits [15:12] [11:0] Bit Name RESERVED IOUT_OC_WARN_LIMIT Settings Description Always reads as 0000b. Overcurrent warning threshold for the IOUT measurement, expressed in direct format. Set to default value to disable. Reset 0x0 0x7FF Access Reserved RW Reset 0x0 0xFFF Access Reserved RW VIN OV WARNING LIMIT REGISTER Address: 0x57, Reset: 0x0FFF, Name: VIN_OV_WARN_LIMIT The VIN_OV_WARN_LIMIT command sets the overvoltage warning limit for the voltage measured on the VIN pin. Table 15. Bit Descriptions for VIN_OV_WARN_LIMIT Bits [15:12] [11:0] Bit Name RESERVED VIN_OV_WARN_LIMIT Settings Description Always reads as 0000b. Overvoltage warning threshold for the VIN pin measurement, expressed in direct format. Set these bits to the default value to disable. Rev. B | Page 33 of 48 ADM1293/ADM1294 Data Sheet VIN UV WARNING LIMIT REGISTER Address: 0x58, Reset: 0x0000, Name: VIN_UV_WARN_LIMIT The VIN_UV_WARN_LIMIT command sets the undervoltage warning limit for the voltage measured on the VIN pin. Table 16. Bit Descriptions for VIN_UV_WARN_LIMIT Bits [15:12] [11:0] Bit Name RESERVED VIN_UV_WARN_LIMIT Settings Description Always reads as 0000b. Undervoltage warning threshold for the VIN pin measurement, expressed in direct format. Set these bits to the default value to disable. Reset 0x0 0x000 Access Reserved RW PIN OP WARNING LIMIT REGISTER Address: 0x6B, Reset: 0x7FFF, Name: PIN_OP_WARN_LIMIT The PIN_OP_WARN_LIMIT command sets the overpower warning limit for the calculated power value. If the warning limit is a positive number, an overpower condition is triggered by a more positive power readback. If the warning limit is a negative number, an overpower condition is triggered by a more negative power readback. Table 17. Bit Descriptions for PIN_OP_WARN_LIMIT Bits [15:0] Bit Name PIN_OP_WARN_LIMIT Settings Description Overpower warning threshold for the calculated power, expressed in direct format. Set these bits to the default value to disable. Reset 0x7FFF Access RW STATUS BYTE REGISTER Address: 0x78, Reset: 0x00, Name: STATUS_BYTE The STATUS_BYTE command provides status information for communication fault and certain top level status commands in the device. This is also the lower byte returned by STATUS_WORD. A bit set to 1 indicates a fault or warning has occurred. Table 18. Bit Descriptions for STATUS_BYTE Bits [7:2] 1 Bit Name RESERVED CML_FAULT Settings 0 1 0 NONEABOVE_STATUS 0 1 Description Always reads as 000000b. Communication fault. This bit is latched. No communications error detected on the I2C/PMBus interface. An error was detected on the I2C/PMBus interface. Errors detected are unsupported command, invalid PEC byte, and incorrectly structured message. None of the above. This bit is live. No other active status bit reported by any other status command. Active status bits are waiting to be read by one or more status commands. Reset 0x00 0x0 Access Reserved R 0x0 R STATUS WORD REGISTER Address: 0x79, Reset: 0x0000, Name: STATUS_WORD The STATUS_WORD command provides status information for communication faults and all top level status commands in the device. The lower byte is also returned by STATUS_BYTE. Table 19. Bit Descriptions for STATUS_WORD Bits 15 14 Bit Name RESERVED IOUT_STATUS Settings 0 1 Description Always reads as 0. IOUT warning. This bit is live. There are no active status bits to be read by STATUS_IOUT. There are one or more active status bits to be read by STATUS_IOUT. Rev. B | Page 34 of 48 Reset 0x0 0x0 Access Reserved R Data Sheet Bits 13 ADM1293/ADM1294 Bit Name INPUT_STATUS Settings 0 1 12 MFR_STATUS 0 1 [11:8] [7:2] 1 0 RESERVED RESERVED CML_FAULT NONEABOVE_STATUS Description Input warning. This bit is live. There are no active status bits to be read by STATUS_INPUT. There are one or more active status bits to be read by STATUS_INPUT. Manufacturer specific warnings. This bit is live. There are no active status bits to be read by STATUS_MFR_SPECIFIC. There are one or more active status bits