1
Temperature Controller E5C2
DIN-sized (48 x 48 mm) Temperature
Controller With Analog Setting
Compact, low-cost Temperature Controller.
Incorporates proportional control and reset adjust-
ment function.
Incorporates a plug-in socket, thus allows to
DIN-track and flush mounting.
Ordering Information
Temperature Controllers
Setting
h
d
Indication
h
d
Control
d
Output Model
g
method method mode Thermocouple
(with sensor burnout
detection circuit)
Platinum resistance
thermometer
JPt100
Thermistor
THE
Digital
i
No indication ON/OFF Relay E5C2-R20K E5C2-R20J E5C2-R20P E5C2-R20G
g
setting PRelay E5C2-R40K E5C2-R40J E5C2-R40P ---
Note: When placing an order, specify the standard temperature range and supply voltage in addition to the model number.
(e.g., E5C2-R20K 0!C to 200!C100/110 VAC)
Accessories (Order Separately)
Name Model
Front Connecting Socket P2CF-08
Back Connecting Socket (for flush mounting) P3G-08
Watertight Cover Y92A-48N
Temperature Ranges
Input Thermocouple Platinum resistance
thermometer Thermistor (see note 2)
K(CA)
Chromel vs. alumel J(IC)
Iron vs. constantan JPt100 THE
Range !C0to200(5),
0 to 300 (10),
0 to 400 (10),
0 to 600 (20),
0 to 800 (20),
0 to 1,000 (25),
0 to 1,200 (25)
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)
--50 to 50 (2),
--20 to 80 (2),
0to50(1),
0 to 100 (2),
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)
--50 to 50 (2) (6 k"at 0!C),
0to100(2)(6k
"at 0!C),
50 to 150 (2) (30 k"at 0!C),
100 to 200 (2) (550 "at 200!C),
150 to 300 (2) (4 k"at 200!C)
!F32 to 392 (10),
32 to 572 (20),
32 to 752 (20),
32 to 1,112 (40),
32 to 1,472 (50),
32 to 1,832 (50),
32 to 2,192 (50)
32 to 392 (10),
32 to 572 (20),
32 to 752 (20)
32 to 212 (5),
32 to 392 (10) ---
Note: 1. Values in parentheses are the smallest division.
2. Values in parentheses are the thermistor resistive value.
E5C2 E5C2
2
Specifications
Ratings
Supply voltage 100/110, 200/220, 110/120, 220/240 VAC, 50/60 Hz
Operating voltage range 90% to 110% of rated supply voltage
Power consumption Approx. 2 VA
Input Thermocouple (with sensor burnout detection circuit), platinum resistance thermometer, or
thermistor
Control mode ON/OFF or P control
Setting method Analog setting
Indication method No indication
Control output Relay output: SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA)
Characteristics
Setting accuracy #2% FS max.
Hysteresis Approx. 0.5% FS (fixed)
Proportional band 3% FS (fixed)
Proportional period Approx. 20 s
Reset range (see note 1) 3% FS min.
Insulation resistance 20 M"min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts
Vibration resistance Malfunction: 10 to 55 Hz, 0.2-mm double amplitude for 10 min each in X, Y, and Z directions
Destruction: 16.7 Hz, 4-mm double amplitude for 2 hrs each in X, Y, and Z directions
Shock resistance Malfunction: 147 m/s2(15G), 3 times each in 6 directions
Destruction: 294 m/s2(30G), 3 times each in 6 directions
Life expectancy Mechanical: 10,000,000 operations min.
Electrical: 100,000 operations min. (3 A at 110 VAC, resistive load)
Ambient temperature Operating: --10!Cto55
!C (with no icing)
Ambient humidity Operating: 45% to 85%
Enclosure ratings Front panel: IEC standard IP40 (see note 2)
Terminals: IEC standard IP00
Weight Approx. 200 g (with flush-mounting adapter)
Note: 1. No reset function is incorporated by any E5C2 model with ON/OFF control.
2. The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48N.
Nomenclature
Temperature setting knob
Operation indicator
RESET shaft
No reset function is incorporated by
any E5C2 model with ON/OFF
control.
Operation Indicator
Indicator Output
Red Lit ON
Not lit OFF
E5C2 E5C2
3
Dimensions
Note: All units are in millimeters unless otherwise indicated.
