https://www.phoenixcontact.com/us/products/2986025 Safety module - PSR-SPP- 24DC/TS/M - 2986025 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Freely configurable safety module, with 20 safe inputs and 4 safe outputs, 4 signal, 2 clock, and 2 ground switching outputs; can be extended via additional I/O modules, up to SILCL 3, Cat. 4/PL e, SIL 3, EN 50156, plug-in spring-cage terminal block The figure shows a version with a screw connection Your advantages Freely configurable safety module for monitoring emergency stops, safety doors, light grids, etc. With 20 safe inputs, 4 safe outputs, 4 alarm outputs, and 2 clock outputs on a design width of just 67.5 mm Multifunctional use for a wide range of safety functions Including IFS-CONFSTICK memory stick for easily storing and saving the configuration Easy graphical configuration with the SAFECONF software Easy graphical configuration instead of complex programming Quick startup thanks to comprehensive simulation and test functions Option for connecting fieldbus gateways for diagnostics and signaling functions Up to Cat. 4/PL e according to ISO 13849-1, SILCL 3 according to IEC 62061, SIL 3 according to IEC 61508 EN 50156 Safe and standard extension via INTERFACE DIN rail TBUS Flexible extension with safe inputs and outputs Key Commercial Data Packing unit 1 pc GTIN GTIN 4046356345897 Weight per Piece (excluding packing) 400.000 g Custom tariff number 85371098 Country of origin Germany 04/02/2019 Page 1 / 11 https://www.phoenixcontact.com/us/products/2986025 Safety module - PSR-SPP- 24DC/TS/M - 2986025 Technical data Note Utilization restriction EMC: class A product, see manufacturer's declaration in the download area Dimensions Width 67.5 mm Height 112 mm Depth 114.5 mm Ambient conditions Ambient temperature (operation) -20 C ... 55 C Ambient temperature (storage/transport) -20 C ... 70 C Max. permissible relative humidity (operation) 75 % (On average, 85 % occasionally) Max. permissible humidity (storage/transport) 75 % (On average, 85 % occasionally) Air pressure (operation) 70 kPa ... 108 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 66 kPa ... 108 kPa (up to 3500 m above sea level) Maximum altitude max. 2000 m (See Appendix "Using PSR-TRISAFE modules at altitudes greater than 2000 m above sea level") Power supply Rated control circuit supply voltage US 24 V DC (A1/A2) 18 V DC ... 30 V DC (Incl. all tolerances, incl. residual ripple) Rated control supply current IS typ. 110 mA Limiting continuous current max. 6 A (For looped-through current paths A1/A1 and A2/A2) Filter time typ. 20 ms (Load-dependent, in the event of voltage dips at US) Status display 3x LED green, 1x LED red Protective circuit Yes, within the scope of the operating voltage limits Digital inputs Description of the input Digital, type HTL Number of inputs 10 (Two-channel, up to SIL 3) 20 (Single-channel, up to SIL 2) Input voltage range "0" signal 0 V DC ... 5 V DC (for safe Off) Input voltage range "1" signal 11 V DC ... 30 V DC Current consumption typ. 4 mA Cable length max. 2000 m Status display 20 x LED green (1 LED per input) Digital outputs Number of outputs 4 (Safe semiconductor outputs, up to Cat. 4 in accordance with EN ISO 13849-1) 04/02/2019 Page 2 / 11 https://www.phoenixcontact.com/us/products/2986025 Safety module - PSR-SPP- 24DC/TS/M - 2986025 Technical data Digital outputs 2 (Ground switching outputs) Nominal output voltage 24 V DC (Supply via 24 V/0 V) Nominal output voltage range 18 V DC ... 30 V DC (Incl. all tolerances, incl. residual ripple) Limiting continuous current 2 A (Per channel, see Derating) 2 A (Total current of all outputs) Output voltage < 5 V (Low state) Leakage current max. 2 mA Max. capacitive load max. 1 F (Electronic components) Max. inductive load See "Protective circuit" Test pulses < 1 ms Note on protection circuit Yes, within the scope of the operating voltage limits Short-circuit protection Yes Status display 4 x LED green (1 LED per output) Clock outputs Output description Digital Number of outputs 2 Voltage 24 V DC (Supply via 24 V/0 V) Limiting continuous current 100 mA Test pulses < 1 ms Short-circuit protection Yes Alarm outputs Output