to be read by STATUS_MFR_SPECIFIC. Always reads as 0000b. Duplicate of corresponding bit in STATUS_BYTE. Duplicate of corresponding bit in STATUS_BYTE. Duplicate of corresponding bit in STATUS_BYTE. Reset 0x0 Access R 0x0 R 0x0 0x00 0x0 0x0 Reserved Reserved R R IOUT STATUS REGISTER Address: 0x7B, Reset: 0x00, Name: STATUS_IOUT The STATUS_IOUT command provides status information for warnings related to the IOUT current being monitored. Table 20. Bit Descriptions for STATUS_IOUT Bits [7:6] 5 Bit Name RESERVED IOUT_OC_WARN Settings 0 1 [4:0] RESERVED Description Always reads as 00b. IOUT overcurrent warning. No overcurrent condition on the output supply was detected by the power monitor using the IOUT_OC_WARN_LIMIT command. An overcurrent condition was detected by the power monitor using the IOUT_OC_WARN_LIMIT command. This bit is latched. Always reads as 00000b. Reset 0x0 0x0 Access Reserved R 0x00 Reserved Reset 0x0 0x0 Access Reserved R 0x0 R 0x0 0x0 Reserved R INPUT STATUS REGISTER Address: 0x7C, Reset: 0x00, Name: STATUS_INPUT The STATUS_INPUT command provides status information for warnings related to VIN and PIN. Table 21. Bit Descriptions for STATUS_INPUT Bits 7 6 Bit Name RESERVED VIN_OV_WARN Settings 0 1 5 VIN_UV_WARN 0 1 [4:1] 0 RESERVED PIN_OP_WARN 0 1 Description Always reads as 0. VIN overvoltage warning. No overvoltage condition on the VIN pin was detected by the power monitor using the VIN_OV_WARN_LIMIT command. An overvoltage condition on the VIN pin was detected by the power monitor using the VIN_OV_WARN_LIMIT command. This bit is latched. VIN undervoltage warning. No undervoltage condition on the VIN pin was detected by the power monitor using the VIN_UV_WARN_LIMIT command. An undervoltage condition on the VIN pin was detected by the power monitor using the VIN_UV_WARN_LIMIT command. This bit is latched. Always reads as 0000b. PIN overpower warning. No overpower condition on the input supply detected by the power monitor using the PIN_OP_WARN_LIMIT command. An overpower condition on the input supply was detected by the power monitor using the PIN_OP_WARN_LIMIT command. This bit is latched. Rev. B | Page 35 of 48 ADM1293/ADM1294 Data Sheet MANUFACTURER SPECIFIC STATUS REGISTER Address: 0x80, Reset: 0x00, Name: STATUS_MFR_SPECIFIC The STATUS_MFR_SPECIFIC command provides status information for manufacturer specific faults and warnings. Table 22. Bit Descriptions for STATUS_MFR_SPECIFIC Bits 7 6 Bit Name RESERVED VAUX_OV_WARN Settings 0 1 5 VAUX_UV_WARN 0 1 [4:0] RESERVED Description Always reads as 0. VAUX overvoltage warning. No overvoltage condition was detected on the VAUX pin by the power monitor using the VAUX_OV_WARN_LIMIT command. An overvoltage condition was detected on the VAUX pin by the power monitor using the VAUX_OV_WARN_LIMIT command. This bit is latched. VAUX undervoltage warning. No undervoltage condition was detected on the VAUX pin by the power monitor using the VAUX_UV_WARN_LIMIT command. An undervoltage condition was detected on the VAUX pin by the power monitor using the VAUX_UV_WARN_LIMIT command. This bit is latched. Always reads as 00000b. Reset 0x0 0x0 Access Reserved R 0x0 R 0x00 Reserved READ EIN REGISTER Address: 0x86, Reset: 0x000000000000, Name: READ_EIN The READ_EIN command reads the forward flow energy meter registers in a single operation to ensure time consistent data. READ_EIN accumulates power data when IOUT is positive. Table 23. Bit Descriptions for READ_EIN Bits [47:24] Bit Name SAMPLE_COUNT [23:16] EIN_ROLLOVER_COUNT [15:0] EIN_ENERGY_COUNT Settings Description This is the total number of PIN samples acquired and accumulated in both the forward flow and reverse flow energy count accumulator. Byte 5 is the high byte, Byte 4 is the middle byte, and Byte 3 is the low byte. Number of times that the forward flow energy count has rolled over. On the ADM1293-1 and ADM1294-1, the rollover counter increases by 1 each time the energy count rolls over from 0xFFFF to 