Data Sheet ES001-0108 Issue 1
Not to be used for installation purposes.
Page 1 of 2
The Edwards 125 Class Strobe beacons are UL and cUL listed signaling devices, available in two versions, normal light
output and high light output. Both versions feature a corrosion resistant Type 4X enclosure and can be panel or conduit
mounted. The base is manufactured from a polycarbonate/ABS blend, and the lens is made of shatter resistant
polycarbonate. Both the normal light output and high light output beacons are available with either a black or gray
base, and amber, blue, clear, green or red lens.
The 125 Class Strobe beacons can be mounted on 1/2" or 3/4" NPT conduit using a 1/2" internal or 3/4" external conduit
hub that comes with the unit. It can also be panel-mounted using the mounting gasket provided with the unit. When panel-
mounting the 125 Class Strobe, the surface and construction details of the panel must be taken into consideration to
ensure the integrity of the outdoor, NEMA 4X rating is fully maintained.
125 Class Strobe Features
• High Light Output available in 120V AC
Normal Light Output available in 12-48V DC, 120V AC
or 240V AC
• Available with gray or black base
• Option for panel or conduit mounting
Available in High Light Output or Normal Light Output
versions
• Available with amber, blue, clear, green or red lens
• -31°F to 150°F (-35°C to 66°C) operating temperature
• Protective wire guard available, Cat. No. 125GRD
125 Class
Strobe Beacons
for NEMA 4X Applications
125 Class
Strobe Beacons
Description
Strobe
Output Cat. No. Base Color LED Colors
Operating
Voltage Current
Replacement
Lens
Replacement
Strobe Tube
Strobe Beacons in NEMA
4X Enclosure
High
Output
300,000 peak
candlepower**
125STRH*120A Gray Amber, Blue, Clear,
Green, Red
120V AC
50/60 Hz 0.120 A 125L* 91B-ST
125STRH*120AB Black Amber, Blue, Clear,
Green, Red
120V AC
50/60 Hz 0.120 A 125L* 91B-ST
Normal
Output
175,000 peak
candlepower
125STRN*1248D Gray Amber, Blue, Clear,
Green, Red 12-48V DC 0.350 A 125L* 114-ST
125STRN*120A Gray Amber, Blue, Clear,
Green, Red
120V AC
50/60 Hz 0.100 A 125L* 91B-ST
125STRN*240A Gray Amber, Blue, Clear,
Green, Red
240V AC
50/60 Hz 0.050 A 125L* 91B-ST
125STRN*1248DB Black Amber, Blue, Clear,
Green, Red 12-48V DC 0.350 A 125L* 114-ST
125STRN*120AB Black Amber, Blue, Clear,
Green, Red
120V AC
50/60 Hz 0.100 A 125L* 91B-ST
125STRN*240AB Black Amber, Blue, Clear,
Green, Red
240V AC
50/60 Hz 0.050 A 125L* 91B-ST
Data Sheet ES001-0108 Issue 1
Not to be used for installation purposes.
Page 2 of 2
41 Woodford Avenue
Plainville, CT 06062
1.800.336.4206
www.edwardssignaling.com
© Copyright 2010 Edwards Signaling
*Letter in this position designates lens color: A - amber, B - blue, C - clear, G - green, or R - red
**Maximum capacitor operating temperature (Tc) is 185°F (85°C).
Dimensional Drawings
Agency Approvals
Gasket (provided for use
when direct panel mounting)
Locknut - 1.3625" O.D. (provided
for use when direct panel
mounting)
3.25"
(82.6mm)
3.875"
(98.4mm)
Double threaded for
panel mounting or
1/2" internal or
3/4" external
conduit mounting
1638 Listed Listed
NEMA 4X
Enclosure
Listed