description Digital Number of outputs 4 Voltage 24 V DC (Supply via 24 V/0 V) Limiting continuous current 100 mA Short-circuit protection Yes Times Response time max. 30 ms (plus response time of PSR-TS-SDOR4) Recovery time < 10 s General Nominal operating mode 100% operating factor Net weight 154 g Mounting position On horizontal DIN rail Mounting type DIN rail mounting Degree of protection IP20 04/02/2019 Page 3 / 11 https://www.phoenixcontact.com/us/products/2986025 Safety module - PSR-SPP- 24DC/TS/M - 2986025 Technical data General IP54 Min. degree of protection of inst. location IP54 Housing material Polyamide PA non-reinforced Housing color yellow Number of possible extension modules 1 (Max. continuous current via PSR-TBUS: 4 A) Number of possible safe extension modules 10 (Max. continuous current via PSR-TBUS: 4 A) Connection data Connection method Spring-cage connection pluggable Yes Conductor cross section solid min. 0.2 mm Conductor cross section solid max. 1.5 mm Conductor cross section flexible min. 0.2 mm Conductor cross section flexible max. 1.5 mm Conductor cross section AWG min. 24 Conductor cross section AWG max. 16 Stripping length 8 mm Safety-related characteristic data Stop category 0 Designation IEC 61508 - High demand Safety Integrity Level (SIL) 2 (1-channel parameterization) 3 (2-channel parameterization) Designation IEC 61508 - Low demand Safety Integrity Level (SIL) 2 (1-channel parameterization) 3 (2-channel parameterization) Designation EN ISO 13849 Performance level (PL) d (1-channel parameterization) e (2-channel parameterization) Category 2 (1-channel parameterization) 4 (2-channel parameterization) Designation EN 62061 Safety Integrity Level Claim Limit (SIL CL) 2 (1-channel parameterization) 3 (2-channel parameterization) Designation EN 50156 Safety Integrity Level (SIL) max. 3 (Reference IEC 61508) Standards and Regulations Designation Air clearances and creepage distances between the power circuits 04/02/2019 Page 4 / 11 https://www.phoenixcontact.com/us/products/2986025 Safety module - PSR-SPP- 24DC/TS/M - 2986025 Technical data Standards and Regulations Standards/regulations DIN EN 50178 Degree of pollution 2 Overvoltage category III Vibration (operation) 2g Shock (operation) 10g (t = 11 ms, three shocks in each space direction) 10g (t = 16 ms, continuous shock, 1000 shocks in each space direction) Environmental Product Compliance REACh SVHC Lead 7439-92-1 China RoHS Environmentally friendly use period: unlimited = EFUP-e No hazardous substances above threshold values Drawings Circuit diagram A1 A2 PSR-TBUSbus connectors PSR-TBUSbus connectors INTERFACE-PSR use only PSR-TBUS INTERFACE-PSR use only PSR-TBUS INTERFACE-PSR use only PSR-TBUS TBUS NON-SAFE POWER 24V DC T0 T0 T1 T1 TEST PULSE OUTPUT I0 I1 I19 M0 M1 M2 M3 SAFE INPUT MONITORING OUTPUT PSR-TBUS SAFE Connection diagram LOGIC POWER 24V DC SAFE OUTPUT USB CONF STICK 24V 0V O0 O1 O2 O3 O0- O1- PSR-TBUSbus connectors PSR-TBUS DIN rail connectors are used for cross-wiring between the modules. Total current Output Ox [A] Diagram 2 1,5 1 0,5 0 0 25 30 35 40 45 50 55 60 Ambient temperature [C] 04/02/2019 Page 5 / 11 https://www.phoenixcontact.com/us/products/2986025 Safety module - PSR-SPP- 24DC/TS/M - 2986025 Application drawing PSR-TBUS SAFE TBUS NON-SAFE A1 A1 A2 A2 24V 0V O0O1T0 T0 T1 T1 M0 M1 M2 M3 24V DC I0 I1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12 I13 I14 I15 I16 I17 I18 I19 O0 O1 O2 O3 TRISAFE-M S1 K2 K1 K1 K2 S2 0V Classifications eCl@ss eCl@ss 4.0 27371102 eCl@ss 4.1 27371102 eCl@ss 5.0 27371901 eCl@ss 5.1 27371900 eCl@ss 6.0 27371800 eCl@ss 7.0 27371819 eCl@ss 8.0 27371819 eCl@ss 9.0 27371819 ETIM ETIM 2.0 EC001449 ETIM 3.0 EC001449 ETIM 4.0 EC001449 ETIM 5.0 EC001449 ETIM 6.0 EC001449 UNSPSC UNSPSC 6.01 30211901 UNSPSC 7.0901 39121501 04/02/2019 Page 6 / 11 https://www.phoenixcontact.com/us/products/2986025 Safety module - PSR-SPP- 24DC/TS/M - 2986025 Classifications UNSPSC UNSPSC 11 39121501 UNSPSC 12.01 39121501 UNSPSC 13.2 39121501 Approvals Approvals Approvals UL Listed / cUL Listed / Functional Safety / cULus Listed Ex Approvals Approval details UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324 cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324 Functional Safety cULus Listed 01/205/5151.03/17 Accessories Accessories Device parameterization 04/02/2019 Page 7 / 11 https://www.phoenixcontact.com/us/products/2986025 Safety module - PSR-SPP- 24DC/TS/M - 2986025 Accessories Configuration package - SAFECONF - 2986119 Configuration software for SafetyBridge technology and PSR-TRISAFE modules, connecting cable for PSR-TRISAFE DIN rail connector DIN rail bus connectors - ME 22,5 TBUS 1,5/ 5-ST-3,81 GN - 2707437 DIN rail connector, nominal current (Ex): 8 A, nominal voltage (Ex): 125 V, number of positions: 5, pitch: 3.81 mm, Articles with gold-plated contacts, bus connectors for connecting with electronic housings DIN rail bus connectors - PSR-TBUS - 2890425 DIN rail connector for safety switching devices, for supplying/controlling/monitoring (depending on the module) Filter terminal block Filter terminal block - PSR-FTB/20/86 - 2904477 Terminal block for filtering test pulses from safe semiconductor outputs with adjustable filter values (20 F/86 F), as well as for EMC filtering of 24 V signals up to an amperage of 2 A. Filter terminal block - PSR-FTB/1.5/11.5 - 2904476 Terminal block for filtering test pulses from safe semiconductor outputs with adjustable filter values (1.5 F/11.5 F), as well as for EMC filtering of 24 V signals up to an amperage of 2 A. 04/02/2019 Page 8 / 11 https://www.phoenixcontact.com/us/products/2986025 Safety module - PSR-SPP- 24DC/TS/M - 2986025 Accessories Gateways/Proxies Data interface - EM-CAN-GATEWAY-IFS - 2901504 (R) Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via CANopen . The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Data interface - EM-MODBUS-GATEWAY-IFS - 2901528 Gateway for the connection of up to 32 INTERFACE system devices via Modbus/TCP to a higher-level controller. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Data interface - EM-DNET-GATEWAY-IFS - 2901529 Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via DeviceNetTM. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Data interface - EM-ETH-GATEWAY-IFS - 2901988 Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via EtherNet/IPTM. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Data interface - EM-PNET-GATEWAY-IFS - 2904472 Gateway for the connection of up to 32 INTERFACE system devices via PROFINET to a higher-level controller. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. 04/02/2019 Page 9 / 11 https://www.phoenixcontact.com/us/products/2986025 Safety module - PSR-SPP- 24DC/TS/M - 2986025 Accessories Data interface - EM-PB-GATEWAY-IFS - 2297620 Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via PROFIBUS DP. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Data interface - EM-RS232-GATEWAY-IFS - 2901526 Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via Modbus/RS-232. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Data interface - EM-RS485-GATEWAY-IFS - 2901527 Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via Modbus/RS-485. The INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided. Memory block Memory block - IFS-CONFSTICK - 2986122 Multi-functional memory block for the INTERFACE systemf for easy storage and backup of the configuration. Copy and delete station - COPYSTATION - IFS - 2901985 Copy and delete station for IFS-CONFSTICK memory modules for copying data from a master stick to up to four slave sticks and for deleting data on one ore more slave sticks, connection via USB/mini USB cable. 04/02/2019 Page 10 / 11 https://www.phoenixcontact.com/us/products/2986025 Safety module - PSR-SPP- 24DC/TS/M - 2986025 Accessories Programming cable USB cable - CABLE-USB/MINI-USB-3,0M - 2986135 USB connecting cable: USB plug type A to USB plug type Mini-B; length: 3 m Starter kit Starter kit - PSR-TRISAFE STARTER KIT - 2986300 STARTER kit for the PSR-TRISAFE safety module consisting of: PSR-TRISAFE demoboard (with inputs & outputs), SAFECONF CD, Quick Start Guide, USB cable (3m) , voltage supply with international connector adapters and package inserts. Phoenix Contact 2019 (c) - all rights reserved http://www.phoenixcontact.com 04/02/2019 Page 11 / 11