0x0000. On the ADM1293-2 and ADM1294-2, the rollover counter increases by 1 each time the energy count rolls over from 0x7FFF to 0x0000. This is an unsigned 8-bit binary value. Forward flow energy accumulator value in direct format. Byte 1 is the high byte, and Byte 0 is the low byte. On the ADM1293-1 and ADM1294-1 devices, the data is presented as unsigned integer. On the ADM1293-2 and ADM1294-2 devices, the data is presented in twos complement format. Internally, the energy accumulator is a 24-bit value, but only the most significant 16 bits are returned with this command. Use the READ_EIN_EXT to access the nontruncated version. Rev. B | Page 36 of 48 Reset 0x000000 Access R 0x00 R 0x0000 R Data Sheet ADM1293/ADM1294 READ EOUT REGISTER Address: 0x87, Reset: 0x000000000000, Name: READ_EOUT The READ_EOUT command reads the reverse flow energy meter registers in a single operation to ensure time consistent data. READ_EOUT accumulates power data when IOUT is negative. Table 24. Bit Descriptions for READ_EOUT Bits [47:24] [23:16] Bit Name SAMPLE_COUNT EOUT_ROLLOVER_COUNT [15:0] EOUT_ENERGY_COUNT Settings Description Duplicate of corresponding bit in READ_EIN. Number of times that the reverse flow energy count has rolled over. On the ADM1293-1 and the ADM1294-1, the rollover counter increases by 1 each time the energy count rolls over from 0xFFFF to 0x0000. On the ADM1293-2 and the ADM1294-2, the rollover counter increases by 1 each time the energy count rolls over from 0x7FFF to 0x0000. This is an unsigned 8-bit binary value. Reverse flow energy accumulator value in direct format. Byte 1 is the high byte, and Byte 0 is the low byte. On the ADM1293-1 and ADM1294-1, the data is presented as unsigned integer. On the ADM1293-2 and ADM1294-2, the data is presented in twos complement format. Internally, the energy accumulator is a 24-bit value, but only the most significant 16 bits are returned with this command. Use the READ_EOUT_EXT to access the nontruncated version. Reset 0x000000 0x00 Access R R 0x0000 R READ VIN REGISTER Address: 0x88, Reset: 0x0000, Name: READ_VIN The READ_VIN command reads the input voltage, VIN, from the device. Table 25. Bit Descriptions for READ_VIN Bits [15:12] [11:0] Bit Name RESERVED READ_VIN Settings Description Always reads as 0000b. Voltage measurement on the VIN pin after averaging, expressed in direct format. Reset 0x0 0x000 Access Reserved R READ IOUT REGISTER Address: 0x8C, Reset: 0x0000, Name: READ_IOUT The READ_IOUT command reads the output current, IOUT, from the device. Table 26. Bit Descriptions for READ_IOUT Bits [15:0] Bit Name READ_IOUT Settings Description Current measurement derived from differential voltage between the SENSEP and SENSEN pins, after averaging, expressed in direct format. Reset 0x0000 Access R Reset 0x0000 Access R READ PIN REGISTER Address: 0x97, Reset: 0x0000, Name: READ_PIN The READ_PIN command reads the calculated input power, PIN, from the device. Table 27. Bit Descriptions for READ_PIN Bits [15:0] Bit Name READ_PIN Settings Description Input power calculation, using VIN x IOUT, after averaging, expressed in direct format. Rev. B | Page 37 of 48 ADM1293/ADM1294 Data Sheet PMBus REVISION REGISTER Address: 0x98, Reset: 0x22, Name: PMBUS_REVISION The PMBUS_REVISION command allows the system to read the PMBus revision that the device supports. Table 28. Bit Descriptions for PMBUS_REVISION Bits [7:4] Bit Name PMBUS_P1_REVISION [3:0] PMBUS_P2_REVISION Settings 0010 0010 Description PMBus Part I Support. Revision 1.2. PMBus Part II Support. Revision 1.2. Reset 0x2 Access R 0x2 R MANUFACTURER ID REGISTER Address: 0x99, Reset: 0x494441, Name: MFR_ID The MFR_ID command returns a string identifying the manufacturer of the device. Table 29. Bit Descriptions for MFR_ID Bits [23:0] Bit Name MFR_ID Settings Description String identifying manufacturer as ADI. Reset 0x494441 Access R Reset Access R Reset 0x32 Access R MANUFACTURER MODEL REGISTER Address: 0x9A, Name: MFR_MODEL