93+1
0141+1
0189+1
0237+1
0285+1
0
Terminal Arrangement
(Bottom View)
Dimensions with Flush-mounting Adapter (Accessory),
and Back Connecting Socket (Sold Separately)
Panel Cutout
60 min.
60 min.
Side-by-side Mounting
of N Controllers
N23456
L
Note: 1. Recommended panel thickness is 1 to 4 mm.
2. Closeside-by-sidemountingispossible(inasingledirection).
48 x 48
44.8 x 44.8
Flush-mounting
adapter
Panel
Y92F-30 Flush-mounting adapter
P3G-08 Back con-
necting socket
Tightening screw
(96) (see note)
Note: 109 mm for US08 Back Connecting Socket
Accessories (Order Separately)
P2CF-08 Front Connecting Socket Terminal Arrangement/
Internal Connections
(Top View)
Mounting Holes
70 max.
Eight, M3.5 x 7.5 sems
Two,
4.5-dia.
holes
Two, 4.5 dia. or Two, M4
P3G-08 Back Connecting Socket (for Flush Mounting) Terminal Arrangement/
Internal Connections
(Bottom View)
27 dia.
50 max. 20 max.
Note: Can also be
mounted to a
DIN track.
E5C2 E5C2
4
Installation
Connections
Input
Connectathermocouple,theE52-THEjThermistororplatinumre-
sistancethermometertotheE5C2asshowninthefollowingillustra-
tion.
Thermocouple input
Platinum resistance
thermometer input Relay output
Thermistor input
Power supply
100/110, 200/220,
110/120, 220/240 VAC
50/60 Hz
Output
If the load circuit isaheatingcontrolsystem,besuretoconnectthe
load to terminals 4 and 5. If the load circuit is a cooling control sys-
tem, be sure to connect the load to terminals 4 and 6. If the heating
controlsystemisconnectedtoterminals 4and6orthe coolingcon-
trolsystemisconnectedtoterminals4and5,thetemperatureofthe
heating control system or cooling control system will be abnormal
and a serious accident may result.
IftheE5C2isinfrequentoperation, suchas proportionaloperation,
addanappropriateexternalrelaytotheE5C2byconsideringtheca-
pacity of the load and the life of the relay.
Power Supply
IfasinglepowersupplyisusedfortheE5C2andtheload,thesupply
voltage of thepowersupply mayvary greatly when the load isopen
or closed if the capacity of the power supply is not large enough.
Make sure that the capacity of the powersupply is large enoughso
thatthesupplyvoltagerangewillbealwaysfrom90%to110%ofthe
rated supply voltage.
The E5C2 operates at either 50 or 60 Hz.
Precautions
Mounting
Track Mounting (E5C2 with P2CF-08)
When mounting two or more E5C2 models with track-mounting
sockets,leaveaspaceofapproximately20mmonbothsidesofthe
sockets where hooks are located.
20
P2CF-08
Panel
Hook
Duct
Flush Mounting
Insert E5C2 into thesquare hole of the panel andinsert an adapter
from the back so that there will be no space between E5C2 andthe
panel. Then, secure the E5C2 with a screw.
Tightening screw
The P3G-08 can be wired in the same way as the P2CF-08.
Dismounting
Ifflushmounted,loosenthescrewoftheadapteranddisengagethe
hooks for dismounting.
Temperature Setting
DonotturnthetemperaturesettingknoboftheE5C2withexcessive
force, otherwise the stopper of the knob may break.
Others
DonotremovethehousingoftheE5C2,otherwisethehousingmay
break.
To clean the surface of the E5C2, use a soft cloth wet with neutral
detergent or alcohol. Do not use any organic solvent, such as paint
thinnerorbenzine,strongacidorstrongalkalitocleanthesurfaceof
theE5C2,otherwisethesurfaceoftheE5C2willbecomedamaged.
OMRON Corporation
Systems Components Division
28th Fl., Crystal Tower Bldg.
1-2-27, Shiromi, Chuo-ku,
Osaka 540 Japan
Phone: 06-949-6012 Fax: 06-949-6021
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. H081-E1-1 In the interest of product improvement, specifications are subject to change without notice.
Printed in Japan
0496-1M (0496) a