The MFR_MODEL command returns a string identifying the specific model of the device. Table 30. Bit Descriptions for MFR_MODEL Bits [79:0] Bit Name MFR_MODEL Settings Description String identifying model as ADM129x-yz, where x identifies the particular model, y identifies the particular model type, and z identifies the grade. MANUFACTURER REVISION REGISTER Address: 0x9B, Reset: 0x32, Name: MFR_REVISION The MFR_REVISION command returns a string identifying the hardware revision of the device. Table 31. Bit Descriptions for MFR_REVISION Bits [7:0] Bit Name MFR_REVISION Settings Description String identifying hardware revision in ASCII code, for example 0x32 for 2. MAXIMUM IOUT REGISTER Address: 0xD0, Reset: 0xF800, Name: MAX_IOUT The MAX_IOUT command reports the most positive IOUT value recorded, expressed in direct format. Writing a 0 with this command resets it to the default value. Table 32. Bit Descriptions for MAX_IOUT Bits [15:0] Bit Name MAX_IOUT Settings Description Reports the most positive IOUT value recorded, expressed in direct format. Writing 0 with this command resets it to the default value. Rev. B | Page 38 of 48 Reset 0xF800 Access R Data Sheet ADM1293/ADM1294 PEAK VIN REGISTER Address: 0xD1, Reset: 0x0000, Name: PEAK_VIN The PEAK_VIN command reports the most positive VIN value recorded, expressed in direct format. Writing a 0 with this command resets it to the default value. Table 33. Bit Descriptions for PEAK_VIN Bits [15:12] [11:0] Bit Name RESERVED PEAK_VIN Settings Description Always reads as 0000b. Reports the most positive VIN value recorded, expressed in direct format. Writing 0 with this command resets it to the default value. Reset 0x0 0x000 Access Reserved R PEAK VAUX REGISTER Address: 0xD2, Reset: 0x0000, Name: PEAK_VAUX The PEAK_VAUX command reports the most positive VAUX value recorded, expressed in direct format. Writing a 0 with this command resets it to the default value. Table 34. Bit Descriptions for PEAK_VAUX Bits [15:12] [11:0] Bit Name RESERVED PEAK_VAUX Settings Description Always reads as 0000b. Reports the most positive VAUX value recorded, expressed in direct format. Writing 0 with this command resets it to the default value. Reset 0x0 0x000 Access Reserved R Reset 0x00 0x1 Access Reserved RWAS POWER MONITOR CONTROL REGISTER Address: 0xD3, Reset: 0x01, Name: PMON_CONTROL The PMON_CONTROL command starts and stops the power monitor. Table 35. Bit Descriptions for PMON_CONTROL Bits [7:1] 0 Bit Name RESERVED CONVERT Settings 0 1 Description Always reads as 0000000b. Convert enable. Power monitor is not running. Power monitor is sampling. In single shot mode, this bit clears itself after one complete cycle. In continuous mode, this bit must be written to 0 to stop sampling. A rising edge on a convert (CONV) input pin sets this bit to 1. During sampling, additional rising edges on CONV are ignored. Rev. B | Page 39 of 48 ADM1293/ADM1294 Data Sheet POWER MONITOR CONFIGURATION REGISTER Address: 0xD4, Reset: 0x0714, Name: PMON_CONFIG The PMON_CONFIG command is used to configure the power monitor. Different combinations of channels can be included in the sampling round robin, and averaging can be set for different measurements. Table 36. Bit Descriptions for PMON_CONFIG Bits 15 14 Bit Name RESERVED SIMULTANEOUS Settings 0 1 [13:11] PWR_AVG 000 001 010 011 100 101 110 111 [10:8] VI_AVG 000 001 010 011 100 101 110 111 [7:6] IRANGE 00 01 10 11 5 4 RESERVED PMON_MODE 0 1 [3:2] VIN_SEL 00 01 10 11 1 VAUX_EN 0 1 0 RESERVED Description Always reads as 0. Simultaneous sampling mode enable. Simultaneous sampling disabled. Simultaneous sampling enabled. PIN averaging mode select. Disables sample averaging for power. Sets sample averaging for power to two samples. Sets sample averaging for power to four samples. Sets sample averaging for power to eight samples. Sets sample averaging for power to 16 samples. Sets sample averaging for power to 32 samples. Sets sample averaging for power to 64 samples. Sets sample averaging for power to 128 samples. VIN/VAUX/IOUT averaging mode select. Disables sample averaging for current and voltage. Sets sample averaging for current and voltage to two samples. Sets sample averaging for current and voltage to four samples. Sets sample averaging for current and voltage to eight samples. Sets sample averaging for current and voltage to 16 samples. Sets sample averaging for current and voltage to 32 samples. Sets sample averaging for current and voltage to 64 samples. Sets sample averaging for current and voltage to 128 samples. Current sense range (CSR) select. Sets current sense range to 25 mV. Sets current sense range to 50 mV. Sets current sense range to 100 mV. Sets current sense range to 200 mV. Always reads as 0. Conversion mode select. Single shot sampling. Continuous sampling. VIN Sampling mode select. VIN sampling disabled. VIN sampling as direct ADC input with full scale of 1.2 V. VIN sampling with ADC full scale of 7.4 V. VIN sampling with ADC full scale of 21 V. VAUX sampling enable. VAUX sampling disabled. VAUX sampling enabled. Always reads as 0. Rev. B | Page 40 of 48 Reset 0x0 0x0 Access Reserved RW 0x0 RW 0x7 RW 0x0 RW 0x0 0x1 Reserved RW 0x1 RW 0x0 RW 0x0 Reserved Data Sheet ADM1293/ADM1294 ALERT 1 CONFIGURATION REGISTER Address: 0xD5, Reset: 0x0000, Name: ALERT1_CONFIG The ALERT1_CONFIG command allows different combinations of faults and warnings to be configured on the GPO1/ALERT1/CONV output pin. The pin can operate in different modes, configured using the DEVICE_CONFIG command. Table 37. Bit Descriptions for ALERT1_CONFIG Bits [15:12] 11 10 9 8 7 6 5 4 3 [2:0] Bit Name RESERVED CML_ERROR_EN1 IOUT_OC_WARN_EN1 HYSTERETIC_EN1 VIN_OV_WARN_EN1 VIN_UV_WARN_EN1 VAUX_OV_WARN_EN1 VAUX_UV_WARN_EN1 RESERVED PIN_OP_WARN_EN1 RESERVED Settings Description Always reads as 0000b. Communications error enable. IOUT overcurrent warning enable. Hysteretic output enable. VIN overvoltage warning enable. VIN undervoltage warning enable. VAUX overvoltage warning enable. VAUX undervoltage warning enable. Always reads as 0. PIN overpower warning enable. Always reads as 000b. Reset 0x0 0x0 0x0 0x0 0x0 0x0 0x0 0x0 0x0 0x0 0x0 Access Reserved RW RW RW RW RW RW RW Reserved RW Reserved ALERT 2 CONFIGURATION REGISTER Address: 0xD6, Reset: 0x0000, Name: ALERT2_CONFIG The ALERT2_CONFIG command allows different combinations of faults and warnings to be configured on the GPO2/ALERT2 output pin. The pin can operate in different modes, configured using the DEVICE_CONFIG command. Table 38. Bit Descriptions for ALERT2_CONFIG Bits [15:12] 11 10 9 8 7 6 5 4 3 [2:0] Bit Name RESERVED CML_ERROR_EN2 IOUT_OC_WARN_EN2 HYSTERETIC_EN2 VIN_OV_WARN_EN2 VIN_UV_WARN_EN2 VAUX_OV_WARN_EN2 VAUX_UV_WARN_EN2 RESERVED PIN_OP_WARN_EN2 RESERVED Settings Description Always reads as 0000b. Communications error enable. IOUT overcurrent warning enable. Hysteretic output enable. VIN overvoltage warning enable. VIN undervoltage warning enable. VAUX overvoltage warning enable. VAUX undervoltage warning enable. Always reads as 0. PIN overpower warning enable. Always reads as 000b. Rev. B | Page 41 of 48 Reset 0x0 0x0 0x0 0x0 0x0 0x0 0x0 0x0 0x0 0x0 0x0 Access Reserved RW RW RW RW RW RW RW Reserved RW Reserved ADM1293/ADM1294 Data Sheet DEVICE CONFIGURATION REGISTER Address: 0xD8, Reset: 0x0000, Name: DEVICE_CONFIG The DEVICE_CONFIG command configures the GPO1/GPO2 output modes. Table 39. Bit Descriptions for DEVICE_CONFIG Bits [15:11] 10 Bit Name RESERVED PWR_HYST_EN Settings 0 1 [9:8] GPO2_MODE 00 01 10 11 7 GPO2_INVERT 0 1 [6:5] GPO1_MODE 00 01 10 11 4 GPO1_INVERT 0 1 [3:0] RESERVED Description Always reads as 0000b. Power hysteretic comparison enable. When enabled the hysteresis functions refer to power rather than current. The HYSTERETIC_EN bit also needs to be set in ALERT_CONFIG. Current hysteresis mode. Power hysteresis mode. GPO2 configuration mode. Default. GPO2 is configured to generate SMBALERTs. GPO2 can be used a general-purpose digital output pin. The GPO2_INVERT bit is used to change the output state. Reserved. Digital comparator mode. The output pin now reflects the live status of the warning or fault bit selected for the output. In effect, this is a nonlatched SMBALERT. GPO invert mode. In SMBALERT mode the output is not inverted, and active low. In GPO mode, the output is set low. In SMBALERT mode the output is inverted, and active high. In GPO mode, the output is set high. GPO1 configuration mode. Default. GPO1 is configured to generate SMBALERTs. GPO1 can be used a general-purpose digital output pin. The GPO1_INVERT bit is used to change the output state. GPO1 is configured as a convert (CONV) input pin. Digital comparator mode. The output pin reflects the live status of the warning or fault bit selected for the output. In effect, this is a nonlatched SMBALERT. GPO1 invert mode. In SMBALERT mode, the output is not inverted, and active low. In GPO mode, the output is set low. In SMBALERT mode the output is inverted, and active high. In GPO mode, the output is set high. Always reads as 0000b. Reset 0x0 0x0 Access Reserved RW 0x0 RW 0x0 RW 0x0 RW 0x0 RW 0x0 Reserved MAXIMUM PIN REGISTER Address: 0xDA, Reset: 0x8000, Name: MAX_PIN The MAX_PIN command reports the most positive PIN value recorded, expressed in direct format. Writing 0 with this command resets it to the default value. Table 40. Bit Descriptions for MAX_PIN Bits [15:0] Bit Name MAX_PIN Settings Description Reports the most positive PIN value recorded, expressed in direct format. Writing 0 with this command resets it to the default value. Rev. B | Page 42 of 48 Reset 0x8000 Access R Data Sheet ADM1293/ADM1294 READ PIN (EXTENDED) REGISTER Address: 0xDB, Reset: 0x000000, Name: READ_PIN_EXT The READ_PIN_EXT command reads the extended precision version of the calculated input power, PIN, from the device. Table 41. Bit Descriptions for READ_PIN_EXT Bits [23:0] Bit Name READ_PIN_EXT Settings Description Extended precision version of input power calculation, PIN, expressed in direct format. Reset 0x000000 Access R READ EIN (EXTENDED) REGISTER Address: 0xDC, Reset: 0x0000000000000000, Name: READ_EIN_EXT The READ_EIN_EXT command reads the extended precision version of the forward flow energy meter register, EIN, from the device. Table 42. Bit Descriptions for READ_EIN_EXT Bits [63:40] Bit Name SAMPLE_COUNT [39:24] EIN_ROLLOVER_EXT [23:0] EIN_ENERGY_EXT Settings Description These bits report the total number of PIN samples acquired and accumulated in both the forward and reverse flow energy count accumulator. Byte 7 is the high byte, Byte 6 is the middle byte, and Byte 5 is the low byte. These bits report the number of times that the forward flow energy count has rolled over. On the ADM1293-1 and ADM1294-1, the rollover counter increases by 1 each time the energy count rolls over from 0xFFFFFF to 0x000000. On the ADM1293-2 and ADM1294-2, the rollover counter increases by 1 each time the energy count rolls over from 0x7FFFFF to 0x000000. This is an unsigned 16-bit binary value. Byte 4 is the high byte, and Byte 3 is the low byte. Extended precision forward flow energy accumulator value in direct format. Byte 2 is the high byte, and Byte 0 is the low byte. On the ADM1293-1 and ADM1294-1, the data is presented as unsigned integer. On the ADM1293-2 and ADM1294-2, the data is presented in twos complement format. Reset 0x000000 Access R 0x0000 R 0x000000 R READ VAUX REGISTER Address: 0xDD, Reset: 0x0000, Name: READ_VAUX The READ_VAUX command reads the auxiliary input voltage, VVAUX, from the device. Table 43. Bit Descriptions for READ_VAUX Bits [15:12] [11:0] Bit Name RESERVED READ_VAUX Settings Description Always reads as 0000b. Voltage measurement on VAUX pin after averaging, expressed in direct format. Reset 0x0 0x000 Access Reserved R VAUX OV WARNING LIMIT REGISTER Address: 0xDE, Reset: 0x0FFF, Name: VAUX_OV_WARN_LIMIT The VAUX_OV_WARN_LIMIT command sets the overvoltage warning limit for the voltage measured on the VAUX pin. Table 44. Bit Descriptions for VAUX_OV_WARN_LIMIT Bits [15:12] [11:0] Bit Name RESERVED VAUX_OV_WARN_LIMIT Settings Description Always reads as 0000b. Overvoltage warning threshold for the VAUX pin measurement, expressed in direct format. Set these bits to the default value to disable. Rev. B | Page 43 of 48 Reset 0x0 0xFFF Access Reserved RW ADM1293/ADM1294 Data Sheet VAUX UV WARNING LIMIT REGISTER Address: 0xDF, Reset: 0x0000, Name: VAUX_UV_WARN_LIMIT The VAUX_UV_WARN_LIMIT command sets the undervoltage warning limit for the voltage measured on the VAUX pin. Table 45. Bit Descriptions for VAUX_UV_WARN_LIMIT Bits [15:12] [11:0] Bit Name RESERVED VAUX_UV_WARN_LIMIT Settings Description Always reads as 0000b. Undervoltage warning threshold for the VAUX pin measurement, expressed in direct format. Set these bits to the default value to disable. Reset 0x0 0x000 Access Reserved RW MINIMUM IOUT REGISTER Address: 0xE3, Reset: 0x7FF, Name: MIN_IOUT The MIN_IOUT command reports the most negative IOUT value recorded, expressed in direct format. Writing 0 with this command resets it to the default value. Table 46. Bit Descriptions for MIN_IOUT Bits [15:0] Bit Name MIN_IOUT Settings Description Reports the most negative IOUT value recorded, expressed in direct format. Writing 0 with this command resets it to the default value. Reset 0x7FF Access R MINIMUM PIN REGISTER Address: 0xE4, Reset: 0x7FFF, Name: MIN_PIN The MIN_PIN command reports the most negative PIN value recorded, expressed in direct format. Writing 0 with this command resets it to the default value. Table 47. Bit Descriptions for MIN_PIN Bits [15:0] Bit Name MIN_PIN Settings Description Reports the most negative PIN value recorded, expressed in direct format. Writing 0 with this command resets it to the default value. Reset 0x7FFF Access R READ EOUT (EXTENDED) REGISTER Address: 0xE5, Reset: 0x0000000000000000, Name: READ_EOUT_EXT The READ_EOUT_EXT command reads the extended precision version of the reverse flow energy meter register, EOUT, from the device. Table 48. Bit Descriptions for READ_EOUT_EXT Bits [63:40] [39:24] Bit Name SAMPLE_COUNT EOUT_ROLLOVER_EXT [23:0] EOUT_ENERGY_EXT Settings Description Duplicate of corresponding bit in READ_EIN_EXT. Reports the number of times that the reverse flow energy count has rolled over. On the ADM1293-1 and ADM1294-1, the rollover counter increases by 1 each time the energy count rolls over from 0xFFFFFF to 0x000000. On the ADM1293-2 and ADM1294-2, the rollover counter increases by 1 each time the energy count rolls over from 0x7FFFFF to 0x000000. This is an unsigned 16-bit binary value. Byte 4 is the high byte, and Byte 3 is the low byte. Extended precision reverse flow energy accumulator value in direct format. Byte 2 is the high byte, and Byte 0 is the low byte. On the ADM1293-1 and ADM1294-1, the data is presented as unsigned integer. On the ADM1293-2 and ADM1294-2, the data is presented in twos complement format. Rev. B | Page 44 of 48 Reset 0x000000 0x0000 Access R R 0x000000 R Data Sheet ADM1293/ADM1294 HYSTERESIS LOW THRESHOLD LEVEL REGISTER Address: 0xF2, Reset: 0x8000, Name: HYSTERESIS_LOW The HYSTERESIS_LOW command sets the lower threshold used to generate the hysteretic output signal that is available on a GPOx pin. Table 49. Bit Descriptions for HYSTERESIS_LOW Bits [15:0] Bit Name HYSTERESIS_LOW Settings Description Value setting the lower hysteresis threshold, expressed in direct format. Reset 0x8000 Access RW HYSTERESIS HIGH THREHSOLD LEVEL REGISTER Address: 0xF3, Reset: 0x7FFF, Name: HYSTERESIS_HIGH The HYSTERESIS_HIGH command sets the higher threshold that generates the hysteretic output signal that is available on a GPOx pin. Table 50. Bit Descriptions for HYSTERESIS_HIGH Bits [15:0] Bit Name HYSTERESIS_HIGH Settings Description Value setting the higher hysteresis threshold, expressed in direct format. Reset 0x7FFF Access RW HYSTERESIS STATUS REGISTER Address: 0xF4, Reset: 0x00, Name: STATUS_HYSTERESIS The STATUS_HYSTERESIS status register reports if the hysteretic comparison is above or below the user defined HYSTERESIS_HIGH and HYSTERESIS_LOW thresholds, the resulting hysteretic output and the IOUT_OC_WARNING status bit. Table 51. Bit Descriptions for STATUS_HYSTERESIS Bits [7:4] 3 Bit Name RESERVED IOUT_OC_WARN Settings 0 1 2 HYST_STATE 0 1 1 HYST_GT_HIGH 0 1 0 HYST_LT_LOW 0 1 Description Always reads as 0000b. IOUT overcurrent warning. No overcurrent condition on the output supply detected by the power monitor using the IOUT_OC_WARN_LIMIT command. An overcurrent condition was detected by the power monitor using the IOUT_OC_WARN_LIMIT command. Hysteretic comparison output. Comparison output low. Comparison output high. Hysteretic upper threshold comparison. Compared value is equal or below upper threshold. Compared value is above upper threshold. Hysteretic lower threshold comparison. Compared value is equal or above the lower threshold. Compared value is below the lower threshold. Rev. B | Page 45 of 48 Reset 0x0 0x0 Access Reserved R 0x0 R 0x0 R 0x0 R ADM1293/ADM1294 Data Sheet OUTLINE DIMENSIONS 4.10 4.00 SQ 3.90 PIN 1 INDICATOR 0.35 0.30 0.25 0.65 BSC 16 13 PIN 1 INDICATOR 12 1 EXPOSED PAD 2.70 2.60 SQ 2.50 4 9 FOR PROPER CONNECTION OF THE EXPOSED PAD, REFER TO THE PIN CONFIGURATION AND FUNCTION DESCRIPTIONS SECTION OF THIS DATA SHEET. 0.05 MAX 0.02 NOM COPLANARITY 0.08 0.20 REF SEATING PLANE 0.20 MIN BOTTOM VIEW 08-16-2010-C 0.80 0.75 0.70 5 8 0.45 0.40 0.35 TOP VIEW COMPLIANT TO JEDEC STANDARDS MO-220-WGGC. Figure 41. 16-Lead Lead Frame Chip Scale Package [LFCSP_WQ] 4 mm x 4 mm Body, Very Very Thin Quad (CP-16-17) Dimensions shown in millimeters 5.10 5.00 4.90 14 8 4.50 4.40 4.30 6.40 BSC 1 7 PIN 1 0.65 BSC 1.20 MAX 0.15 0.05 COPLANARITY 0.10 0.30 0.19 0.20 0.09 SEATING PLANE 8 0 COMPLIANT TO JEDEC STANDARDS MO-153-AB-1 Figure 42. 14-Lead Thin Shrink Small Outline Package [TSSOP] RU-14 Dimensions shown in millimeters Rev. B | Page 46 of 48 0.75 0.60 0.45 061908-A 1.05 1.00 0.80 Data Sheet ADM1293/ADM1294 ORDERING GUIDE Model1 ADM1293-1AACPZ ADM1293-1AACPZ-RL7 ADM1293-1BACPZ ADM1293-1BACPZ-RL7 ADM1293-1AARUZ ADM1293-1AARUZ-RL7 ADM1293-1BARUZ ADM1293-1BARUZ-RL7 ADM1293-2AACPZ ADM1293-2AACPZ-RL ADM1294-1AACPZ ADM1294-1AACPZ-RL7 ADM1294-1BACPZ ADM1294-1BACPZ-RL7 ADM1294-1AARUZ ADM1294-1AARUZ-RL7 ADM1294-1BARUZ ADM1294-1BARUZ-RL7 ADM1294-2AACPZ ADM1294-2AACPZ-RL EVAL-ADM1293EBZ EVAL-ADM1294EBZ 1 2 Temperature Range2 -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C -40C to +105C Grade A A B B A A B B A A A A B B A A B B A A Z = RoHS Compliant Part. The operation temperature is specified as ambient for ADM1293 and junction for ADM1294. Rev. B | Page 47 of 48 Package Description 16-Lead LFCSP_WQ 16-Lead LFCSP_WQ 16-Lead LFCSP_WQ 16-Lead LFCSP_WQ 14-Lead TSSOP 14-Lead TSSOP 14-Lead TSSOP 14-Lead TSSOP 16-Lead LFCSP_WQ 16-Lead LFCSP_WQ 16-Lead LFCSP_WQ 16-Lead LFCSP_WQ 16-Lead LFCSP_WQ 16-Lead LFCSP_WQ 14-Lead TSSOP 14-Lead TSSOP 14-Lead TSSOP 14-Lead TSSOP 16-Lead LFCSP_WQ 16-Lead LFCSP_WQ Evaluation Kit Evaluation Kit Package Option CP-16-17 CP-16-17 CP-16-17 CP-16-17 RU-14 RU-14 RU-14 RU-14 CP-16-17 CP-16-17 CP-16-17 CP-16-17 CP-16-17 CP-16-17 RU-14 RU-14 RU-14 RU-14 CP-16-17 CP-16-17 ADM1293/ADM1294 Data Sheet NOTES I2C refers to a communications protocol originally developed by Philips Semiconductors (now NXP Semiconductors). (c)2014-2015 Analog Devices, Inc. All rights reserved. Trademarks and registered trademarks are the property of their respective owners. D11891-0-3/15(B) Rev. B | Page 48 of 48 Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Analog Devices Inc.: ADM1294-1AARUZ ADM1293-1AARUZ EVAL-ADM1294EBZ EVAL-ADM1293EBZ ADM1294-1AACPZ ADM12931AACPZ-RL7 ADM1293-1BACPZ-RL7 ADM1293-1BARUZ ADM1293-1BARUZ-RL7 ADM1294-1AARUZ-RL7 ADM1293-1BACPZ ADM1294-1BACPZ-RL7 ADM1294-1AACPZ-RL7 ADM1293-1AACPZ ADM1293-1AARUZ-RL7 ADM1294-1BACPZ